temperzone OPA 171RLTFYD Econex Pro HVAC Unit Specifications and Wiring
Specifications
Specification | Value |
---|---|
Model | OPA 171RLTFYD(H/V) Econex Pro |
Item No. (Horizontal/Vertical Supply Air) | 877-017-003 / 877-017-013 |
Cooling capacity (net) 1 | 16.4 kW |
Cooling capacity range (gross) | 5.3 ~ 20.3 kW |
Heating capacity 1 | 17.3 kW |
Heating capacity range | 4.0 ~ 20.7 kW |
Electrical input - cooling | 4.9 kW |
Electrical input - heating | 5.1 kW |
EER / AEER (cooling) 1 | 3.34 / 3.30 |
COP / ACOP (heating) 1 | 3.42 / 3.38 |
Operating Range (outdoor ambient) - cooling | -10°C ~ 50°C |
Operating Range (outdoor ambient) - heating | -10°C ~ 25°C |
Master Controller | c.pCO Mini |
Slave Controller | UC8 |
Refrigerant | R32 |
Refrigerant Charge | 4.0 kg |
Minimum floor area (@2.4m below ceiling diffuser) | 8.5 m² |
Compressor oil type | 4MA-POE (NXG5020 or equivalent) |
Compressor type | inverter scroll |
Power supply 2 | 3 ph. 400 V ac 50 Hz + N + E |
Compressor (3ph.) run amps at rating cond. | 8.5 A/ph. |
Indoor fan type (motor/wheel) | EC / forward curved |
Indoor fan motor size | 500 W (x2) |
Nominal air flow at rating conditions | 900 l/s |
Indoor fan motor (1ph.) - full load | 2.5 A (x2) |
Outdoor air fan motor (1ph.) - full load | 1.5 A |
Outdoor air fan capacitor size | 8 μfd |
Outdoor fan motor – max. ext. static pressure available | 25 Pa (@1,800 l/s) |
Control circuit breaker (internal) | 4 A |
Running amps (total system) | 9 A/ph. |
Max. running amps (total system) | 14 A/ph. |
RCD type recommended | type B, 30mA, 3 pole |
Net weight | 248 kg |
Shipping weight | 281 kg |
Optional Controls: | |
Remote wired Service Interface Device (pGD1) | 201-000-867 |
Note: Tested in accordance with AS/NZS 3823. Voltage fluctuation range: 376-440V.
Dimensions
Diagrams illustrating the physical dimensions of the OPA 171RLTFYD(H/V) unit. The diagrams show front, side, and top views, indicating overall dimensions, mounting centers, and clearance requirements.
Key dimensions include:
- Overall height: 1230 mm (O/A)
- Overall width: 1176 mm (O/A)
- Overall depth: 1254 mm (O/A)
- Mounting centers: 1170 mm (width), 800 mm (depth)
- Clearance requirements: 500 mm (side/fan access), 1000 mm (front/rear), 2000 mm (top)
- Supply Air (S/A) Spigot: 778 mm
- Return Air (R/A) Spigot: 1030 mm
- Electrical/Comms/Power/Drain connections are indicated with specific port sizes.
Point Loads (kg):
Location | W | X | Y | Z |
---|---|---|---|---|
56 | 58 | 68 | 66 | |
269 | 778 | 134 | 246 | |
432 | 317 | 304 | 104 | |
1170 | 44 | 40 | 50 |
Note: Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.
Wiring Diagrams
Detailed electrical wiring schematics for the temperzone OPA 171RLTFYD unit, illustrating internal and client-side connections. The diagrams cover power distribution, control signals, fan motors, sensors, and communication interfaces.
Internal Wiring (Sheet 1 of 2)
This diagram shows the internal connections within the unit. Key components and connections include:
- Power Input: L1, L2, L3, N, PE (Protective Earth) connected via Main Isolator Switch (MIS), Control Circuit Breaker (CCB), Outdoor Fan Circuit Breaker (OFCB), Indoor Fan Circuit Breaker (IFCB), Variable Speed Drive Circuit Breaker (VSDCB).
- Controllers: UC8 Unit Controller and Carel c.pCO Mini Master Controller are central to the system.
- Fan Motors: Indoor Fan Motors (IFM1, IFM2) and Outdoor Fan Motors (OFM1, OFM2) are shown with their respective power and control connections, including Triac Fan Controllers (TFC).
- Sensors & Transducers: Various sensors are connected, including Discharge Temperature (DL), Suction Temperature (SL), Ambient Temperature (AMB), De-ice Temperature (DEI), Suction Pressure (LPT), and Discharge Pressure (HPT).
- Power Supply & Drives: Power supply (3-phase 400V AC) is distributed, with connections to the Power Speed Drive (PSD2) for motor control.
- Terminal Blocks: Numerous terminal blocks (TB1-TB28) are used for internal and external connections.
- Communication: Ethernet (ETH1-ETH10) ports are shown for communication.
- DIP Switches: Settings for UC8, PSD, and TFC are detailed in tables.
Client Wiring (Sheet 2 of 2)
This diagram details how external equipment and sensors connect to the unit. Key elements include:
- Client External Protection & Isolator Switch: Connection to the main power supply.
- Ethernet Port: For network communication.
- Carel cPCO - Mini High End Version Connections: Terminal blocks (TB1-TB28) are mapped to specific signals for sensors, actuators, and control inputs/outputs.
- Sensors: Connections for Room, Return Air (RA), Supply Air (SA), and Fresh Air (FA) temperature and humidity sensors. CO2 sensors and Drain sensors are also listed as optional.
- Actuators: Connections for dampers (DMRA, DMFA) are shown, including their control and feedback signals.
- Control Signals: Inputs for Unoccupied mode (UN-OCC), enable (ENB), fault (FAULT), and fan speed control (0-10V) are detailed.
- Communication Interfaces: RS-485 for Service Interface (J3) and other communication protocols (FBus, CAN) are indicated.
- Important Notes: Emphasize the need for a 24-hour power supply for control circuits and crankcase heaters. Also, notes on sensor connections for economiser functionality.
Component Glossary:
- CCB: Control Circuit Breaker
- CCH: Crankcase Heater
- CK: DC Choke
- CLMP: EMC Earth Clamp
- CM: Compressor Motor
- EEV: Electronic Expansion Valve
- ETH: Earth
- IFCB: Indoor Fan Circuit Breaker
- IFM: Indoor Fan Motor
- IBB: Insulated Bus Bar
- MIS: Main Isolator Switch
- OFCB: Outdoor Fan Circuit Breaker
- OFM: Outdoor Fan Motor
- PCLP: EMC Earth P-Clip
- RCR: Reactor
- RV: Reversing Valve
- TB: Terminal Block
- TFC: Triac Fan Controller
- TR: Transformer
- UC8: Unit Controller 8
- VSDCB: Variable Speed Drive Circuit Breaker
- W: Cable Marker
Document Information:
- Drawing Number: 291-003-547
- Revision: A
- Date: 06-07-25 (Drawn), 08-07-25 (Approved)
- Manufacturer: temperzone Ltd