Lennox V33D018S6-5P VRF 4-Way Cassette Submittal Data
Powered by SAMSUNG
General Information
- Compatible with R-32 VRF air, water, and mini-VRF systems.
- The indoor unit shall feature Calm air mode. When activated in cooling mode, the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit, preventing cold air drafts on occupants.
- The indoor unit shall have an integral condensate pump with maximum 30-3/8" lift from bottom of the unit (21-5/8" from drain outlet) with check valve and float switch to disable unit in the event of condensate overflow.
- The indoor unit fascia panel shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.
- Knock out for outside air capability.
Construction
- Insulated, HIPS chassis and fascia panel certified to UL94 V0.
- High-voltage terminal block temperature sensor to disable unit in the event of power connection overheating.
Refrigerant System
- The heat exchanger shall be mechanically boded aluminum fin to copper tube.
- The indoor unit shall include an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Indoor fan is a single turbo type.
- Three fan speed settings and auto settings.
- Electro-static, washable filter as standard (included with fascia panel).
- Fascia panel shall have LED indicator lights, infrared receiver, and (4) motorized louvers with independent control (32°-65° louver control range).
Controls
- Control wiring shall be 2 X 16 AWG.
- The unit shall be operated via a wired remote controller model VSTAT04P-1, purchased separately.
- Dual set temperature support when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
- External heat control configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat.
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating.
Convenience
- Emergency Temperature Output (ETO) function: when indoor unit is in error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Certifications
- ETL Listed
- AHRI CERTIFIED® Unitary Small HP (AHRI Standard 210/240) - Certification applies only when the complete system is certified.
- Link to AHRI directory: www.ahridirectory.org
Specifications
Model | Description | Value |
---|---|---|
Indoor Unit Model Number | V33D018S6-5P | |
Nominal Capacity Cooling | 18,000 Btu/h | |
Nominal Capacity Heating | 20,000 Btu/h | |
Voltage | 1 / 208-230 / 60 Hz | |
Operating Current (max.) Cooling | 0.32 A | |
Operating Current (max.) Heating | 0.32 A | |
MCA | 0.51 A | |
MOP | 15 A | |
Evaporator Fan Type | BLDC (1) With Turbo Type Fan (1) | |
Evaporator Fan Output | 65 Watts | |
Airflow Cooling (CFM) | 618 / 671 / 742 | |
Airflow Heating (CFM) | 618 / 671 / 742 | |
Refrigerant Type | R-32 | |
Refrigerant A2L Leak Detection | Integral | |
Pipe Connections High side | 1/4 in. | |
Pipe Connections Low side | 1/2 in. | |
Pipe Connections Condensate | 1 1/4 in. OD, 1 in. ID | |
Dimensions W x H x D | 33 1/16 x 9 9/16 x 33 1/16 in. | |
Weight | 41.40 lbs. | |
Sound Pressure Level Low/Med./High | 32 / 34 / 35.5 dB(A) | |
Safety Certifications | UL 60335-2-40 | |
Fascia Panel L x W x H | 37 3/8 x 37 3/8 x 7/8 in. | |
Fascia Panel Weight | 13.9 lbs. | |
Fascia Panel Safety Certifications | UL 60335-2-40 |
Accessories
Accessory Type | Description/Model |
---|---|
Fascia Panel White | V1V33D01CPWW |
Fascia Panel Black | V1V33D01CPBW |
Wired controller Advanced | VSTAT04P-1 |
Wired controller Touchscreen | VSTAT02P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless controller | VSTAT01P-1 |
External temperature sensor | VCTRL11P-1 |
External contact control interface module | VSTAT10P-1 |
Motion Detect Sensor (MDS) | V1MDS01CS |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
Unit: Inches
The document includes multiple views of the unit: a top view, front view, side views, and a bottom view showing dimensions and connection points.
A table details specific connection points and dimensions:
No. | Description |
---|---|
1 | Liquid pipe connection (1/4") |
2 | Gas pipe connection (1/2") |
3 | Drain hose connection |
4 | Opening for power and communication wire conduit |
5 | Fresh air intake (diameter 4") |
Overall dimensions are provided, including:
- Width: 37-3/8 inches
- Depth: 37-3/8 inches
- Height (Fascia Panel): 7/8 inches
- Unit Depth (W x H x D): 33 1/16 x 9 9/16 x 33 1/16 inches
- Ceiling opening range: 35-1/16 to 35-13/16 inches
- Suspension position: 28-15/16 inches