Lennox V36D030S6-5P VRF 360 Cassette Submittal Data

[Lennox Logo] Powered by [Samsung Logo]

General Information

Construction

Refrigerant System

Indoor Fan

Controls

External Heat Control

Convenience

Certifications

The unit is [Intertek LISTED] and [AHRI CERTIFIED® Unitary Small HP AHRI Standard 210/240].

Note: AHRI certification applies only when the complete system is certified.

Specifications

ModelV36D030S6-5P
Indoor Unit Model NumberV36D030S6-5P
PerformanceNominal Capacity
Cooling: 30,000 Btu/h
Heating: 34,000 Btu/h
Voltage1 / 208-230 / 60 Hz
PowerOperating Current (max.)
Cooling: 0.42 A
Heating: 0.42 A
MCA: 0.82 A
MOP: 15 A
Evaporator FanType: BLDC (1) With Turbo Type Fan (1)
Output: 97 Watts
AirflowAir Volume (L/M/H)
Cooling: 706 / 795 / 901 CFM
Heating: 706 / 795 / 901 CFM
RefrigerantType: R-32
A2L Leak Detection: Integral
Pipe ConnectionsHigh side: 3/8 in., Low side: 5/8 in.
Condensate1 1/4 in. OD, 1 in. ID
DimensionsW X H X D: 37 1/4 X 14 3/8 X 37 1/4 in.
Weight50.70 lbs.
Sound Pressure LevelLow/Med./High: 36 / 38 / 40 dB(A)
SafetyCertifications: UL 60335-2-40
Fascia PanelOpen Type (Round):
L X W X H: 41 3/8 X 3 3/8 in.
Weight: 8.85 lbs.
Ceiling Type (Square):
L X W X H: 39 3/8 X 39 3/8 X 2 5/8 in.
Weight: 6.62 lbs.
SafetyCertifications: UL 60335-2-40

Accessories

Fascia PanelOpen Type (round, black) [V1V36D02CPBW]
Open Type (round, white) [V1V36D02CPWW]
Ceiling Type (square, black) [V1V36D01CPBW]
Ceiling Type (square, white) [V1V36D01CPWW]
Wired controllerAdvanced [VSTAT04P-1]
Touchscreen [VSTAT02P-1]
Thermostat adapter (for connection to standard 24VAC thermostats)[VSTAT09P-1]
Wireless controller[VSTAT01P-1]
External temperature sensor[VCTRL11P-1]
External contact control interface module[VSTAT10P-1]
Motion detect sensor (MDS, white, compatible with square panel only)[V1MDS03CS]
CN83 Pigtail (for 12VDC VENT output)[JV DB39-01263A CN83 Pigtail]

Dimensional Drawings

Dimensional Drawing - With Ceiling Type Fascia Panel

Unit: Inches

The drawing provides multiple views (Front, Back, Side) illustrating the dimensions and connection points for the unit with a ceiling type fascia panel.

Key Components:

  • 1: Liquid pipe connection (1/4 in.)
  • 2: Gas pipe connection (1/2 in.)
  • 3: Drain pipe connection
  • 4: Opening for power and communication wire conduit
  • 5: Air outlet opening
  • 6: Air inlet grille
  • 7: Suction inlet for booster fan
  • 8: Fascia panel
  • 9: Drain hose
  • 10: Fresh air intake
  • 11: Display
  • 12: Wireless signal receiver

Dimensional Drawing - With Open Type Fascia Panel

Unit: Inches

The drawing provides multiple views (Front, Back, Side) illustrating the dimensions and connection points for the unit with an open type fascia panel.

Key Components:

  • 1: Liquid pipe connection (1/4 in.)
  • 2: Gas pipe connection (1/2 in.)
  • 3: Drain pipe connection
  • 4: Opening for power and communication wire conduit
  • 5: Air outlet opening
  • 6: Air inlet grille
  • 7: Suction inlet for booster fan
  • 8: Fascia panel
  • 9: Drain hose
  • 10: Fresh air intake
  • 11: Display
  • 12: Wireless signal receiver

Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.

PDF preview unavailable. Download the PDF instead.

sbmtl v36d030s6-5p 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox VOWD007S6-5P VRF 1-Way Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox VOWD007S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance metrics, accessories, and dimensional details.
Preview Lennox VOWD012S6-5P VRF 1-Way Cassette Submittal Data
Submittal data for the Lennox VOWD012S6-5P VRF 1-Way Cassette indoor unit, detailing its features, specifications, and accessories. Compatible with R-32 VRF systems.
Preview Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit Specifications
Detailed submittal data and specifications for the Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit, highlighting features like Calm Air mode, Wi-Fi connectivity, R-32 refrigerant compatibility, and external heat control.
Preview Lennox V36D024S6-5P VRF 360 Cassette Submittal Data & Specifications
Detailed submittal data and specifications for the Lennox V36D024S6-5P VRF 360 Cassette indoor unit, covering general information, construction, refrigerant system, fan, controls, external heat control, convenience features, technical specifications, and accessories.
Preview Lennox V36D018S6-5P VRF 360 Cassette Submittal Data
Submittal data for the Lennox V36D018S6-5P VRF 360 Cassette indoor unit, detailing specifications, features, construction, and dimensional information.
Preview Lennox VUCD036S6-5P VRF Ceiling Mount Submittal Data and Specifications
Comprehensive submittal data and technical specifications for the Lennox VUCD036S6-5P VRF Ceiling Mount indoor unit, detailing performance, construction, controls, accessories, and dimensional information.