ProtectONE® T Caisson de désenfumage 11039535 ProtectONE® TR 355 1V
Ventilateurs de désenfumage
Description
ProtectONE® TR 1V is an F400-120 single-speed smoke extraction unit designed for tertiary and industrial premises. It is equipped with a belt-driven reaction impeller. Its ProtectONE® Adapt adjustment device allows for simple extraction flow rate adjustment in all circumstances.
PLUS PRODUIT
- Easy flow rate adjustment with the exclusive ProtectONE® Adapt device.
- Fully demountable as standard (except for insulated models).
- Thermal insulation for installation in technical rooms.
- Reaction impeller: low variation in flow rate even when pressure drops vary.
RÉGLEMENTATIONS & CONFORMITÉ(S)
- PV CE Number: 1812-CPR-1548
Principes de fonctionnement
Upon command from the CMSI, the ProtectONE®T smoke extraction unit is activated in smoke extraction mode by the relay control unit, enabling smoke extraction. The control unit then switches it to "fault" mode, followed by "standby" mode.
Domaines d'application
New construction, Renovation, Tertiary premises
Mise en oeuvre
- Installation indoors or outdoors.
- For indoor installation: opt for the thermo-acoustic insulation option (EN 12101-3).
- For outdoor installation: fit a rain guard + grille.
- Proximity switch supplied mounted and wired with position contacts.
Caractéristiques principales
- Compliant with CE marking 1812-CPR-1548.
- EFECTIS F400-120 approved according to EN12101-3.
- NF conformity of the relay control unit (NF S61-937-1, NFS61937-9, NF S37).
- Compliant with European eco-design regulation (No. 1253/2014).
- Belt-driven extraction unit (pulley-belt system).
- 8 unit models for flow rates from 1,000 to 35,000 m³/h.
- 1-speed motorizations from 1.1 kW to 22 kW.
- Balanced reaction impeller.
- Variable pulley.
- Class F, IP55 electric motor.
- Standard demountable casing, galvanized steel.
- Motor access face modifiable on-site.
- Factory-fitted proximity switch.
- Integrated flow rate adjustment device: ProtectONE® Adapt (patented system), exclusive to ALDES (optional).
- ProtectONE® TR 1V enables extraction of:
- Smoke and hot gases in case of fire in all tertiary buildings.
- Stale air in tertiary and industrial premises.
- Pollutants in professional kitchens.
Caractéristiques complémentaires
- Accessories:
- Square/circular plate for adaptation to suction.
- Anti-volatile rain guard at discharge.
- Flexible rectangular and circular collar.
- Flexible rectangular-to-circular transformation at discharge.
- Anti-vibration mounts.
- Non-return damper.
- Rain guard + grille.
- Discharge flange.
- AXONE 1V relay control unit, 1V soft start.
- AXONE 2V relay control unit, smoke extraction and smoke extraction+comfort.
- Available options:
- "All-in-One" solution: relay control unit + switch + pressure switch factory-fitted and wired.
- Choice of motor access face.
- Horizontal or vertical discharge.
- Thermo-acoustic insulation approved to 12101-3 for installation in technical rooms.
- Variable pulley.
- ProtectONE® Adapt (patented system): rapid flow rate adjustment.
Accessoires
Designations | References |
---|---|
Grille de rejet vertical ProtectONE® T 355 | 11039625 |
Raccord souple - Ø 630 | 11096942 |
Support antivibratile 6 pièces | 11039348 |
MS RECT ASPI.225 RFLT.355 PROTECTONE T | 11039566 |
TRANS REC.CIR ASP D630 355 PROTECTONE T | 11039575 |
PARE-PLUIE.GRILLE 355 PROTECTONE T | 11039585 |
BRIDE REFLT 355 PROTECTONE T | 11039595 |
TRANSFO.SOUPL.REFOUL.355 PROTECTONE T | 11039605 |
ANTI-RET 355 PROTECTONE T | 11039615 |
Options
Designations | Références |
---|---|
base | |
TOUT EN UN 1V<13kW | 1V<13KW |
TOUT EN UN 1V<23kW | 1V<23KW |
TOUT EN UN 1V<9kW | 1V<9KW |
5.5kW 1V 2P | 5.5/2P |
7.5kW 1V 2P | 7.5/2P |
Bride de raccordement | BRIDE2 |
Isolation thermique | ISOLB |
Pare pluie ProtectOne | PPTATR |
Pressostat | PRESSD |
Poulie variable | PVAR5 |
Protectone Adapt | VOLET2 |
Données générales
Références | Type de moteur | Type de roue |
---|---|---|
11039535 | AC | Réaction |
Données dimensionnelles
Références | A (mm) | A.R (mm) | B (mm) | B.R (mm) | C (mm) | D (mm) | E (mm) | F (mm) | G (mm) | H (mm) |
---|---|---|---|---|---|---|---|---|---|---|
11039535 | 1467 | 550 | 1092 | 43 | 1011 | 794 | 430 | 155 | 800 | 455 |
Diagrams showing dimensions and profiles of the unit.
Encombrement (mm) - vue de profil
Encombrement (mm) - vue de dessus
Encombrement (mm) - vue de face
Données électriques
Références | Tension (V) | Intensité max (A) | Intensité nominale (A) | Id/In | Nombre de pôles | Puissance (kW) | Caractéristiques électriques |
---|---|---|---|---|---|---|---|
11039535 | 400 | 7-7,2-7,5(2P)/7,8(4P) | 2/4 | 4-5,5-7,5 |
Installation
Diagrams illustrating the installation of accessories and the unit.
Schéma en vue de dessus, avec accès gauche
Schéma en vue de dessus, avec accès droit
Courbes
Performance curves for the ProtectONE® TR 355 - 1V unit, showing Total Pressure (Ptot) in Pascals (Pa) against flow rate (Q) in m³/h and m³/s.
Caractéristiques aérauliques ProtectONE® TR 355 - 1V
Curves according to NF EN ISO 5801:
- Suction connected, free discharge.
- Ptot: Total pressure.
- Pd asp.: Dynamic pressure in the duct at suction.
- AP rfit connected: pressure gain with connected discharge instead of free discharge.
- Refer to ProtectONE TA 225 for curve usage.
For more information, contact your Aldes advisor.