ProtectONE® T TA 250 2V BI Smoke Extraction Unit
Model: 11039522
Product Overview
The ProtectONE® TA 2V BI is a smoke extraction unit rated F400-120, designed for tertiary and industrial applications. It features a belt-driven centrifugal impeller and the exclusive ProtectONE® Adapt system for easy airflow adjustment.
Key Features & Benefits
- Easy airflow adjustment with the exclusive ProtectONE® Adapt system (patented).
- Fully demountable design as standard.
- Thermal insulation for installation in technical rooms.
- Compliant with CE marking (1812-CPR-1548).
- EFECTIS agrément F400-120 according to EN12101-3.
- NF certification for the relay control unit (NF S61-937-1, NF S61-937-9, NF 537).
- Belt-driven centrifugal extraction fan.
- Available in 9 models for airflow rates from 1,000 to 40,000 m³/h.
- Two-speed motor options with independent windings, from 1.1 kW to 20 kW.
- Balanced centrifugal impeller.
- Variable pulley.
- Class F, IP55 electric motor.
- Demountable galvanized steel casing as standard.
- Motor access panel can be modified on-site.
- Factory-fitted proximity switch with position contacts.
Operational Principle
Upon command from the fire safety system (CMSI), the ProtectONE® T unit is activated in smoke extraction mode via the relay control unit. The control unit then switches the unit to 'fault' mode and subsequently to 'standby' mode.
Application Areas
- New construction
- Renovation
- Tertiary sector premises
- Industrial premises
Installation & Implementation
- Can be installed indoors or outdoors.
- For indoor installation, thermal-acoustic insulation (EN 12101-3) is recommended.
- For outdoor installation, a rain guard + grille is required.
- Proximity switch is supplied pre-mounted and wired with position contacts.
Complementary Features & Options
Accessories
- Square/circular flange for connection to ductwork.
- Anti-volatile rain guard for discharge.
- Flexible rectangular and circular duct connectors.
- Flexible rectangular-to-circular transition for discharge.
- Anti-vibration mounts.
- Non-return damper.
- Rain guard + grille.
- Discharge flange.
- AXONE 1V relay control unit (with soft start).
- AXONE 2V relay control unit (for smoke extraction and smoke extraction+comfort).
Available Options
- 'All-in-One' solution: Relay control unit, switch, and pressure switch pre-mounted and wired at the factory.
- Choice of motor access panel orientation.
- Horizontal or vertical discharge.
- Thermal-acoustic insulation certified to EN 12101-3 for technical room installations.
- Variable pulley.
- ProtectONE® Adapt (patented system) for rapid airflow adjustment.
Dimensional Data
The following table and diagrams provide dimensional information for the ProtectONE® TA 250 2V BI unit.
Reference | A (mm) | A.R (mm) | B (mm) | B.R (mm) | C (mm) | D (mm) | E (mm) | F (mm) | G (mm) | H (mm) |
---|---|---|---|---|---|---|---|---|---|---|
11039522 | 1152 | 400 | 792 | 43 | 791 | 619 | 319 | 145 | 600 | 324 |
Diagrams illustrating front, top, and side views with key dimensions are provided.
Electrical Characteristics
Reference | Voltage (V) | Max Current (A) | Nominal Current (A) | Id/In | Number of Poles | Power (kW) |
---|---|---|---|---|---|---|
11039522 | 400 | 4.01/1.78-5.53/2.72 | 3.65/1.62-5.03/2.48 | 5.5/4.5-6/5.5 | 4/6 | 1.5/0.37, 2.2/0.7 |
Performance Curves
The performance curves illustrate the relationship between airflow (Q) and total pressure (Ptot) for different motor power ratings (1.1 kW, 1.5 kW, 2.2 kW). These curves are based on NF EN ISO 5801 standards for ducted suction and free discharge, with notations for total pressure (Ptot), dynamic pressure at suction (Pd asp.), and pressure gain with ducted discharge (AP rflt. raccordé).
Note: Refer to ProtectONE TA 225 for curve usage.
Contact Information
For more information, please contact your Aldes advisor.
Aldes reserves the right to make technical modifications to its products. Information is non-contractual.