R. STAHL 9176/10-16-00k: Loop-Powered Binary Output for Ex i Field Circuits

Article Number: 222183

Product Overview

The R. STAHL 9176/10-16-00k is a loop-powered binary output module designed for the intrinsically safe operation of Ex i solenoid valves, signal lamps, or horns. This device does not require a separate auxiliary power supply, as it is powered via the control current circuit. The intrinsically safe outputs are galvanically isolated from the inputs. Two-channel variants offer reduced space requirements and feature galvanically isolated channels.

Technical Data

Explosion Protection

T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C
Parameter Value
Explosive Atmosphere (Zones) ?, 0, 1, 2, 20, 21, 22
Ex Interface Zone IECEx BVS 13.0012 X
IECEx Gas Explosion Protection Ex nA [ia Ga] IIC T4 Gc
IECEx Dust Explosion Protection [Ex ia Da] IIIC
ATEX Gas Explosion Protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX Dust Explosion Protection II (1) D [Ex ia Da] IIIC
FM16US0122X FM16US0122X
FM16CA0067X FM16CA0067X
cFM Marking Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Temperature Rating
Certifications ATEX (BVS), Brazil (ULB), IECEx (BVS), Canada (FM), Korea (KTL), SIL (exida), USA (FM), People's Republic of China (NEPSI)
Marine Approval CCS, EU RO MR (DNV)
Declarations of Conformity ATEX (EUK), People's Republic of China (CCC)

Safety-Related Data

Parameter Value
Maximum Voltage Uo 27.6 V
Max. Current Io (Ex ia) 110 mA
Max. Current I (Ex ib) 50 mA
Maximum Power Po 760 mW
Max. external capacitance C. for IIC 0.085 μF
Max. external inductance L. for IIC 1.2 mH
Max. external capacitance C. for IIB 0.667 μF
Max. external inductance L. for IIB 9 mH
Internal Capacitance C 1.1 nF
Internal Inductance L Negligible
Safety-Related Voltage Max. 253 V

Electrical Data

Parameter Value
Number of Channels 1
Auxiliary Power None
Auxiliary Power Consumption 0.5 W + (Ia x 37 mW / mA)
Reverse Polarity Protection Yes
Galvanic Isolation Test Voltage (per norm) EN IEC 60079-11, EN 50178
Isolation Voltage Input to Input 350 V AC
Input Voltage for ON 18 - 31.2 V
Input Voltage for OFF 0 - 5 V
Control Power PE 0.5 W + (Ia x 37 mW / mA) (where Ia = max. required output current)
Output Open Circuit Voltage U 25 V
Max. Output Current Ia max 35 mA
Output Internal Resistance R₁ 250 Ω
Output Ripple Voltage < 100 mV
Output Switching Frequency ≤ 10 Hz
Switching Delay ON/OFF ≤ 50 ms
Switching Delay OFF/ON ≤ 18 ms
Output State Indicator Yellow LED "OUT"

Output Characteristic Curve

The diagram shows the output characteristic curve for 9175/.0-16-11 and 9176/.0-16-00. The X-axis represents current in mA, and the Y-axis represents voltage in V. The curve illustrates the relationship between output current and voltage, with specific operating conditions noted for different ambient temperatures.

Conditions:

Environmental and Mechanical Data

Environmental Conditions

Parameter Value
Ambient Temperature (Single Device) -20 °C ... 70 °C
Ambient Temperature (Group Mounting) -20 °C ... 60 °C
Ambient Temperature (Single Device, Fahrenheit) -4 °F ... +158 °F
Ambient Temperature (Group Mounting, Fahrenheit) -4 °F ... +140 °F
Storage Temperature -40 °C ... 80 °C (-40 °F ... +176 °F)
Maximum Relative Humidity 95%
Usage at Altitude < 2000 m
Electromagnetic Compatibility Tested according to standards and regulations: EN 61326-1 Industrial Environment; NAMUR NE 21

Mechanical Data

Parameter Value
Housing Type (IP) IP30
Terminal Type (IP) IP20
Flame Retardancy (UL 94) VO
Housing Material Polyamide
Mounting Width 17.6 mm (0.69 in)
Height 114.5 mm (4.51 in)
Length 128 mm (5.04 in)
Weight 180 g (0.4 lb)

Mounting / Installation

Parameter Value
Mounting Type DIN rail NS35/15, NS35/7.5
Mounting Position Vertical, Horizontal
Connection Type Spring clamp terminal
Conductor Cross-Section (Solid, min./max.) 0.2 mm² ... 2.5 mm²
Conductor Cross-Section (Flexible, min./max.) 0.2 mm² ... 2.5 mm²
Conductor Cross-Section AWG 24 ... 14

Diagrams and Connections

The document includes a technical drawing illustrating the connection between an Ex device (field device) in Zone 0/1 and a safe area (Zone 2) using the ISpac isolating transducer. It also shows a dimensional drawing with all measurements in mm [in].

Accessories and Spare Parts

Accessories:

Spare Parts - Screw Terminals:

Spare Parts - Screw Terminals with Test Sockets:

Spare Parts - Spring Clamp Terminals:

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-10-16-00k-222183-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data
Technical specifications and data for the R. STAHL 9276A loop-powered binary output for Ex i field circuits. Details include explosion protection, safety data, electrical specifications, environmental conditions, and mechanical data.
Preview R. STAHL 9176/20-16-00k Loop-Powered Binary Output Ex i Field Circuit
Technical datasheet for the R. STAHL 9176/20-16-00k, a loop-powered binary output for Ex i field circuits. Details technical specifications, safety data, certifications, and dimensions.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output
Technical specifications and features of the R. STAHL 9176A loop-powered binary output galvanic isolator for Ex i field circuits. Details on safety, electrical characteristics, environmental conditions, and mechanical specifications.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/10-16-00s loop-powered binary output module, designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. Features include no separate auxiliary power requirement, galvanic isolation, and various safety certifications.
Preview R. STAHL 9176/20-16-00k Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/20-16-00k loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns. Features include two-channel variants, no auxiliary power requirement, and galvanic separation.