Temperzone Econex Pro OPA 680RLTB2FPQD-Z
Specifications
Model | OPA 680RLTB2FPQD-Z Econex Pro |
Configuration | Horizontal Supply Air |
Item No. (Standard / Opposite Hand) | 877-068-701 / 877-068-710 |
Configuration | Downward Supply Air |
Item No. (Standard / Opposite Hand) | 877-068-723 / 877-068-732 |
Configuration | Upward Supply Air |
Item No. (Standard / Opposite Hand) | 877-068-745 / 877-068-754 |
Cooling capacity (net) 1 | 65.1 kW |
Cooling capacity range (gross) | 14.4~79.0 kW |
Heating capacity 1 | 64.5 kW |
Heating capacity range | 8.3~72.3 kW |
Electrical input - cooling | 17.1 kW |
Electrical input - heating | 16.5 kW |
EER / AEER (cooling) 1 | 3.81 / 3.78 |
COP / ACOP (heating) 1 | 3.91 / 3.88 |
Operating Range (outdoor ambient) - cooling | -10°C ~ 50°C |
Operating Range (outdoor ambient) - heating | -10°C ~ 25°C |
Master Controller | c.pCO |
Slave Controllers | UC8 (x2) |
Refrigerant | R32 |
Refrigerant Charge | 7.0 kg/sys. |
Minimum floor area (@2.4m below ceiling diffuser) | 26 m² |
Compressor oil type | POE-46 (NXG5020 or equivalent) |
Compressor type | inverter scroll (x2) |
Power supply 2 | 3 ph. 400 V ac 50 Hz + N + E |
Compressor (3ph.) run amps at rating cond. | 12.5 A/ph.(x2) |
Compressor + VSD circuit breaker | 32 A (x2) |
Indoor fan motor size | EC Plug 500 dia. 3.65kW (x2) |
Nominal air flow at rating conditions | 3 600 l/s |
Indoor fan motor (3ph.) - full load | 4.8 A/ph. (x2) |
Outdoor fan motor (3ph.) - full load | 3.5 A/ph. (x2) |
Outdoor fan - max. external static available@ 8 400 l/s | 100 Pa |
Control circuit breaker (internal) | 2 A |
Single phase socket circuit breaker | 10 A |
Running amps (total system) 1 | 25 / 28 / 31 A |
Max. running amps (total system) | 50 / 54 / 59 A |
RCD type recommended | type B, 30mA, 3 pole |
Net weight (excl. cowl) | 1221 kg |
Shipping weight (excl. cowl) | 1286 kg |
Net Weight c/w Economiser | 1261 kg |
Accessories
- Remote wired Service Interface Device (pGDN): 201-000-867
- Filters - rated EU4/G4 disposable: 019-400-004 500x500x50 (x9)
- Filters - rated EU4/G4 washable (NZ Only): 019-000-033 500x500x50 (x9)
- Drain tundish (2 per set; 2 sets required): 060-000-653
Refer to temperzone for other options.
1 Tested in accordance with AS/NZS 3823
2 Voltage range: 376-440V
3 Filter sizes are nominal; refer to Temperzone for actual measurements.
Dimensions (mm)
OPA 680RLTB2FPQD01-Z Standard Hand, Horizontal Supply
POINT LOADS (kg) | W | X | Y | Z |
---|---|---|---|---|
Eco Std | 336 | 314 | 234 | 377 |
Eco Opp | 377 | 234 | 314 | 336 |
Diagram Description: Top view of the horizontal supply unit showing dimensions W, X, Y, Z, and clearance requirements. Includes labels for ECONOMISER COWL, FILTER ACCESS, ELECTRICAL BOX, FAN ACCESS, POWER ENTRY, and COMM'S.
Diagram Description: Side view of the horizontal supply unit showing overall height, mounting centers, and clearance requirements. Includes labels for ECONOMISER COWL (STD HD).
OPA 680RLTB2FPQD23-Z Standard Hand, Downward Supply
Diagram Description: Front view of the downward supply unit showing dimensions, supply and return air connections, and drain tray access. Includes labels for E-BOX END, DRAIN TRAY ACCESS, and DRAIN.
Diagram Description: Side view of the downward supply unit showing overall height and clearance requirements.
Diagram Description: Top view of the downward supply unit showing dimensions and supply/return air configuration.
OPA 680RLTB2FPQD45-Z Standard Hand, Upward Supply
Diagram Description: Front view of the upward supply unit showing dimensions and supply/return air connections. Includes labels for OPPOSITE HAND, SUPPLY AIR, RETURN AIR.
Diagram Description: Side view of the upward supply unit showing overall height and clearance requirements.
Diagram Description: Top view of the upward supply unit showing dimensions and supply/return air configuration. Includes labels for OPPOSITE HANDING, SUPPLY AIR, RETURN AIR, ECONOMISER COWL.
NOTE: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.
Wiring Diagrams
Diagram Description: Wiring schematic for the Temperzone OPA 680RLTB2FPQD-(Z) UC8 system, detailing connections for compressors, fan motors, VSDs, and control circuits. Includes terminal block layouts and component identification.
Diagram Description: Detailed wiring schematic showing connections for indoor and outdoor fan motors, VSDs, and various sensors. Includes terminal block assignments and cable routing.
Diagram Description: Wiring diagram illustrating connections for client BMS, remote displays, and optional modules. Details field bus communication and sensor inputs/outputs.
Diagram Description: Wiring schematic for optional dampers and sensors, including CO2 sensors and reheat coil valve wiring. Shows terminal block connections for actuators and sensors.
Diagram Description: Client wiring overview, including reheat coil and indoor coil layouts, VSD DIP switch settings, and Modbus device addressing. Provides a summary of component functions and connections.