Lennox V36D024S6-5P VRF 360 Cassette Submittal Data & Specifications

Submittal Data: Lennox V36D024S6-5P VRF 360 Cassette

Powered by SAMSUNG

Job Name: [Not Specified]
Purchaser: [Not Specified]
Submitted to: [Not Specified]
Unit designation: [Not Specified]
Location: [Not Specified]
Engineer: [Not Specified]
Reference: [Not Specified]
Approval: [Not Specified]
Construction: [Not Specified]
Schedule: [Not Specified]

General Information

The system features comfort humidity control, optimizing indoor unit coil temperature based on an integral humidity sensor and dew point to maximize energy savings while ensuring space dehumidification and occupant comfort.

The indoor unit includes an integral condensate pump with a maximum 29-inch lift from the unit bottom, featuring a check valve and float switch to disable the unit in case of condensate overflow.

The indoor unit fascia panel is equipped with a standard built-in Wi-Fi adapter for control and monitoring via the Samsung SmartThings app.

Construction

The chassis and fascia panel are constructed from insulated HIPS material, certified to UL94 V0.

Includes a knock-out for outside air capability, allowing for booster fan connection.

All heat exchangers utilize mechanically bonded aluminum fins to copper tubes.

Refrigerant System

The system uses low-GWP R-32 refrigerant.

Refrigerant flow is managed by an electronic expansion valve located at the indoor unit.

An R32 alarm output plug is provided for simple notification of R32 leak detection (requires VSTAT10P-1 accessory).

Indoor Fan

Offers three fan speed settings and an auto setting.

Equipped with a washable filter as standard.

Features LED indicator lights and an infrared receiver.

The indoor unit design avoids air louvers or blades that restrict full airflow.

Air direction control is achieved by creating a low-pressure area near the air outlet, guiding discharge air angle.

Provides fixed or auto-swing air direction control (10° to 60° angle) with local and central controller options.

Independent air distribution control is available with wireless or premium wired controllers, offering three directions (10° to 60° angle).

Controls

Utilizes 2 x 16 AWG control wiring.

Operation is supported via a wireless or wired remote control with DDC-type signal (purchased separately).

Supports dual set temperature when used with compatible controllers.

No additional interface modules or adapters are needed when connecting to Samsung central control options.

Wired or wireless controllers must be purchased separately.

External Heat Control

External heat control functionality allows configuration of fan operation during auxiliary heat, defrost, and emergency heat modes (requires VSTAT10P-1 accessory).

Configuration settings include external heat lockout based on outside ambient conditions, external compressor lockout, and time delay options (requires VSTAT10P-1 accessory).

Emergency heat functionality ensures the system continues controlling the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).

Convenience

Features an Emergency Temperature Output (ETO) function. When the indoor unit is in an error status or the room temperature exceeds a configurable threshold, the system outputs a signal to an external source, such as a backup system, building management system, or alert device (e.g., status light, warning lamp, buzzer).

Visual Descriptions

The document includes images of two fascia panel types:

  • Open Type Panel (Round): Depicts a round fascia panel.
  • Ceiling Type Panel (Square): Depicts a square fascia panel.

Specifications

Specification Value
Indoor Unit Model NumberV36D024S6-5P
Nominal Capacity (Cooling)24,000 Btu/h
Nominal Capacity (Heating)27,000 Btu/h
Voltage1 / 208-230 / 60 Hz
Operating Current (max.) Cooling0.28 A
Operating Current (max.) Heating0.28 A
MCA0.53 A
MOP15 A
Evaporator Fan TypeBLDC (1) With Turbo Type Fan (1)
Evaporator Fan Output65 Watts
Airflow (Cooling)512 CFM
Airflow (Heating)512 CFM
Air Volume (L/M/H)583 / 671 CFM
Refrigerant TypeR-32
Refrigerant Leak DetectionA2L
Pipe Connections (High side)3/8 in.
Pipe Connections (Low side)5/8 in.
Condensate Connection1 1/4 in. OD, 1 in. ID
Dimensions (W x H x D)37 1/4 in. x 11 1/16 in. x 37 1/4 in.
Weight44.50 lbs.
Sound Pressure Level (Low/Med/High)32 / 35 / 38 dB(A)
Safety CertificationsUL 60335-2-40
Fascia Panel (Open Type Round) Dimensions (L x W x H)41 3/8 in. x 3 3/8 in.
Fascia Panel (Open Type Round) Weight8.85 lbs.
Fascia Panel (Ceiling Type Square) Dimensions (L x W x H)39 3/8 in. x 39 3/8 in. x 2 5/8 in.
Fascia Panel (Ceiling Type Square) Weight6.62 lbs.
Fascia Panel Safety CertificationsUL 60335-2-40

Accessories

Fascia Panel

  • Open Type (round, black): V1V36D02CPBW
  • Open Type (round, white): V1V36D02CPWW
  • Ceiling Type (square, black): V1V36D01CPBW
  • Ceiling Type (square, white): V1V36D01CPWW

Controllers & Modules

  • Wired controller (Advanced): VSTAT04P-1
  • Wired controller (Touchscreen): VSTAT02P-1
  • Thermostat adapter (for connection to standard 24VAC thermostats): VSTAT09P-1
  • Wireless controller: VSTAT01P-1
  • External temperature sensor: VCTRL11P-1
  • External contact control interface module: VSTAT10P-1
  • Motion detect sensor (MDS, white, compatible with square panel only): V1MDS03CS
  • CN83 Pigtail (for 12VDC VENT output): JV DB39-01263A CN83 Pigtail

Dimensional Drawings

Dimensional Drawing - With Ceiling Type Fascia Panel

Unit: Inches

Overall Dimensions (approximate): The drawing shows a square unit with various dimensions indicated. Key dimensions include a width/depth of approximately 39-3/8 inches and a height of approximately 11-1/16 inches for the main unit body, with specific mounting and connection points detailed.

Component List (Ceiling Type):
  • 1: Liquid pipe connection (3/8 in.)
  • 2: Gas pipe connection (5/8 in.)
  • 3: Drain pipe connection
  • 4: Opening for power and communication wire conduit
  • 5: Air outlet opening
  • 6: Air inlet grille
  • 7: Suction inlet for booster fan
  • 8: Fascia panel
  • 9: Drain hose
  • 10: Fresh air intake
  • 11: Display
  • 12: Wireless signal receiver

Dimensional Drawing - With Open Type Fascia Panel

Unit: Inches

Overall Dimensions (approximate): Similar to the ceiling type, this drawing shows a round unit. Key dimensions include a width/depth of approximately 41-3/8 inches and a height of approximately 11-1/16 inches for the main unit body, with specific mounting and connection points detailed.

Component List (Open Type):
  • 1: Liquid pipe connection (3/8 in.)
  • 2: Gas pipe connection (5/8 in.)
  • 3: Drain pipe connection
  • 4: Opening for power and communication wire conduit
  • 5: Air outlet opening
  • 6: Air inlet grille
  • 7: Suction inlet for booster fan
  • 8: Fascia panel
  • 9: Drain hose
  • 10: Fresh air intake
  • 11: Display
  • 12: Wireless signal receiver

Note: Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.

PDF preview unavailable. Download the PDF instead.

sbmtl v36d024s6-5p 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox V36D018S6-5P VRF 360 Cassette Submittal Data
Submittal data for the Lennox V36D018S6-5P VRF 360 Cassette indoor unit, detailing specifications, features, construction, and dimensional information.
Preview Lennox V33D018S6-5P VRF 4-Way Cassette Submittal Data
Technical submittal data for the Lennox V33D018S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, refrigerant system, fan, controls, external heat control, convenience functions, accessories, and dimensional drawings.
Preview Lennox VOWD012S6-5P VRF 1-Way Cassette Submittal Data
Submittal data for the Lennox VOWD012S6-5P VRF 1-Way Cassette indoor unit, detailing its features, specifications, and accessories. Compatible with R-32 VRF systems.
Preview Lennox V22D007S6-5P VRF 4-Way Cassette Submittal Data
Technical submittal data for the Lennox V22D007S6-5P VRF 4-Way Cassette indoor unit. Details features like Calm Air mode, Wi-Fi connectivity, R-32 refrigerant compatibility, and external heat control.
Preview Lennox V36D030S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and technical specifications for the Lennox V36D030S6-5P VRF 360 Cassette indoor unit, including performance, construction, refrigerant, fan, controls, and accessories.
Preview Lennox VOWD015S6-5P VRF 1-Way Cassette Submittal Data
Detailed submittal data and specifications for the Lennox VOWD015S6-5P VRF 1-Way Cassette indoor unit, including features, construction, refrigerant system, fan, controls, and accessories.
Preview Lennox V36D012S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox V36D012S6-5P VRF 360 Cassette indoor unit, including general information, construction, refrigerant system, fan, controls, external heat control, convenience features, specifications, and accessories.
Preview Lennox VOWD007S6-5P VRF 1-Way Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox VOWD007S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance metrics, accessories, and dimensional details.