temperZONE OPA 171RLTFY(H/V) Econex Air Conditioner

Specifications

Model OPA 171RLTFY(H/V) Econex
Item No. (Horizontal/Vertical Supply Air) 876-017-003 / 876-017-013
Cooling capacity (net) 1 16.4 kW
Cooling capacity range (gross) 5.3~20.3 kW
Heating capacity 1 17.3 kW
Heating capacity range 4.0~20.7 kW
Electrical input - cooling 4.9 kW
Electrical input - heating 5.1 kW
EER / AEER (cooling) 1 3.34 / 3.30
COP / ACOP (heating) 1 3.42 / 3.38
Operating Range (outdoor ambient) - cooling -10°C ~ 50°C
Operating Range (outdoor ambient) - heating -10°C ~ 25°C
Unit Controller UC8
Refrigerant R32
Refrigerant Charge 4.0 kg
Minimum floor area (@2.4m below ceiling diffuser) 8.5 m²
Compressor oil type 4MA-POE (NXG5020 or equivalent)
Compressor type inverter scroll
Power supply 2 3 ph. 400 V ac 50 Hz + N + E
Compressor (3ph.) run amps at rating cond. 8.5 A/ph.
Indoor fan type (motor/wheel) EC / forward curved
Indoor fan motor size 500 W (x2)
Nominal air flow at rating conditions 1 900 l/s
Indoor fan motor (1ph.) - full load 2.5 A (x2)
Outdoor air fan motor (1ph.) - full load 1.5 A
Outdoor air fan capacitor size 8 μfd
Outdoor fan motor – max. ext. static pressure available 25 Pa (@1,800 l/s)
Control circuit breaker (internal) 4 A
Running amps (total system) 1 9 A/ph.
Max. running amps (total system) 14 A/ph.
RCD type recommended type B, 30mA, 3 pole
Net weight 247 kg
Shipping weight 280 kg

Optional Controls:

Refer to temperZONE for other options.

1 Tested in accordance with AS/NZS 3823.

2 Voltage fluctuation range: 376-440V.

Dimensions

The unit dimensions are provided in millimeters (mm). The diagrams show the unit from top, front, and side views, indicating overall dimensions, clearance requirements, and mounting details.

Overall Dimensions (Approximate):

Clearance Requirements:

Mounting Details:

Point Loads (kg):

W X Y Z
56 58 68 66

Note: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.

Electrical Wiring and Components

The document includes detailed electrical wiring schematics and client wiring diagrams. These illustrate the connections for the temperZONE OPA 171RLTFY(H/V) Econex unit, managed by the UC8 controller.

Key Components and Terminals:

Wiring Diagram Descriptions:

The wiring diagrams show the internal electrical layout, including:

Important Note: The unit requires a 24-hour power supply for the control circuit and crankcase heaters.

PDF preview unavailable. Download the PDF instead.

OPA 171RLTFY Specifications 0725 Adobe PDF Library 17.0 Adobe InDesign 20.5 (Macintosh)

Related Documents

Preview Temperzone Econex Packaged Units: Energy Efficient Air Conditioning
Discover the Temperzone Econex Packaged Units, featuring R32 inverter technology for superior energy efficiency, lower Global Warming Potential (GWP), and advanced comfort control. Explore features, specifications, and benefits for commercial and light commercial applications.
Preview Temperzone OPA 211RLTFY(H/V) Econex Air Conditioner Specifications and Wiring
Detailed specifications, dimensional data, and electrical wiring schematics for the Temperzone OPA 211RLTFY(H/V) Econex air conditioning unit, including component definitions and DIP switch settings.
Preview Temperzone Econex Packaged Units: Efficient, Sustainable, Low-GWP HVAC
Explore Temperzone's Econex Air-Cooled Packaged Units, featuring R32 refrigerant for lower GWP and superior energy efficiency with inverter technology. These low-carbon HVAC solutions are ideal for commercial applications, offering advanced features and durable design.
Preview Temperzone Econex Pro OPA 680RLTB2FPQD-Z Specifications and Wiring
Detailed specifications and wiring diagrams for the Temperzone Econex Pro OPA 680RLTB2FPQD-Z horizontal, downward, and upward supply air units. Includes technical data, dimensions, and electrical schematics.
Preview Temperzone Econex Pro OPA 211RLTFYD(H/V) - Technical Specifications and Wiring
Detailed technical specifications, dimensions, and electrical wiring diagrams for the Temperzone Econex Pro OPA 211RLTFYD(H/V) air conditioning unit, featuring R32 refrigerant and UC8 controller.
Preview temperZONE OPA Econex Pro Technical Guide: Features, Modes, and Controls
Comprehensive technical guide for temperZONE's OPA Econex Pro series air conditioning units. Covers comfort modes, controller overview, settings, and system information for models OPA 171, 211, 680, 820, 970, 1410, 1710, and 2110.
Preview Temperzone Econex Pro Packaged Units: Advanced Humidity Control and Energy Efficiency
Discover the Temperzone Econex Pro Air Cooled Packaged Units, designed for superior humidity control, energy efficiency, and reliability. Featuring R32 refrigerant, inverter compressors, and EC fans, these units offer advanced performance for commercial and industrial applications.
Preview Temperzone Packaged Rooftop Air Conditioners R32 Econex Series Technical Data
Detailed technical data, specifications, performance charts, and dimensions for Temperzone's R32 Econex and Econex Pro series packaged rooftop air conditioning units, designed for commercial applications.