Temperzone Econex Pro OPA 211RLTFYD(H/V) Specifications and Wiring
Specifications
Model | OPA 211RLTFYD(H/V) Econex Pro |
Item No. (Horizontal/Vertical Supply Air) | 877-021-003/877-021-013 |
Cooling capacity (net) 1 | 19.9 kW |
Cooling capacity range (gross) | 7.3~25.3 kW |
Heating capacity 1 | 19.7 kW |
Heating capacity range | 5.8~26.4 kW |
Electrical input - cooling | 5.7 kW |
Electrical input - heating | 5.4 kW |
EER/AEER (cooling) 1 | 3.52/3.48 |
COP / ACOP (heating) 1 | 3.67/3.63 |
Operating Range (outdoor ambient) - cooling | -10°C~50°C |
Operating Range (outdoor ambient) - heating | -10°C~25°C |
Master Controller | c.pCO Mini |
Slave Controller | UC8 |
Refrigerant | R32 |
Refrigerant Charge | 4.75 kg |
Minimum floor area (@2.4m below ceiling diffuser) | 12 m² |
Compressor type | 4MA-POE (NXG5020 or equivalent) inverter scroll |
Power supply 2 | 3 ph. 400V ac 50Hz + N + E |
Compressor (3ph.) run amps at rating cond. | 8 A/ph. |
Indoor fan type (motor/wheel) | EC / forward curved |
Indoor fan motor size | 500 W (x2) |
Nominal air flow at rating conditions | 1050 l/s |
Indoor fan motor (1ph.) - full load | 3.0 A (x2) |
Outdoor air fan motor (1ph.) - full load | 1.5 A (x2) |
Outdoor air fan capacitor size | 8 μfd |
Outdoor fan motor – max. ext. static pressure available | 25 Pa (@3,750 l/s) |
Control circuit breaker (internal) | 4 A |
Running amps (total system) | 11.5 A/ph. |
Max. running amps (total system) | 20.0 A/ph. |
RCD type recommended | type B, 30mA, 3 pole |
Net weight | 299 kg |
Shipping weight | 341 kg |
Optional Controls: Remote wired Service Interface Device (pGD1) | 201-000-867 |
1 Tested in accordance with AS/NZS 3823
2 Voltage fluctuation range: 376-440V
Dimensions (mm)
OPA 211RLTFYD(H/V)
Diagram showing the unit's external dimensions and mounting points. It includes labels for width (W), depth (X), height (Y), and mounting centers (Z), with minimum clearance requirements indicated. Point loads for mounting are also specified.
POINT LOADS (kg) | X | W | Y | Z |
67 | 70 | 83 | 79 |
Note: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.
Wiring Diagrams
The following diagrams illustrate the electrical connections for the Temperzone Econex Pro unit.
Diagram showing the main electrical wiring schematic. It details connections to various components like the compressor, indoor and outdoor fan motors, control boards (UC8, PSD2), and power supply. Terminal blocks (TB1-TB11) and internal wiring paths are clearly marked. DIP switch settings for UC8 and PSD are also provided.
Diagram illustrating client wiring connections. This includes connections for optional accessories such as room sensors, CO2 sensors, and damper controls. It details terminal block assignments (TB1-TB28) for various signals like temperature, RH%, fan speed requests, and fault outputs. It also shows connections for external protection and isolator switches.