Lennox V36D018S6-5P VRF 360 Cassette Submittal Data
Powered by SAMSUNG
Job Information
Job Name:
Location:
Purchaser:
Engineer:
Submitted to:
Reference:
Unit designation:
Schedule:
Approval:
Construction:
General Information
- The system features comfort humidity control, optimizing indoor unit coil temperature based on dew point using an integral humidity sensor for energy savings and occupant comfort.
- The indoor unit includes an integral condensate pump with a maximum 29" lift and a check valve with a float switch to disable the unit in case of overflow.
- The indoor unit fascia panel has a standard built-in Wi-Fi adapter for control and monitoring via the Samsung SmartThings app.
Construction
- Insulated HIPS chassis and fascia panel certified to UL94 V0.
- Knock-out provided for outside air capability (booster fan connection).
- All heat exchangers feature mechanically bonded aluminum fin to copper tube construction.
Refrigerant System
- The system utilizes low-GWP R-32 refrigerant.
- Refrigerant flow is controlled by an electronic expansion valve located at the indoor unit.
- An R32 alarm output plug is included for simple notification of R32 leak detection (requires VSTAT10P-1 accessory).
Indoor Fan
- Features three fan speed settings and an auto setting.
- Includes a washable filter as standard.
- The indoor unit is equipped with LED indicator lights and an infrared receiver.
- The indoor unit design prevents air louvers or blades from restricting full airflow.
- Air direction control is achieved by creating a low-pressure area near the air outlet, directing discharge air.
- Fixed or auto-swing air direction is possible with local and central controller options, offering a 10° to 60° angle range.
- Independent air distribution control is available with wireless or premium wired controllers, supporting three directions from 10° to 60° angle.
Controls
- Control wiring uses 2 x 16 AWG.
- The unit can be operated via a wireless or wired remote control with a DDC-type signal (purchased separately).
- Supports dual set temperature when connected to compatible controllers.
- No additional interface modules or adapters are needed when connecting to Samsung central control options.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality enables fan operation configuration during auxiliary heat, defrost, and emergency heat modes (requires VSTAT10P-1 accessory).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).
- Emergency heat functionality allows the system to continue controlling the external heat source even if system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).
Convenience
- Features an Emergency Temperature Output (ETO) function. When the indoor unit is in an error status or room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer).
Specifications
Specification | Details |
---|---|
Model | Indoor Unit Model Number: V36D018S6-5P |
Performance | Nominal Capacity Cooling (Btu/h): 18,000 |
Nominal Capacity Heating (Btu/h): 20,000 | |
Voltage | Ø / V / Hz: 1 / 208-230 / 60 |
Power | Operating Current (max.) Cooling (A): 0.18 |
Operating Current (max.) Heating (A): 0.18 | |
MCA (A): 0.4 | |
MOP (A) | 15 |
Evaporator Fan | Type: BLDC (1) With Turbo Type Fan (1) |
Output (Watts): 65 | |
Airflow | Air Volume (L/M/H) Cooling (CFM): 494 / 530 / 565 |
Air Volume (L/M/H) Heating (CFM): 494 / 530 / 565 | |
Refrigerant | Type: R-32 |
A2L Leak Detection: Integral | |
Refrigerant High side (In.): 1/4 | |
Pipe Connections | Refrigerant Low side (In.): 1/2 |
Condensate | 1 1/4 in. OD, 1 in. ID |
Dimensions | W x H x D (In.): 37 1/4 x 11 1/16 x 37 1/4 |
Weight (lbs.): 44.50 | |
Sound Pressure Level | Low/Med./High (dB(A)): 29 / 31 / 33 |
Fascia Panel - Open Type (Round) | L x W x H (in.): 41 3/8 x 3 3/8 |
Weight (lbs.): 8.85 | |
Fascia Panel - Ceiling Type (Square) | L x W x H (in.): 39 3/8 x 39 3/8 x 2 5/8 |
Weight (lbs.): 6.62 | |
Safety | Certifications: UL 60335-2-40 |
Dimensional Drawing - Ceiling Type Fascia Panel
Unit: Inches
This section provides dimensional details for the unit with a Ceiling Type Fascia Panel. It includes front, back, and side views illustrating measurements in inches. The front view shows the circular air outlet grille, display, and suspension points. The back view details pipe connections, a conduit opening, and the drain hose. Side views indicate adjustable mounting dimensions. A table lists specific components by number.
No. | Description |
---|---|
1 | Liquid pipe connection (1/4) |
2 | Gas pipe connection (1/2) |
3 | Drain pipe connection |
4 | Opening for power and communication wire conduit |
5 | Air outlet opening |
6 | Air inlet grille |
7 | Suction inlet for booster fan |
8 | Fascia panel |
9 | Drain hose |
10 | Fresh air intake |
11 | Display |
12 | Wireless signal receiver |
Dimensional Drawing - Open Type Fascia Panel
Unit: Inches
This section provides dimensional details for the unit with an Open Type Fascia Panel. It includes front, back, and side views illustrating measurements in inches. The front view shows the circular air outlet grille, display, and suspension points. The back view details pipe connections, a conduit opening, and the drain hose. Side views indicate adjustable mounting dimensions. A table lists specific components by number.
No. | Description |
---|---|
1 | Liquid pipe connection (1/4) |
2 | Gas pipe connection (1/2) |
3 | Drain pipe connection |
4 | Opening for power and communication wire conduit |
5 | Air outlet opening |
6 | Air inlet grille |
7 | Suction inlet for booster fan |
8 | Fascia panel |
9 | Drain hose |
10 | Fresh air intake |
11 | Display |
12 | Wireless signal receiver |
Accessories
Category / Item | Model Number |
---|---|
Fascia Panel: Open Type (round, black) | V1V36D02CPBW |
Fascia Panel: Open Type (round, white) | V1V36D02CPWW |
Fascia Panel: Ceiling Type (square, black) | V1V36D01CPBW |
Fascia Panel: Ceiling Type (square, white) | V1V36D01CPWW |
Wired controller: Advanced | VSTAT04P-1 |
Wired controller: Touchscreen | VSTAT02P-1 |
Wired controller | VSTAT09P-1 |
Wired controller | VSTAT01P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VCTRL11P-1 |
Wireless controller | VSTAT10P-1 |
External temperature sensor | V1MDS03CS |
External contact control interface module | |
Motion detect sensor (MDS, white, compatible with square panel only) | |
CN83 Pigtail (for 12VDC VENT output) |
Certifications
Intertek ETL Listed US
AHRI Certified® Unitary Small HP, AHRI Standard 210/240
Certification applies only when the complete system is certified.