RBAY15 Series Field-Adjustable LED Luminaire Installation Guide
This guide provides instructions for the installation, field adjustment, and maintenance of RAB Lighting's RBAY15S, RBAY15M, and RBAY15L LED luminaires.
Important Safety Information
IMPORTANT: READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved. Ensure installation is performed by a qualified electrician. Suitable for damp locations.
V-Hook / Chain Mounting
This method is used to mount the housing to a sturdy ceiling structure.
- Secure the provided V-Hooks (2) through the side slots on the housing.
- Attach the 3.28ft Chain (2) to the V-Hooks.
- Remove the Access Plate (location varies by model: RBAY15M & RBAY15L use the plate shown in Figure 2; RBAY15S uses the plate shown in Figure 3).
- Feed supply wires through a strain relief connector.
- Make electrical connections as shown in the wiring diagram (Figure 21), using approved wiring connectors and adhering to local NEC codes.
- Carefully push all wires back into the housing, ensuring they are not pinched.
- Reinstall the Access Plate and secure it with the supplied screw (1).
Diagram Description (Figure 1): Illustrates V-Hooks being inserted into the side slots of the luminaire housing.
Diagram Description (Figure 2): Shows the V-Hook and chain connection to the housing for RBAY15M/RBAY15L models, including the access plate for feeding supply wires.
Diagram Description (Figure 3): Shows the V-Hook and chain connection to the housing for RBAY15S models, including the access plate for feeding supply wires.
Pendant Mounting (RBAY15S)
Requires an accessory kit (Model# PMKRBAY15S) and components supplied by others.
- Select the desired length for a 3/4" NPS Pendant Stem (by others).
- Install the Pendant Junction Box (ordered separately) onto the Pendant Stem and secure it using locknuts (by others).
- Mount the Housing onto the Pendant Junction Box by engaging the hook feature and tightening the two provided screws.
- Remove the knockout from the side panel.
- Pull supply wires through the side knockout and feed them through the provided Flex Conduit.
- Secure the Flex Conduit to the side panel.
- Secure the side panels with the two provided screws. Ensure wires are not pinched.
- Wire the housing leads to the supply wires using UL-listed wire connectors according to NEC and local codes.
- Push all wires back into the housing.
- Secure the Flex Conduit to the Access Plate.
Diagram Description (Figure 4): Depicts the components for RBAY15S pendant mounting, including pendant screws, side panels, and locknuts.
Diagram Description (Figure 5): Illustrates the process of attaching a pendant junction box to a pendant stem using locknuts.
Diagram Description (Figure 6): Shows the luminaire housing being mounted to a pendant junction box via hooks and screws, with wires routed through a knockout and flex conduit, and the flex conduit secured to the access plate.
Pendant Mounting (RBAY15M/RBAY15L)
Requires an accessory kit (Model# PMKRBAY15) and components supplied by others.
- Select the desired length for a 3/4" NPS Pendant Stem (by others).
- Install the Pendant Junction Box (ordered separately) onto the Pendant Stem and secure it using locknuts (by others).
- Pull supply wires and connect them to the housing leads using UL-listed wire connectors according to NEC and local codes.
- Push all wires back into the housing and secure the Access Plate with the provided screw.
- Mount the Housing onto the Pendant Junction Box by securing it into the hook feature and tightening the two provided screws.
- Install the side panels using the two provided screws. Ensure wires are not pinched.
Diagram Description (Figure 7): Shows components for RBAY15M/RBAY15L pendant mounting, including side panels and locknuts.
Diagram Description (Figure 8): Illustrates mounting the housing onto the pendant junction box using hooks and screws, and installing the side panels for RBAY15M/RBAY15L.
Surface Mounting (RBAY15S)
Requires an accessory kit (Model# SMKRBAY15S) and fasteners supplied by others.
- Install the Surface Mounting Bracket (ordered separately) to a sturdy surface using fasteners (by others).
- Wire the housing leads to supply wires using UL-listed wire connectors according to NEC and local codes. Secure the Access Plate with the provided screw (1).
- Mount the Housing onto the Surface Mounting Bracket by securing it with the hook (4) feature and the two provided screws.
Diagram Description (Figure 9): Shows the installation of a surface mounting bracket onto a surface using fasteners.
Diagram Description (Figure 10): Illustrates mounting the luminaire housing onto the surface mounting bracket using hooks and screws for RBAY15S.
Surface Mounting (RBAY15M/RBAY15L)
Requires an accessory kit (Model# SMKRBAY15) and screws supplied by others.
- Install the Surface Mounting Bracket (ordered separately) to a sturdy surface using screws (by others).
- Wire the housing leads to supply wires using UL-listed wire connectors according to NEC and local codes. Secure the Access Plate with the provided screw (1).
- Mount the Housing onto the Surface Mounting Bracket by securing it with the hook (4) feature and the two provided screws.
Diagram Description (Figure 11): Illustrates mounting the luminaire housing onto the surface mounting bracket using hooks and screws for RBAY15M/RBAY15L.
Field Adjustment: Power (W) and Color Temperature (CCT)
The fixture's power and color temperature can be adjusted after installation.
Factory Settings:
- RBAY15S: 130W / 100W / 80W
- RBAY15M: 260W / 220W / 160W
- RBAY15L: 400W / 320W / 260W
Adjustment Procedure:
- Locate the selector switches on the side of the housing (Figure 12 for RBAY15M/RBAY15L, Figure 13 for RBAY15S).
- Slide the respective switch to select the desired Color Temperature (CCT) and/or Power (W) value.
Diagram Description (Figure 12): Shows the location of the Color Temperature (CCT) and Power (W) selector switches on the side of the housing for RBAY15M and RBAY15L models.
Diagram Description (Figure 13): Shows the location of the Color Temperature (CCT) and Power (W) selector switches on the side of the housing for the RBAY15S model.
Lens Replacement
The lens can be rotated in the field for different light distributions.
- Remove the side cap and carefully slide the lens off the housing.
- Rotate the lens 180 degrees. Do not flip it.
- Slide the rotated lens back onto the luminaire.
- Reinstall the side cap and tighten the screws securely.
Diagram Description (Figure 14): Illustrates removing the side cap and sliding the lens off the luminaire.
Diagram Description (Figure 15): Shows the lens being rotated 180 degrees.
Diagram Description (Figure 16): Depicts sliding the rotated lens back onto the luminaire and reinstalling the side cap.
Diagram Description (Figure 17): Shows the side cap securely fastened after the lens replacement procedure.
Wire Guard
A wire guard can be installed for protection. Purchase the correct size wire guard from the manufacturer. Place the wire guard on the lamp and fix it with screws.
Diagram Description (Figure 18): Illustrates placing a wire guard onto the luminaire and securing it with screws.
MVS/PIR Sensor Installation
For units ordered with an MVS or PIR Sensor, follow these steps:
- Remove the Sensor Base Plug located on the housing.
- Insert the MVS or PIR Sensor into the Sensor Base Plug and turn to secure it.
- Refer to the specific MVS/PIR Sensor instructions for pre-set and programmable settings.
- An optional remote control (Model# MSR1) can be used for user programming.
Diagram Description (Figure 19): Shows the location of the sensor base plug on the luminaire housing.
Diagram Description (Figure 20): Depicts inserting an MVS or PIR sensor into the base plug and securing it by turning.
0-10V Dimmable Wiring
The universal voltage driver operates at 120V through 277V, 50 or 60 Hz. For 0-10V dimming, follow the wiring directions below.
- Connect the LINE supply lead (typically Black) to the hot AC supply line.
- Connect the COMMON supply lead (typically White) to the common AC supply line.
- Connect the GROUND lead (typically Green) to the ground connection.
- Connect the DIM V+ lead (typically Purple) to the dimming control signal positive.
- Connect the DIM V- lead (typically Pink) to the dimming control signal negative.
Note: Do not connect DIM V+ (purple) or DIM V- (pink) to line voltage or supply ground.
Diagram Description (Figure 21): A wiring diagram illustrating the connections for 0-10V dimming, showing connections for LINE (Black), COMMON (White), GROUND (Green), DIM V+ (Purple), DIM V- (Pink), and Vaux (Black/White).
Battery Backup Models: Wiring
CAUTION: Voltage can be present in the BATTERY. To prevent high voltage on output leads, the Inverter connector must remain open until installation is complete and AC power is supplied to the emergency driver. Use only 120-277V, 50/60 Hz supply voltage.
An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver.
- Connect the UNSWITCHED HOT lead to the HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect the SWITCHED HOT lead to the external switched line.
- Connect the pink DIM (-) lead to the dimming control signal negative.
- For 0-10V dimming, connect the purple DIM (+) lead and the pink DIM (-) lead to the 0-10V dimming connection. Do not connect GROUND to the output leads.
- Cap and insulate all unused leads.
The CHARGING INDICATOR LIGHT should illuminate to show the battery is charging.
Diagram Description (Figure 22): A wiring diagram for battery backup models, showing connections for the light fixture, AC supply (Unswitched Line, Switched Line, Neutral, Ground), and dimming leads (DIM+, DIM-).
Battery Backup Models: Operation
- When AC power is applied, the charging indicator light illuminates, indicating the battery is charging.
- During a power failure, the system automatically switches to emergency power from the internal battery, operating at reduced illumination.
- When AC power is restored, the emergency driver automatically returns to charging mode.
Battery Backup Models: Maintenance
While routine maintenance is not required, periodic checks are recommended:
- Visually inspect the charging indicator light monthly; it should be illuminated.
- Perform a short duration test monthly by pressing the Test Button. The fixture should operate for at least 30 seconds.
- Conduct a 90-minute discharge test annually. The fixture should operate at reduced illumination for a minimum of 90 minutes.
Diagram Description (Figure 23): Shows the location of the Test Button on RBAY15S and RBAY15M/RBAY15L models for battery backup testing.
Troubleshooting (Battery Backup Models)
- If the charging indicator light does not illuminate after pressing the Test Button, check the battery connection.
Cleaning & Maintenance
Clean the luminaire only with a solution of warm water and any mild, non-abrasive household detergent. Rinse with clean water and wipe dry.
Troubleshooting
Note: These instructions do not cover all details or variations in equipment, nor do they provide for every possible situation during installation, operation, or maintenance.
Contact Information and Warranty
For comments or inquiries, contact the Marketing Department at 888-RAB-1000 or email marketing@rablighting.com.
Visit rablighting.com for product information and easy answers.
For technical assistance, call experts at 888-722-1000.
For prompt sales inquiries, email sales@rablighting.com.
RAB Warranty: RAB's warranty is subject to all terms and conditions found at rablighting.com/warranty.
Free lighting layouts are available online or by request.
© 2022 RAB LIGHTING Inc.