General Information

  • Compatible with R-32 VRF air, water, and mini-VRF systems.
  • Calm air mode: Closes louver in cooling mode, dispersing air through micro-holes to prevent cold drafts.
  • Integral condensate pump with 30-3/8" maximum lift, check valve, and float switch for overflow protection.
  • Built-in Wi-Fi adapter for control and monitoring via Samsung SmartThings app.
  • Knock-out provision for outside air intake.

Construction

  • Insulated HIPS chassis and fascia panel, UL94 V0 certified.
  • High-voltage terminal block with temperature sensor for overheating protection.

Refrigerant System

  • Mechanically bonded aluminum fin to copper tube heat exchanger.
  • R32 alarm output plug for third-party equipment notification/interlock (requires VSTAT10P-1 accessory).

Indoor Fan

  • Single turbo type fan.
  • Three fan speed settings plus auto.
  • Electro-static, washable filter included with fascia panel.
  • Fascia panel features LED indicators, infrared receiver, and four motorized louvers with independent control (32°-65° range).

Controls

  • Control wiring: 2 x 16 AWG.
  • Operated via wired remote controller model VSTAT04P-1 (purchased separately).
  • Supports dual set temperature when connected to compatible controllers.
  • Wired or wireless controllers must be purchased separately.

External Heat Control

Configuration options for fan operation during auxiliary heat, defrost, and emergency heat (requires VSTAT10P-1 accessory). Includes settings for outside ambient lockouts and time delays. Emergency heat functionality ensures control of the external heat source even if system errors prevent heat pump operation.

Convenience

  • Emergency Temperature Output (ETO) function: Signals an external source (e.g., BMS, alert device) when the unit is in error status or room temperature exceeds a configurable level.

Specifications

V33D006S6-5P Specifications
Feature Details
Indoor Unit Model NumberV33D006S6-5P
Nominal CapacityCooling: 6,300 Btu/h
Heating: 7,100 Btu/h
Voltage1 / 208-230 / 60 Hz
Operating Current (max.)Cooling: 0.17 A
Heating: 0.17 A
MCA0.4 A
MOP15 A
Evaporator FanType: BLDC (1) With Turbo Type Fan (1)
Output: 65 Watts
AirflowCooling/Heating: 353 / 459 / 547 CFM
RefrigerantType: R-32
A2L Leak Detection: Integral
Pipe ConnectionsHigh side: 1/4 in.
Low side: 1/2 in.
Condensate1 1/4 in. OD, 1 in. ID
Dimensions (WxHxD)33 1/16" x 9 9/16" x 33 1/16"
Weight41.40 lbs.
Sound Pressure Level (Low/Med/High)26 / 28 / 30 dB(A)
Safety CertificationsUL 60335-2-40
Fascia Panel (LxWxH)37 3/8" x 37 3/8" x 7/8"
Fascia Panel Weight13.9 lbs.
Fascia Panel Safety CertificationsUL 60335-2-40

Accessories

Available Accessories for V33D006S6-5P
Accessory Type Model Number
Fascia PanelWhite: V1V33D01CPWW
Black: V1V33D01CPBW
Wired controllerAdvanced: VSTAT04P-1
Touchscreen: VSTAT02P-1
Thermostat adapter (for connection to standard 24VAC thermostats)VSTAT09P-1
Wireless controllerVSTAT01P-1
External temperature sensorVCTRL11P-1
External contact control interface moduleVSTAT10P-1
Motion Detect Sensor (MDS)V1MDS01CS
CN83 Pigtail (for 12VDC VENT output)JV DB39-01263A CN83 Pigtail

Dimensional Drawing Description

The dimensional drawing provides a detailed overview of the V33D006S6-5P unit's dimensions and connection points, measured in inches.

Key Dimensions:

  • Overall Unit Dimensions (approximate): Width: 33-1/16", Height: 9-9/16", Depth: 33-1/16".
  • Ceiling Opening Required: Approximately 35-1/16" to 35-13/16".
  • Suspension Position: Approximately 28-15/16".
  • Fascia Panel Dimensions: 37 3/8" x 37 3/8" x 7/8".

Connection Points:

  • Liquid Pipe Connection: 1/4 inch.
  • Gas Pipe Connection: 1/2 inch.
  • Drain Hose Connection.
  • Opening for power and communication wire conduit.
  • Fresh Air Intake: 4 inch diameter (Ø 4").

The drawing includes top, side, and front/back views illustrating these measurements and connection locations.

Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.

PDF preview unavailable. Download the PDF instead.

sbmtl V33D006S6-5P 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox V22D020S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data for the Lennox V22D020S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, and dimensional information for HVAC applications.
Preview Lennox V36D048S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including features, construction, refrigerant system, fan, controls, external heat control, convenience functions, specifications, and accessories.
Preview Lennox VOWD009S6-5P VRF 1-Way Cassette Indoor Unit Submittal Data & Specifications
Detailed submittal data and technical specifications for the Lennox VOWD009S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance, airflow, controls, and available accessories.
Preview Lennox Samsung VOWD024S6-5P VRF 1-Way Cassette Submittal Data
Technical specifications and features for the Lennox Samsung VOWD024S6-5P VRF 1-Way Cassette indoor unit, including performance data, dimensions, and accessories.
Preview Lennox V22D009S6-5P VRF 4-Way Cassette: Submittal Data & Specifications
Detailed submittal data and specifications for the Lennox V22D009S6-5P VRF 4-Way Cassette indoor unit, featuring Calm air mode, R-32 refrigerant compatibility, and advanced control options.
Preview Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit Specifications
Detailed submittal data and specifications for the Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit, highlighting features like Calm Air mode, Wi-Fi connectivity, R-32 refrigerant compatibility, and external heat control.
Preview Lennox VUCD048S6-5P VRF Ceiling Mount Submittal Data and Specifications
Detailed submittal data, specifications, and dimensional drawings for the Lennox VUCD048S6-5P VRF Ceiling Mount unit, featuring R-32 refrigerant, integral Wi-Fi, and advanced controls.
Preview Lennox V36D048S6-5P VRF 360 Cassette Indoor Unit Submittal Data
Technical specifications, features, and dimensional data for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including construction, refrigerant system, fan, controls, and accessories.