JABLOTRON JA-110A Internal Bus Siren
This document provides installation instructions and technical specifications for the JABLOTRON JA-110A internal bus siren. The product is part of the JABLOTRON system and is used for alarm indication within a building. Pressing a button on the siren can silence the alarm indication, confirming the presence of a person in the building. Installation must be performed by a trained technician holding a valid certificate from an authorized distributor.
Installation
Important: Always connect the bus only when the system is completely de-energized.
- Remove the siren's cover (buttons) from the plastic frame by pressing one side of the cover (labeled '1.') with a screwdriver, as shown in Figure 1.
- Remove the frame's middle part (labeled '3.') by pressing the four tabs marked with arrows (labeled '2.').
- Thread the bus cable through a designated rectangular cutout in the plastic base.
- Fasten the plastic base to the chosen location using screws.
- Reassemble the plastic frame with the plastic base onto the bottom piece.
- Connect the bus cable to the terminals (labeled '6') according to Figure 2 and reattach the housing to the plastic frame.
Note: Ensure the sabotage sensors (labeled '7') are positioned above the magnets in the plastic base.
Diagram Description (Figure 1): Illustrates the disassembly process. It shows the siren cover being removed from the plastic frame by pressing a side clip (labeled '1.'). The middle part of the frame (labeled '3.') is then removed by pressing four tabs (indicated by arrows, labeled '2.').
Diagram Description (Figure 2): Shows the internal components of the siren. The numbered parts are: 1 - electronics locks, 2 - internal buttons, 3 - serial number, 4 - housing pins, 5 - piezoelectric siren, 6 - bus terminals, and 7 - sabotage sensor.
System Registration and Settings
Depending on the control panel type, use the recommended software or application. Refer to the control panel's manual for specific instructions.
Technical Specifications
Specification | Details |
---|---|
Power Supply | from the bus 12 V DC (9...15 V) |
Quiescent Current Consumption | 5 mA |
Maximum Current Consumption | 30 mA |
Siren Type | piezoelectric, 85 dB/m |
Type of Warning Device | indoor, type X |
Dimensions | 80 x 80 x 28 mm |
Acoustic Performance | 80 dB / 1 m |
Classification | Security Class 2 / Environmental Class II. (according to EN 50131-1) |
Environment | indoor general |
Weight | 70 grams |
Operating Temperature Range | -10 °C to +40 °C |
Average Operating Humidity | 75% RF, non-condensing |
Certification Body | Trezor Test sro (No. 3025) |
Complies with | EN 50131-1, -4, EN 50130-4, EN 55032, EN IEC 62368-1, EN IEC 63000 |
Can be operated according to | ERC REC 70-03 |
Recommended Screw | Ø 3.5 x 40 mm (countersunk head) |
Compliance and Disposal
JABLOTRON a.s. hereby declares that the JA-110A is in compliance with the relevant harmonisation legislation of the European Union: Directive No.: 2014/30/EU, 2014/35/EU, 2011/65/EU, when used as intended. The original of the conformity assessment is available at www.jablotron.com in the downloads section.
Note on Disposal: By disposing of this product correctly, you help to conserve valuable resources and prevent potential negative effects on human health and the environment, which might otherwise arise from inappropriate waste disposal. Please return the product to your seller or contact your local authority for more information on the nearest collection point.
For an electronic version of this document (available in other languages) or an installation version for JA-100, scan the enclosed QR code.