JABLOTRON JA-111H TRB Wired Detector Interface Bus Module - Installation and Specifications

JABLOTRON JA-111H TRB Bus Module: Interface for Wired Detectors

The JA-111H TRB is a component of the JABLOTRON system. It is used to connect a wired detector with NC/NO outputs to the control panel bus. It powers the detector and reports its activation, tampering, and faults. The module must be installed by a qualified technician with a valid certificate issued by an authorized distributor.

Installation

Always disconnect the power when connecting the module to the system bus.

⚠️ The connected detector's power consumption must not exceed 50 mA (the module's power output is not overload protected).

It is designed for installation inside a standard wired detector (with contact outputs), but thanks to extended cables, it can also be installed outside the detector in a protected installation box.

  1. Install the module in a suitable location inside the detector or within a protected installation box, close to the detector. The cable can be extended up to 3 meters. When installing the module inside the detector, ensure that a short circuit does not occur due to insufficient insulation.
  2. Connect the cables to the detector (as per Figure 1).
  3. Connect the bus cable and power on the control panel.
  4. The control panel must be in service mode.
  5. Close the detector cover with the module installed inside.

Figure 1: Description of the product's internal parts and module cable connections.

  • 1 - bus terminals
  • 2 - production code
  • 3 - yellow LED indicates fault/unregistered device, red LED indicates activation of an input via blinking
  • 4 - module cables, see table below

Table 1: Module Cables

CableSignificanceFunction
Red+12VPower for detector
BlackGNDCommon ground
WhiteINPAlarm input
BlueTMPTamper input
YellowTRBTrouble input

System Enrollment and Configuration

Depending on the control panel type, use the recommended software or application - consult the control panel manual.

Technical Specifications

SpecificationValue
Powerfrom the control panel bus 12 V DC (9...15 V)
Quiescent current consumption8 mA (+ consumption of connected devices) all inputs connected to GND
Maximum current consumption12 mA (+ consumption of connected devices)
Maximum allowed current of detector50 mA
Control device type (ACE)Type B
Dimensions16 x 30 x 12 mm
Weight8 grams
ClassificationSecurity grade 2 / environmental class II (according to EN 50131-1). Note: valid only if integrated into a certified enclosure of security grade 2 or higher.
Environmentgeneral indoor
Operating temperature range-10 °C to +40 °C
Humidity75% relative humidity, non-condensing
Certification bodyTrezor Test sro (No. 3025), Kiwa Nederland bv
Complies withEN 50130-4, EN 55032, T 031, EN 50131-1, -3, EN IEC 63000

Declaration of Conformity:
JABLOTRON a.s. hereby declares that the product JA-111H TRB complies with the relevant Union harmonization legislation: Directives No. 2014/30/EU and 2011/65/EU. The original declaration of conformity can be found at www.jablotron.com, Downloads section.

Disposal Note:
Disposing of this product correctly will help save valuable resources and prevent potential negative effects on human health and the environment that could arise from improper waste management. Return the product to the distributor or contact your local authority for more information on the nearest designated collection point.

Company Information

JABLOTRON a.s.
Pod Skalkou 4567/33
46601 Jablonec nad Nisou
Czech Republic
Tel.: +420 483 559 911
Internet: www.jablotron.com

PDF preview unavailable. Download the PDF instead.

ja-111h-trb leg es from en origin mln20207 Adobe PDF Library 25.1.97

Related Documents

Preview JABLOTRON JA-111H TRB Bus Module: Installation and Technical Specifications
Comprehensive guide to the JABLOTRON JA-111H TRB bus module, detailing its function as an interface for wired detectors, installation instructions, wiring diagrams, technical specifications, and compliance information.
Preview JABLOTRON JA-111H TRB Bus Module - Installation and Technical Specifications
Comprehensive guide to the JABLOTRON JA-111H TRB bus module, covering installation, wiring, technical specifications, and compliance for wired alarm system detectors.
Preview JABLOTRON JA-111H TRB Bus Module: Installation and Specifications
Comprehensive guide to the JABLOTRON JA-111H TRB bus module, detailing its installation, wiring, technical specifications, and compliance for wired alarm system detectors.
Preview JABLOTRON JA-111H TRB Bus Module: Wired Detector Interface
Technical specifications and installation guide for the JABLOTRON JA-111H TRB bus module, an interface for wired detectors in JABLOTRON alarm systems. Includes wiring details, technical data, and compliance information.
Preview JA-111H TRB Bus Module – Interface for Wired Detectors
Technical specifications and installation guide for the JABLOTRON JA-111H TRB bus module, an interface for wired detectors in JABLOTRON alarm systems. It details installation steps, wiring, and product features.
Preview JABLOTRON JA-111H TRB Bus Module: Installation and Technical Specifications
Comprehensive guide to the JABLOTRON JA-111H TRB bus module, detailing installation procedures, wiring diagrams, technical specifications, and compliance information for wired detector integration into JABLOTRON alarm systems.
Preview JABLOTRON JA-111H TRB Busmodule: Installation and Technical Guide
Comprehensive guide to installing and configuring the JABLOTRON JA-111H TRB busmodule for wired detectors. Includes technical specifications, wiring diagrams, and compliance information.
Preview JABLOTRON JA-111H TRB Bus Module - Wired Detector Interface
Technical specifications and installation guide for the JABLOTRON JA-111H TRB bus module, an interface for wired detectors in JABLOTRON alarm systems. Learn about wiring, functions, and technical data.