Lennox Powered by Samsung
Submittal Data
Model: V33D012S6-5P VRF 4-Way Cassette (3 x 3)
Project Information
- Job Name:
- Purchaser:
- Submitted to:
- Unit designation:
- Location:
- Engineer:
- Reference:
- Approval:
- Construction:
- Schedule #:
General Information
- Compatible with R-32 VRF air, water, and mini-VRF systems.
- Features Calm air mode: When activated in cooling mode, the unit closes its louver and disperses air through thousands of micro-holes on the front, preventing cold air drafts.
- Integral condensate pump with maximum 30-3/8" lift from the unit bottom (21-5/8" from drain outlet), including a check valve and float switch to disable the unit in case of condensate overflow.
- Fascia panel includes a built-in Wi-Fi adapter for control and monitoring via the Samsung SmartThings app.
- Includes knockout for outside air capability.
Construction
- Insulated HIPS chassis and fascia panel certified to UL94 V0 flame retardant rating.
- High-voltage terminal block temperature sensor to disable the unit in the event of power connection overheating.
Refrigerant System
- Heat exchanger: Mechanically bonded aluminum fin to copper tube.
- Includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Single turbo type indoor fan.
- Offers three fan speed settings and an auto setting.
- Includes an electro-static, washable filter as standard (integrated into the fascia panel).
- Fascia panel features LED indicator lights, an infrared receiver, and (4) motorized louvers with independent control (32°-65° louver control range).
Controls
- Control wiring: 2 X 16 AWG.
- Operated via a wired remote controller model VSTAT04P-1 (purchased separately).
- Supports dual set temperature when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Functionality for configuring fan operation during auxiliary heat, defrost, and emergency heat (VSTAT10P-1 accessory required).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
- Emergency Temperature Output (ETO) function: Outputs a signal to an external source (e.g., backup system, building management system, alert device) when the indoor unit is in error status or when room temperature exceeds a configurable level.
Specifications
Specification | Details |
---|---|
Indoor Unit Model Number | V33D012S6-5P |
Performance | Nominal Capacity Cooling (Btu/h): 12,000 Heating (Btu/h): 13,500 |
Voltage Ø / V / Hz: 1 / 208-230 / 60 |
|
Power | Operating Current (max.) Cooling (A): 0.17 Heating (A): 0.17 |
MCA (A): 0.4 MOP (A): 15 |
|
Evaporator Fan | Type BLDC (1) With Turbo Type Fan (1) |
Output (Watts): 65 | |
Airflow | Air Volume (L/M/H) Cooling (CFM): 459 / 494 / 547 Heating (CFM): 459 / 494 / 547 |
Refrigerant | Type: R-32 A2L Leak Detection: Integral |
Pipe Connections | Refrigerant High side (In.): 1/4 Low side (In.): 1/2 |
Condensate 1 1/4 in. OD, 1 in. ID |
|
Dimensions | W x H x D (In.): 33 1/16 X 9 9/16 X 33 1/16 |
Weight (lbs.): 41.40 | |
Sound Pressure Level | Low/Med./High (dB(A)): 26 / 28 / 30 |
Safety | Certifications: UL 60335-2-40 |
Fascia Panel | L x W x H (In.): 37 3/8 X 37 3/8 X 7/8 |
Weight (lbs.): 13.9 | |
Safety | Certifications: UL 60335-2-40 |
Accessories
Accessory Type | Model / Description |
---|---|
Fascia Panel | White: V1V33D01CPWW |
Black: V1V33D01CPBW | |
Wired controller | Advanced: VSTAT04P-1 |
Touchscreen: VSTAT02P-1 | |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless controller | VSTAT01P-1 |
External temperature sensor | VCTRL11P-1 |
External contact control interface module | VSTAT10P-1 |
Motion Detect Sensor (MDS) | V1MDS01CS |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
Unit: Inches
The unit is a square cassette designed for ceiling installation. The overall dimensions are approximately 33-1/16 inches in width and depth, with a height of 9-9/16 inches. The fascia panel dimensions are approximately 37-3/8 inches square and 7/8 inches thick.
Key connection points and features are detailed below:
No. | Description |
---|---|
1 | Liquid pipe connection (1/4 inch) |
2 | Gas pipe connection (1/2 inch) |
3 | Drain hose connection |
4 | Opening for power and communication wire conduit |
5 | Fresh air intake (Ø 4 inches) |
The diagram also indicates ceiling opening dimensions ranging from 35-1/16 to 35-13/16 inches, and suspension positions at 28-15/16 inches.
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.
[ETL Certified] [AHRI Certified]