INSTRUCTIONS
A17TM XFU FIELD ADJUSTABLE AREA LIGHT INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

A17 XFU
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE. RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside. WARNING: Do not use an electric generator to test LED fixtures. WARNING: Min 75 °C SUPPLY CONDUCTORS.

Fixture
MOUNTING THE UNIVERSAL ADJUSTABLE

35°

POLE ARM ON THE FIXTURE

Arm

Notice: Adjustable angle is 0-35°
1. Remove the Arm mounting Screws on the Fixture. Open the Arm Cover and run the wires through the Arm as shown in Fig. 1.
2. Install the Arm on the Fixture, replace the Arm Cover and secure with Screws as shown in Fig. 2.

FIG. 1 Arm Cover Screws

Square Pole Mount
1. Place the Bolster Plate inside the Pole as shown in Fig. 3.
2. Fix Arm to Square Pole with Bolt.
3. Open the Arm Cover and pull the wires into the junction box (supplied by others).
4. Feed supply wires from the Pole to connect to the Arm. Make appropriate wire connections per NEC in an approved enclosure (Fig. 8).
5. Use bolts to tighten to the Pole.

Bolster Plate Pole

Bolt Arm Arm Cover

Round Pole Mount

1. Place the Bolster Plate inside the Pole as shown in Fig. 3.

2. Fix Arm to Round Pole with Bolt (Fig. 4).

3. Remove Silicone Plate (Fig. 4).

4. Open the Arm Cover and pull the wires into the junction box (supplied by others).

5. Feed supply wires from the Pole to connect to the Arm.

Pole

Make appropriate wire connections per NEC in an

approved enclosure (Fig. 8).

6. Use bolts to tighten to the Pole.

FIG. 2 Arm
FIG. 3

INSTRUCTIONS
A17TM XFU FIELD ADJUSTABLE AREA LIGHT INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We'd love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

FIELD ADJUSTMENT

0-10V DIMMABLE WIRING

Follow instructions below to change Fixture Color Temperature (CCT) or Power (W) from the factory settings. WARNING: Do not open or remove Respirator Plug (Fig 5.)
Factory Settings: 4000K (CCT), 70W (Power)
Color Temperature (CCT) Adjustment:
1. Unscrew the CCT Selection Switch Cap as shown in Fig. 5. 2. Adjust the CCT by sliding the respective switch to the desired
value as shown in Fig. 6. 3. Install and tighten the 3/4" Caps.
Power (W) Adjustment:
1. Open the Driver Box Cover by Latch (2) and remove Screws (2 ) as shown in Fig. 5.
2. Locate Power (W) Adjusting Knob as shown in Fig. 7. 3. Select Power (W) setting by turning the respective switch to the
desired value as shown in Fig. 7. 4. Close the Driver Cover Box and secure with Screws (2) and close
Latches (2).

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For 0-10 Dimming, follow the wiring directions as shown in Fig. 8.
1. Connect the black/brown fixture lead to the LINE supply lead.
2. Connect the white/blue fixture lead to the COMMON supply lead.
3. Connect the green/yellow wire from fixture to supply ground. Do NOT connect the GROUND of the dimming fixture to the output.
4. Connect the purple fixture lead to the DIM V+ lead.
5. Connect the pink/gray fixture lead to the DIM V- lead.
6. Cap the yellow fixture lead, if present. Do NOT connect.

FIG. 8

LINE COMMON (+) DIM V+ (-) DIM V-

BLACK/BROWN WHITE/BLUE PURPLE PINK/GRAY

Screw (2)

GROUND

GREEN/YELLOW

CCT Selection Switch Cap

Latch (2)

FIG. 5

Respirator Plug do not open/do not remove.

CCT Selector Switch FIG. 6

CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized. 1. Clean Polycarbonate lens with non-abrasive glass
cleaning solution. 2. Do not open the fixture to clean the LED. Do not touch
the LED.

FIG. 7 Power (W) Adjusting Knob

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

© 2021 RAB LIGHTING Inc.
A17 XFU - IN-1021 73711-RAB

Easy Answers
rablighting.com Visit our website for product info

Tech Help Line Call our experts: 888 722-1000

e-mail Answered promptly - sales@rablighting.com

RAB WARRANTY: RAB's warranty is subject to all terms and conditions found at rablighting.com/warranty

Free Lighting Layouts Answered online or by request


Adobe PDF Library 15.0 Adobe InDesign 16.0 (Windows)