JA-110A Internal Bus Siren
Part of the JABLOTRON system for alarm notifications.
Installation
This document is a machine translation from the original English. For any ambiguities or doubts, please consult the original version of the document. If you encounter errors or have questions, please contact Technical Support (contact details are at the end of this document).
The product is part of the JABLOTRON system. It is used for alarm notifications in a building. By pressing a button on the siren, the alarm notification (= confirmation that someone is in the building) can be acknowledged. The siren must be installed by a qualified technician with a valid certificate from an authorized distributor.
Important: Always connect the bus only when the system power is completely switched off.
- Remove the siren casing (buttons) from the plastic frame by pressing a side of the casing (1.) with a screwdriver, as shown in Fig. 1.
- Remove the middle part of the frame (3.) by pressing the 4 tabs indicated by the arrows (2.).
- Push the bus cable through the designated rectangular cutout in the plastic base.
- Fasten the plastic base with screws in the chosen location.
- Attach the plastic frame to the plastic base again.
- Connect the bus cable to the terminals (6) as shown in Fig. 2 and place the casing back into the plastic frame.
Note: The tamper sensors (7) must be positioned above the magnets in the plastic base.
Figure 1: Siren removal for installation. Shows how to detach the siren casing from the plastic frame using a screwdriver.
Figure 2: Internal view of the siren. Labels indicate: 1 - electronic latches, 2 - internal buttons, 3 - serial number, 4 - casing pins, 5 - piezo-electric siren, 6 - bus terminals, 7 - tamper sensor.
System Enrollment and Settings
Depending on the control panel type, use the recommended software or application. Consult the control panel manual for guidance.
Technical Specifications
Power Supply | 12 V DC bus (9...15 V) |
Quiescent Current | 5 mA |
Max Current | 30 mA |
Siren | Piezo-electric, 85 dB/m |
Warning Device Type | Indoor, Type X |
Dimensions | 80 x 80 x 28 mm |
Acoustic Performance | 80 dB / 1 m |
Classification | Security Class 2 / Environmental Class II (according to EN 50131-1) |
Environment | Indoor, general |
Weight | 70 grams |
Operating Temperature Range | -10 °C to +40 °C |
Average Operating Humidity | 75% RH, non-condensing |
Certification Body | Trezor Test sro (No. 3025) |
Complies with | EN 50131-1, -4, EN 50130-4, EN 55032, EN IEC 62368-1, EN IEC 63000 |
Can be operated according to | ERC REC 70-03 |
Recommended Screw | 2x 3.5 x 40 mm (countersunk head) |
Compliance and Disposal
JABLOTRON a.s. hereby declares that the JA-110A complies with the relevant European Union harmonization legislation: Directives No. 2014/30/EU, 2014/35/EU, 2011/65/EU, when used as intended. The original conformity assessment can be found on www.jablotron.com – Downloads section.
Disposal Notice: Proper disposal of this product saves valuable resources and prevents potential negative effects on human health and the environment that could arise from improper waste handling. Return the product to the dealer or contact your municipality for information on the nearest collection point.
For an electronic version of this document (available in other languages) or an installation version for JA-100, scan the accompanying QR-code (QR code excluded from output).