ALED® FIELD-ADJUSTABLE INSTALLATION INSTRUCTIONS

Brand: RAB Lighting

Models: ALEDXXS, ALEDXS

About RAB Lighting

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. For comments, please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com.

Important Information

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.

CAUTION: For proper weatherproof function all gaskets must be seated properly and all screws inserted and tightened firmly.

Mounting to Pole

For use with standard RAB pole drilling. See Pole Drilling Pattern Detail ([Figure 5]).

  1. Place Gasket between the Pole Mount Bracket and drilled Pole as shown in [Figure 1]. Line-up center hole of Gasket with center hole in the Pole Drilling Pattern.
  2. Place 3/8-16 Bolt (provided) from the Pole Mount Bracket through the top hole of the Gasket to the Pole. Use Nut, Lockwasher and Washer (provided) and tighten inside the Pole.
  3. Loosen (2) Door Screws and open Door as shown in [Figure 1].
  4. Loosen (1) Cleat Screw. Separate Cleat/Door Assembly from fixture. Set desired Color Temperature (CCT), Power (W) and/or Photocell ON/OFF position (see Field Adjustment instructions [Figure 3]).
  5. Secure Cleat/Door Assembly to the Pole Mount Bracket using (2) Stainless Steel Screws (provided).
  6. Slide fixture on Cleat/Door Assembly and secure using (1) Cleat Screw.
  7. Make the necessary wiring connections and knot the wires for strain relief. Wire the fixture using UL listed wire connectors according to NEC and local codes. See wiring diagram, [Figure 6], [Figure 7].
  8. Install the Pole Cap.
[Figure 1]: A diagram illustrating the mounting of the ALED fixture to a pole. It shows the Pole Mount Bracket, Gasket, Pole, a 3/8-16 Bolt, Nut, Lockwasher, and Washer used for securing the bracket to the pole. It also depicts the Cleat/Door Assembly, Door Screws, Cleat Screw, and Pole Cap.

Round Pole Adaptor Accessory

For use with standard RAB Pole Drilling Pattern Detail.

  1. Drill Round Pole using the dimensions shown in Pole Drilling Pattern Detail ([Figure 5]).
  2. Trim Adaptor Gasket supplied with ALED.
  3. A 3/8-16 Bolt may not be long enough as originally supplied with ALED. A longer Fixture Bolt is supplied with the RPA LED kits.
  4. Place Round Pole Adaptor (sold separately) and RPA Gasket (sold separately) between the Pole Mount Bracket and drilled Pole as shown in [Figure 2]. Line up top holes of the Gaskets and Round Pole Adaptor with top hole in the Pole Drilling Pattern.
  5. Place 3/8-16 Bolt from the ALED through the top hole of the RPA and Gaskets to the Round Pole. Use Nut, Lockwasher and Washer and tighten inside the Pole.
  6. Refer to Mounting to Pole section above #3 through #8 to complete the installation.
[Figure 2]: A diagram showing the installation of the Round Pole Adaptor accessory. It includes the Pole Mount Bracket, Cleat/Door Assembly, Trimmed Gasket, RPA Gasket, Round Pole Adaptor, and the hardware (Nut, Lockwasher & Washer) used to attach it to the pole.

Field Adjustment

Photocell Operation

This product is equipped with a photocell. Photocell factory setting is set to the “OFF” position. Should you wish to enable the Photocell "ON" feature slide the center switch to the “ON” position ([Figure 3]). If the Photocell is set to the “ON” position and it is daylight, it may take up to 60-seconds for the light to turn off.

Color Temperature (CCT) Selection

This product is equipped with 3000K, 4000K or 5000K (CCT) Color Temperature selection. For maximum light output use the 4000K Color Temperature.

Power (Wattage) Selection

This product is equipped with power output selection.

Follow instructions below to change Color Temperature (CCT), Power (W) and/or Photocell operation from factory settings.

Factory Settings: ALEDXXS 10W / 4000K / Photocell/OFF; ALEDXS 24W / 4000K / Photocell/OFF

  1. Locate the Selector Switches inside of housing as shown in [Figure 3].
  2. Select Color Temperature (CCT), Power (W) and/or Photocell ON/OFF function by sliding the respective switch to the desired setting.
[Figure 3]: Two diagrams, one for ALEDXXS and one for ALEDXS, showing the interior of the fixture housing with selector switches. These switches are labeled for Color Temperature (CCT), Photocell ON/OFF, and Power (W).

Wiring

LCBS/MVS Wiring (Available for ALEDXS Size Only)

Universal voltage driver permits operation at 120V through 277V 50 or 60 Hz. For LCBS/MVS wiring follow the wiring directions as shown in [Figure 4].

  1. Connect the black fixture lead to the [LINE] supply lead.
  2. Connect the white fixture lead to the [COMMON] supply lead.
  3. Connect the [GROUND] wire from fixture to supply ground.
  4. Connect the pink fixture lead to the pink LCBS/MVS lead.
  5. Connect the purple/white MVS+ fixture lead to the purple LCBS/MVS lead.
  6. Connect the black/white fixture lead to the black/white LCBS/MVS lead.
  7. Cap the purple fixture lead if present. DO NOT connect.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.

[Figure 4]: A wiring diagram for LCBS/MVS connections for ALEDXS. It illustrates how to connect the fixture's leads (black, white, pink, purple/white, black/white) to the supply leads (LINE, COMMON, GROUND) and specific LCBS/MVS leads (pink, purple, black/white). It also notes not to connect DIM V+ or DIM V- to line voltage or ground.

0-10V Dimmable Wiring

Universal voltage driver permits operation at 120V through 277V 50 or 60 Hz. For 0-10V dimming follow the wiring directions as shown in [Figure 6] and [Figure 7].

  1. Connect the black fixture lead to the [LINE] supply lead.
  2. Connect the white fixture lead to the [COMMON] supply lead.
  3. Connect the [GROUND] wire from fixture to supply ground.
  4. Connect the purple fixture lead to the ([+ DIM V]) lead.
  5. Connect the pink fixture lead to the ([- DIM V]) lead.
  6. Cap the Purple/White and Black/White fixture leads. DO NOT connect.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.

[Figure 6]: A wiring diagram for 0-10V dimmable connections for ALEDXXS. It shows connections for LINE, COMMON, GROUND, and fixture leads (black, white, purple for V+, pink for V-, yellow for Vaux 12V).
[Figure 7]: A wiring diagram for 0-10V dimmable connections for ALEDXS. Similar to [Figure 6], it shows connections for LINE, COMMON, GROUND, and fixture leads (black, white, purple for V+, pink for V-, yellow for Vaux). It also shows specific fixture wire labels like MVS+ SOLID WHITE & PURPLE STRIPE and Vaux SOLID WHITE & BLACK STRIPE.

Pole Drilling Pattern Detail

For non-RAB poles use these dimensions to drill the pole. This template is not to scale. Please use measurements shown. For RPA and ALED mounting bottom hole is not necessary.

[Figure 5]: A diagram showing the dimensions for drilling a pole. It provides measurements for two hole diameters (Ø.425 and Ø.625) and their positions (1.00, 2.000, 4.00).

Cleaning & Maintenance

CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

  1. Clean lens with non-abrasive glass cleaning solution.
  2. Do not open the fixture to clean the LED. Do not touch the LED.

Troubleshooting

  1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
  2. Is the fixture grounded properly?
  3. Is the photocell, if used, functioning properly?

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Models: ALEDXXS, ALEDXS, ALEDXXS LED Lighting, ALEDXXS, LED Lighting, Lighting

File Info : application/pdf, 4 Pages, 832.52KB

PDF preview unavailable. Download the PDF instead.

aled-xxs-xs instructions

References

Adobe PDF Library 17.0 Adobe InDesign 20.2 (Windows)

Related Documents

Preview RAB SLIM Field-Adjustable LED Lighting Installation Guide
Comprehensive installation instructions for RAB Lighting's SLIM series field-adjustable LED fixtures, covering mounting, electrical connections, field adjustments for photocell, CCT, wattage, optic angle, and troubleshooting.
Preview RAB Lighting BULLET® Field-Adjustable LED Floodlight Installation Guide
Comprehensive installation, wiring, and adjustment guide for RAB Lighting's BULLET® Field-Adjustable LED floodlights, including sensor operation, mounting, and troubleshooting.
Preview RAB X34 Field-Adjustable LED Fixture Installation Guide
Comprehensive installation instructions for RAB Lighting's X34 series field-adjustable LED fixtures, covering mounting options, wiring, field adjustments for CCT and power, photocell operation, and Lightcloud Blue smart control.
Preview RAB X34 Series Field-Adjustable LED Floodlight Installation Instructions
Comprehensive installation guide for RAB Lighting's X34 series field-adjustable LED floodlights, covering mounting, wiring, field adjustments (CCT, Power, Photocell), and maintenance.
Preview RAB Field-Adjustable BOA Installation Instructions
Comprehensive installation guide for RAB's Field-Adjustable BOA LED lighting fixtures, covering wall, ceiling, surface, recessed, and pendant mounting methods, as well as field adjustments and battery backup operation.
Preview RAB Lighting H17 & H17XL LED Fixture Installation Guide
Comprehensive installation instructions for RAB Lighting H17 and H17XL LED fixtures, covering hook, ceiling, and pendant mounting, wiring, CCT/wattage adjustment, and maintenance.
Preview RAB A17 XFU Field Adjustable LED Area Light Installation Guide
Comprehensive installation instructions for the RAB A17 XFU field adjustable LED area light. Learn how to mount the fixture, adjust CCT and power, and perform 0-10V dimming wiring. Includes safety precautions and maintenance tips.
Preview RBAY15 Series LED Luminaire Installation and Field Adjustment Guide
Comprehensive installation, field adjustment, and maintenance guide for RAB Lighting's RBAY15S, RBAY15M, and RBAY15L LED luminaires. Includes mounting, wiring, sensor integration, battery backup, and troubleshooting instructions.