Lennox VOWD015S6-5P VRF 1-Way Cassette Submittal Data
Brand: Lennox
Powered by: Samsung
General Information
- Compatible with R-32 VRF air, water, and mini systems.
- Features "calm air mode" where the unit closes its louver and disperses air through thousands of micro-holes on the front panel to prevent cold air drafts.
- Includes an integral condensate pump with a maximum 26-5/16" lift from the bottom of the unit (21-5/16" from drain outlet), equipped with a check valve and float switch to disable the unit in case of condensate overflow.
- The fascia panel has a built-in Wi-Fi adapter for control and monitoring via the Samsung SmartThings app.
Construction
- Insulated, HIPS chassis and fascia panel certified to UL94 V0.
- Equipped with a high-voltage terminal block temperature sensor to disable the unit in case of power connection overheating.
Refrigerant System
- Heat exchanger features mechanically bonded aluminum fin to copper tube.
- Includes an R32 alarm output plug for notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).
Indoor Fan
- Offers three fan speed settings and an auto setting.
- Includes an electro-static, washable filter as standard (integrated into the fascia panel).
- Fascia panel features an LED display, infrared receiver, and motorized louvers.
Controls
- Control wiring uses 2 X 16 AWG.
- Operation is via a wired remote controller model MWR-WG01UN (purchased separately).
- Supports dual set temperature when connected to compatible controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Provides external heat control functionality for fan operation during auxiliary heat, defrost, and emergency heat modes (requires VSTAT10P-1 accessory).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).
- Emergency heat functionality allows continued control of the external heat source even if system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).
Convenience
- Features an Emergency Temperature Output (ETO) function. This function signals an external source (e.g., backup system, building management system, alert device) when the indoor unit is in an error status or when room temperature exceeds a configurable level.
Specifications
Specification | Details | |
---|---|---|
Model | VOWD015S6-5P | |
Indoor Unit Model Number | VOWD015S6-5P | |
Performance | Nominal Capacity Cooling (Btu/h) | 15,000 |
Nominal Capacity Heating (Btu/h) | 17,000 | |
Voltage | ø/V/Hz: 1/208-230/60 | |
Power | Operating Current (max.) Cooling (A) | 0.26 |
Operating Current (max.) Heating (A) | 0.26 | |
MCA (A) | 0.33 | |
MOP (A) | 15 | |
Evaporator Fan | Type | BLDC motor with cross-flow fan |
Output (Watts) | 54 | |
Airflow | Cooling (CFM) | 343/378/392 |
Heating (CFM) | 343/378/392 | |
Refrigerant | Type | R-32 |
A2L Leak Detection | Integral | |
Pipe Connections | Refrigerant High side (In.) | 1/4 |
Refrigerant Low side (In.) | 1/2 | |
Condensate | 1 1/4 in. OD, 1 in. ID | |
Dimensions | W X H X D (In.) | 47 1/4 X 5 7/16 X 17 3/4 |
Weight (lbs.) | 28.70 | |
Sound Pressure Level | Low/Med./High (dB(A)) | 34/37/38 |
Safety | Certifications | UL 60335-2-40 |
Fascia Panel L X W X H (In.) | 55 1/2 X 4.75 X 1 3/8 | |
Fascia Panel Weight (lbs.) | 11.0 | |
Fascia Panel Safety | Certifications: UL 60335-2-40 |
Accessories
- Fascia Panel: V1VOWD05CPWW
- Wired controller (Advanced): VSTAT04P-1
- Wired controller (Touchscreen): VSTAT02P-1
- Thermostat adapter (for connection to standard 24VAC thermostats): VSTAT09P-1
- Wireless controller: VSTAT01P-1
- External temperature sensor: VCTRL11P-1
- External contact control interface module: VSTAT10P-1
- CN83 Pigtail (for 12VDC VENT output): JV DB39-01263A CN83 Pigtail
Dimensional Drawing
The document includes a dimensional drawing showing the top, side, and front views of the indoor unit, with dimensions provided in inches. Key connection points and features are detailed:
- 1. Liquid pipe connection: 1/4 inch
- 2. Gas pipe connection: 1/2 inch
- 3. Drain hose connection
- 4. Opening for power and communication wire conduit
- 5. Air outlet louver
- 6. Air inlet grille
Overall unit dimensions (W X H X D) are approximately 47 1/4" x 5 7/16" x 17 3/4". Fascia panel dimensions are approximately 55 1/2" x 4.75" x 1 3/8".
Certifications and Notes
- Certifications: ETL Listed, AHRI Certified (Unitary Small HP, AHRI Standard 210/240). Certification applies only when the complete system is listed with AHRI.
- Lennox maintains a policy of ongoing development; specifications are subject to change without notice.