Temperzone OPA 211RLTFY(H/V) Econex: Specifications and Wiring Details
This document provides detailed technical specifications, dimensional information, and electrical wiring schematics for the Temperzone OPA 211RLTFY(H/V) Econex air conditioning unit.
Product Overview
The Temperzone OPA 211RLTFY(H/V) Econex is an air conditioning unit designed for efficient cooling and heating. It utilizes R32 refrigerant and features an inverter scroll compressor controlled by a UC8 unit controller.
Specifications
Feature | Specification |
---|---|
Model | OPA 211RLTFY(H/V) Econex |
Item No. | 876-021-003 / 876-021-013 |
Cooling Capacity (net) | 19.9 kW |
Cooling Capacity Range (gross) | 7.3 ~ 25.3 kW |
Heating Capacity | 19.7 kW |
Heating Capacity Range | 5.8 ~ 26.4 kW |
Electrical Input - Cooling | 5.7 kW |
Electrical Input - Heating | 5.4 kW |
EER / AEER (cooling) | 3.52 / 3.48 |
COP / ACOP (heating) | 3.67 / 3.63 |
Operating Range (outdoor ambient) - Cooling | -10°C ~ 50°C |
Operating Range (outdoor ambient) - Heating | -10°C ~ 25°C |
Controller | UC8 |
Refrigerant | R32 |
Refrigerant Charge | 4.75 kg |
Minimum Floor Area (@2.4m below ceiling diffuser) | 12 m² |
Compressor Oil Type | 4MA-POE (NXG5020 or equivalent) |
Compressor Type | Inverter scroll |
Power Supply | 3 ph. 400V ac 50Hz + N + E |
Compressor (3ph.) Run Amps at Rating Cond. | 8 A/ph. |
Indoor Fan Type (motor/wheel) | EC / forward curved |
Indoor Fan Motor Size | 500 W (x2) |
Nominal Air Flow at Rating Conditions | 1050 l/s |
Indoor Fan Motor (1ph.) - Full Load | 3.0 A |
Outdoor Air Fan Motor (1ph.) - Full Load | 1.5 A |
Outdoor Air Fan Capacitor Size | 8 μfd |
Outdoor Fan Motor – Max. Ext. Static Pressure Available | 25 Pa (@3,750 l/s) |
Control Circuit Breaker (internal) | 4 A |
Running Amps (total system) | 11.5 A/ph. |
Max. Running Amps (total system) | 20.0 A/ph. |
RCD Type Recommended | Type B, 30mA, 3 pole |
Net Weight | 298 kg |
Shipping Weight | 340 kg |
Optional Controls:
- TZT-100 Room temperature controller (Part No: 201-000-350)
- SAT-3 Room temperature controller (Part No: 201-000-146)
Note: Tested in accordance with AS/NZS 3823. Voltage fluctuation range: 376-440V.
Dimensions and Clearances
The unit is designed with specific clearance requirements for optimal performance and service access. Key dimensions and point load locations are provided.
Unit Model: OPA 211RLTYFH(V)
Point Loads (kg):
- W: 67
- X: 70
- Y: 83
- Z: 79
Clearance Requirements:
- Minimum clearance for fan access: 1000 mm (sides)
- Minimum clearance for top discharge: 2000 mm
- Minimum clearance for air intake/front: 500 mm
- Minimum clearance for electrical/service access: 1000 mm
Note: Specifications are subject to change without notice due to the manufacturer's ongoing research and development program.
Electrical Wiring Schematics
The following sections detail the internal and client wiring for the Temperzone OPA 211RLTFY(H/V) Econex unit, managed by the UC8 controller.
Internal Wiring Overview (Page 3)
The internal wiring schematic illustrates the connections between the main power supply (L1, L2, L3, N, PE), the UC8 controller, indoor and outdoor fan motors (IFM1, IFM2, OFM1, OFM2), compressor (COMP), electronic expansion valve (EEV), power speed drive (PSD), and various sensors and control components. Key terminal blocks (TB1-TB26) are shown, facilitating power distribution, signal transmission, and fault reporting.
Components like capacitors (CAP1, CAP2), transformers (TR), circuit breakers (CCB, IFCB, OFCB), and relays are integrated into the system.
Client Wiring and Connections (Page 4)
Client wiring involves connecting the unit to the external power supply via an isolator switch and protection. It also details connections for customer BMS (Building Management System) inputs, optional room temperature controllers (like TZT-100), and sensor inputs.
Key Connections and Terminals:
- Power Input: TB1 (L1), TB2 (L2), TB3 (L3), TB4 (N), MIS (Main Isolator Switch).
- Control Circuit: TB5, TB6, TB7, TB8, TB9, TB10, TB11 (24V AC), TB12 (24V COM).
- Analog Controls: Compressor (0-10V) via TB13, Fan (0-10V) via TB14.
- Fault Signals: TB16 (N/O), TB17 (COM), TB18 (N/C).
- Remote Control: LOW IN (TB19), MED IN (TB20), HIGH IN (TB21), COM (TB22), HEAT ON (TB23), COMP ON (TB24), ON (TB25), 0V (TB26).
Sensors and Transducers:
Various sensors are connected to the UC8 controller for monitoring and control:
- Temperature Sensors (Type S): Discharge Temp (DL), Suction Temp (SL), Ambient Temp (AMB), De-ice Temp (DEI).
- Pressure Transducers (Type T): Suction Pressure (LPT), Discharge Pressure (HPT).
DIP Switch Settings:
The unit features DIP switches on the UC8, PSD, and TFC modules to configure operational parameters. Specific settings are provided in tables, indicating which switches to set to 'On' or 'Off' for different functions like fan speed control, compressor operation, and fault reporting.
Component Definitions:
A glossary of abbreviations is provided for clarity, including:
- CCB: Control Circuit Breaker
- CCH: Crankcase Heater
- COMP: Compressor
- EEV: Electronic Expansion Valve
- FRB: Fault Relay Board
- IFM: Indoor Fan Motor
- OFM: Outdoor Fan Motor
- PSD: Power Speed Drive
- TFC: Triac Fan Controller
- UC8: Unit Controller 8
- VSDCB: Variable Speed Drive Circuit Breaker
Note: Refer to the 'Installation & Maintenance' pamphlet for more detailed information.