JABLOTRON JA-111H TRB Bus Module – Interface for Wired Detectors
Introduction
This document provides information on the JABLOTRON JA-111H TRB bus module, an interface for wired detectors. It is a component of the JABLOTRON system, designed to connect wired detectors with NC/NO contact outputs to the control panel's bus. The module supplies power to the detector and reports its activation, tampering, and faults. Installation must be performed by a qualified technician certified by an authorized distributor.
Note: This document was automatically translated from the original English. For any uncertainties or doubts, refer to the original document version. If you encounter errors or have further questions, contact technical support.
Installation
? When connecting the module to the system bus, always disconnect the power supply.
The current consumption of the connected detector must not exceed 50 mA (the module's power output is not overload protected).
The module is designed for installation inside a standard wired detector (with contact outputs), but thanks to extended cables, it can also be installed outside the detector, in a protective installation box. The cable can be extended up to a maximum of 3 meters.
- Install the module in a suitable location within the detector or in a protective installation box near the detector.
- Connect the wires to the detector (refer to Figure 1).
- Connect the bus cable and turn on the control panel power supply.
- The control panel must be in service mode.
- Close the detector cover with the module installed inside.
Figure 1: Module Internal Parts and Wiring
Figure 1 illustrates the internal parts of the product and the module's wiring. It shows:
- 1 - Bus terminals
- 2 - Production code
- 3 - LEDs: Yellow indicates a fault or that the device is not registered. Red flashing indicates activation of any input.
- 4 - Module wires (refer to Table 1)
Table 1: Module Wires
Wire | Sense | Function |
---|---|---|
Red | +12 V | Power for the detector |
Black | GND | Common wire |
White | INP | Alarm input |
Blue | TMP | Anti-tamper input |
Yellow | TRB | Trouble input |
Technical Specifications
Energy | From the control panel bus 12 V DC (9...15 V) |
Standby current consumption | 8 mA (+ consumption of connected devices) for all inputs connected to GND |
Maximum current consumption | 12 mA (+ consumption of connected devices) |
Maximum current for connected detector | 50 mA |
Control device type (ACE) | Type B |
Dimensions | 16 x 30 x 12 mm |
Weight | 8 grams |
Classification | Security grade 2 / environmental class II (according to EN 50131-1). Note: valid only if integrated into a certified enclosure with security grade 2 or higher. |
Environment | General indoor |
Operating temperature range | -10 °C to +40 °C |
Average humidity | 75% RH, non-condensing |
Certification body | Trezor Test sro (No. 3025), Kiwa Nederland bv |
Conforms to | EN 50130-4, EN 55032, T 031, EN 50131-1, -3, EN IEC 63000 |
Declaration of Conformity
JABLOTRON a.s. hereby declares that the product JA-111H TRB is in compliance with the relevant EU harmonization legislation: Directives No. 2014/30/EU, 2011/65/EU. The original Declaration of Conformity is available on the website www.jablotron.com - Downloads Section.
Disposal Information
Proper disposal of this product helps conserve valuable resources and prevent potential negative effects on human health and the environment, which could otherwise arise from inappropriate waste disposal. Return the product to the retailer or contact the local authority for more information on the nearest designated collection point.
For an electronic version of this manual (available in other languages) or an installer version for JA-100+, scan the attached QR code.