Temperzone Econex Pro OPA 680RLTB2FPQD-Z

Specifications

Model OPA 680RLTB2FPQD-Z Econex Pro
Configuration Horizontal Supply Air
Item No. (Standard / Opposite Hand) 877-068-701 / 877-068-710
Configuration Downward Supply Air
Item No. (Standard / Opposite Hand) 877-068-723 / 877-068-732
Configuration Upward Supply Air
Item No. (Standard / Opposite Hand) 877-068-745 / 877-068-754
Cooling capacity (net) 1 65.1 kW
Cooling capacity range (gross) 14.4~79.0 kW
Heating capacity 1 64.5 kW
Heating capacity range 8.3~72.3 kW
Electrical input - cooling 17.1 kW
Electrical input - heating 16.5 kW
EER / AEER (cooling) 1 3.81 / 3.78
COP / ACOP (heating) 1 3.91 / 3.88
Operating Range (outdoor ambient) - cooling -10°C ~ 50°C
Operating Range (outdoor ambient) - heating -10°C ~ 25°C
Master Controller c.pCO
Slave Controllers UC8 (x2)
Refrigerant R32
Refrigerant Charge 7.0 kg/sys.
Minimum floor area (@2.4m below ceiling diffuser) 26 m²
Compressor oil type POE-46 (NXG5020 or equivalent)
Compressor type inverter scroll (x2)
Power supply 2 3 ph. 400 V ac 50 Hz + N + E
Compressor (3ph.) run amps at rating cond. 12.5 A/ph.(x2)
Compressor + VSD circuit breaker 32 A (x2)
Indoor fan motor size EC Plug 500 dia. 3.65kW (x2)
Nominal air flow at rating conditions 3 600 l/s
Indoor fan motor (3ph.) - full load 4.8 A/ph. (x2)
Outdoor fan motor (3ph.) - full load 3.5 A/ph. (x2)
Outdoor fan - max. external static available@ 8 400 l/s 100 Pa
Control circuit breaker (internal) 2 A
Single phase socket circuit breaker 10 A
Running amps (total system) 1 25 / 28 / 31 A
Max. running amps (total system) 50 / 54 / 59 A
RCD type recommended type B, 30mA, 3 pole
Net weight (excl. cowl) 1221 kg
Shipping weight (excl. cowl) 1286 kg
Net Weight c/w Economiser 1261 kg

Accessories

Refer to temperzone for other options.

1 Tested in accordance with AS/NZS 3823

2 Voltage range: 376-440V

3 Filter sizes are nominal; refer to Temperzone for actual measurements.

Dimensions (mm)

OPA 680RLTB2FPQD01-Z Standard Hand, Horizontal Supply

POINT LOADS (kg) W X Y Z
Eco Std 336 314 234 377
Eco Opp 377 234 314 336

Diagram Description: Top view of the horizontal supply unit showing dimensions W, X, Y, Z, and clearance requirements. Includes labels for ECONOMISER COWL, FILTER ACCESS, ELECTRICAL BOX, FAN ACCESS, POWER ENTRY, and COMM'S.

Diagram Description: Side view of the horizontal supply unit showing overall height, mounting centers, and clearance requirements. Includes labels for ECONOMISER COWL (STD HD).

OPA 680RLTB2FPQD23-Z Standard Hand, Downward Supply

Diagram Description: Front view of the downward supply unit showing dimensions, supply and return air connections, and drain tray access. Includes labels for E-BOX END, DRAIN TRAY ACCESS, and DRAIN.

Diagram Description: Side view of the downward supply unit showing overall height and clearance requirements.

Diagram Description: Top view of the downward supply unit showing dimensions and supply/return air configuration.

OPA 680RLTB2FPQD45-Z Standard Hand, Upward Supply

Diagram Description: Front view of the upward supply unit showing dimensions and supply/return air connections. Includes labels for OPPOSITE HAND, SUPPLY AIR, RETURN AIR.

Diagram Description: Side view of the upward supply unit showing overall height and clearance requirements.

Diagram Description: Top view of the upward supply unit showing dimensions and supply/return air configuration. Includes labels for OPPOSITE HANDING, SUPPLY AIR, RETURN AIR, ECONOMISER COWL.

NOTE: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.

Wiring Diagrams

Diagram Description: Wiring schematic for the Temperzone OPA 680RLTB2FPQD-(Z) UC8 system, detailing connections for compressors, fan motors, VSDs, and control circuits. Includes terminal block layouts and component identification.

Diagram Description: Detailed wiring schematic showing connections for indoor and outdoor fan motors, VSDs, and various sensors. Includes terminal block assignments and cable routing.

Diagram Description: Wiring diagram illustrating connections for client BMS, remote displays, and optional modules. Details field bus communication and sensor inputs/outputs.

Diagram Description: Wiring schematic for optional dampers and sensors, including CO2 sensors and reheat coil valve wiring. Shows terminal block connections for actuators and sensors.

Diagram Description: Client wiring overview, including reheat coil and indoor coil layouts, VSD DIP switch settings, and Modbus device addressing. Provides a summary of component functions and connections.

PDF preview unavailable. Download the PDF instead.

OPA 680RLTB2FPQD-Z Specifications 0625 Adobe PDF Library 17.0 Adobe InDesign 19.5 (Macintosh)

Related Documents

Preview Temperzone Econex Packaged Units: Efficient, Sustainable, Low-GWP HVAC
Explore Temperzone's Econex Air-Cooled Packaged Units, featuring R32 refrigerant for lower GWP and superior energy efficiency with inverter technology. These low-carbon HVAC solutions are ideal for commercial applications, offering advanced features and durable design.
Preview Temperzone Econex Packaged Units: Energy Efficient Air Conditioning
Discover the Temperzone Econex Packaged Units, featuring R32 inverter technology for superior energy efficiency, lower Global Warming Potential (GWP), and advanced comfort control. Explore features, specifications, and benefits for commercial and light commercial applications.
Preview Temperzone Econex Pro Packaged Units: Advanced Humidity Control and Energy Efficiency
Discover the Temperzone Econex Pro Air Cooled Packaged Units, designed for superior humidity control, energy efficiency, and reliability. Featuring R32 refrigerant, inverter compressors, and EC fans, these units offer advanced performance for commercial and industrial applications.
Preview temperZONE OPA Econex Pro Technical Guide: Features, Modes, and Controls
Comprehensive technical guide for temperZONE's OPA Econex Pro series air conditioning units. Covers comfort modes, controller overview, settings, and system information for models OPA 171, 211, 680, 820, 970, 1410, 1710, and 2110.
Preview Temperzone Econex Pro OPA 211RLTFYD(H/V) - Technical Specifications and Wiring
Detailed technical specifications, dimensions, and electrical wiring diagrams for the Temperzone Econex Pro OPA 211RLTFYD(H/V) air conditioning unit, featuring R32 refrigerant and UC8 controller.
Preview Temperzone Econex Pro OPA 211RLTFYD(H/V) Specifications and Wiring
This document provides detailed specifications, dimensions, and electrical wiring schematics for the Temperzone Econex Pro OPA 211RLTFYD(H/V) air conditioning unit. It includes technical data on cooling and heating capacities, electrical inputs, operating ranges, refrigerant details, and component specifications, along with comprehensive wiring diagrams for client and internal connections.
Preview temperZONE OPA 171RLTFY(H/V) Econex Air Conditioner Specifications and Wiring
Technical specifications, dimensional data, and electrical wiring schematics for the temperZONE OPA 171RLTFY(H/V) Econex air conditioning unit, featuring R32 refrigerant and UC8 controller.
Preview Temperzone Econex Pro Packaged Units: Advanced Air Conditioning Solutions
Discover the Econex Pro Packaged Units by Temperzone, featuring R32 inverter technology for superior comfort, humidity control, and energy efficiency. Explore features, specifications, and benefits for commercial applications.