Aldes ProtectONE® TR 250 1V Smoke Extraction Unit
Model: 11039532
Product Overview
The ProtectONE® TR 1V is a smoke extraction unit designed for tertiary and industrial buildings. It is F400-120 certified and features a belt-driven reaction impeller. The unit is equipped with the exclusive ProtectONE® Adapt system for easy airflow adjustment.
Key Features & Benefits
- Easy Airflow Adjustment: Features the exclusive ProtectONE® Adapt system for simple airflow regulation.
- Fully Demountable: Standard feature for most models, facilitating installation and maintenance.
- Thermal Insulation: Available option for installation in technical rooms.
- Reaction Impeller: Ensures stable airflow even with varying pressure drops.
- Versatile Applications: Suitable for new constructions, renovations, and tertiary/industrial premises.
- Regulatory Compliance: CE marked (1812-CPR-1548), EFECTIS F400-120 approved (EN12101-3), NF certified control box, and compliant with European eco-design regulations (No. 1253/2014).
Operational Principle
Upon command from the fire safety system (CMSI), the ProtectONE® T unit is activated in smoke extraction mode via the relay control box. The control box then switches the unit to 'fault' mode and subsequently to 'standby' mode.
Applications
- Smoke and hot gas extraction in tertiary buildings during fire incidents.
- Extraction of stale air in tertiary and industrial premises.
- Pollutant extraction from professional kitchens.
Installation & Configuration
The unit can be installed indoors or outdoors. For indoor installations, thermal-acoustic insulation is recommended. For outdoor installations, a rain guard and grille are advised. A proximity switch is supplied pre-wired with position contacts.
Technical Specifications
Dimensions (mm)
Reference | A | A.R | B | B.R | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|---|---|---|
11039532 | 1152 | 400 | 792 | 43 | 791 | 619 | 319 | 145 | 600 | 324 |
Electrical Data
Reference | Voltage (V) | Max Current (A) | Nominal Current (A) | Id/In | Number of Poles | Power (kW) | Characteristics |
---|---|---|---|---|---|---|---|
11039532 | 400 | 3.5-5.0-6.5 | 3.2-4.6-5.9 | 7-6.6-7.5 | 2 | 1.5-2.2-3 | AC |
Performance Curves
The performance curves illustrate the relationship between airflow (Q) and total pressure (Ptot) for different power ratings (1.5 kW, 2.2 kW, 3 kW). These curves are based on NF EN ISO 5801 standards and consider different installation configurations such as free discharge and ducted discharge.
Curve Definitions:
- Q (m³/s): Airflow rate in cubic meters per second.
- Ptot (Pa): Total pressure in Pascals.
- Pd asp.: Dynamic pressure in the duct at the suction point.
- AP Rfit raccordé: Pressure gain with a ducted discharge instead of free discharge.
Refer to ProtectONE TA 225 for detailed explanations of the curves.
Accessories & Options
Available Accessories
- Square/circular plate for adaptation to suction.
- Anti-volatile rain guard for discharge.
- Flexible rectangular and circular sleeve.
- Flexible rectangular/circular transformation for discharge.
- Anti-vibration mounts.
- Rain guard + grille.
- Discharge flange.
- AXONE 1V relay control box (standard start, progressive start).
- AXONE 2V relay control box (smoke extraction and smoke extraction + comfort).
Available Options
- 'All-in-One' Solution: Relay control box, circuit breaker, and pressure switch pre-mounted and wired.
- Choice of motor access panel.
- Horizontal or vertical discharge.
- Thermal-acoustic insulation (certified 12101-3) for technical room installation.
- Variable pulley.
- ProtectONE® Adapt (patented system): rapid airflow adjustment.
General Data
Reference | Motor Type | Impeller Type |
---|---|---|
11039532 | AC | Reaction |