AprilAire Air Cleaner
INSTALLATION & OWNER'S MANUAL
Models: 1110, 1210, 1310, 1410, 1910, 2210, 2216, 2310, 2410, & 2416
Models 1210, 1410, 2210, and 2410 shown.
READ AND SAVE THESE INSTRUCTIONS
SAFETY INSTRUCTIONS
[Warning]
ATTENTION INSTALLER: Read this manual before installing. Improper installation or maintenance may cause property damage or injury. It is recommended that installation, service, and maintenance be performed by a trained service technician. This product must be installed in compliance with all local, state, and federal codes.
ELECTRIC SHOCK HAZARD: 120 volts may cause serious injury from electric shock. Disconnect electrical power to the HVAC system before starting installation or servicing. Leave power disconnected until installation/service is completed.
[Notice]
EQUIPMENT DAMAGE MAY OCCUR IF INSTALLATION INSTRUCTIONS ARE NOT FOLLOWED.
- Do not install the air cleaner on the warm air supply or in an area where the temperature may exceed 140°F. This may include areas above heat exchangers in downflow furnaces or above exhaust flues in lowboy furnace cold air returns.
- Do not install air cleaner downstream of a UV light. UV lamps will cause degradation of the filtering media.
[Caution]
SHARP EDGES MAY CAUSE INJURY FROM CUTS. Use care when cutting plenum openings and handling ductwork. Always wear glasses/goggles and gloves when installing the unit.
Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions.
SPECIFICATIONS
1110 | 1210, 2210, 2216 | 1310, 2310 | 1410, 2410, 2416 | 1910 | |
---|---|---|---|---|---|
Airflow Capacity | Up to 1200 CFM maximum | Up to 2000 CFM maximum | Up to 1200 CFM maximum | Up to 2000 CFM maximum | Up to 2000 CFM maximum |
Replacement Air Filter Model | 110 or 113 with Self-Seal™ | 210, 213, 213CBN or 216 with Self-Seal | 310 or 313 with Self-Seal | 410, 413, 413CBN or 416 with Self-Seal | 910 or 913 with Self-Seal |
Maximum Equipment Weight | Cabinet will support 250 lb. static load | Cabinet will support 400 lb. static load | |||
Air Cleaner Operating Environment | Temperature: 0°F–140°F, Humidity: 0–90% non-condensing |
DIMENSIONS (INCHES)
Diagram showing cabinet dimensions A through H, with and without a door.
AIR CLEANER MODEL | A | B | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|---|
1110 | 157/16 | 201/16 | 173/8 | 63/4 | 221/16 | 173/8 | 157/16 | 173/4 |
1210, 2210, 2216 | 193/4 | 253/8 | 213/16 | 63/4 | 273/8 | 213/16 | 193/4 | 221/16 |
1310, 2310 | 181/16 | 201/16 | 157/8 | 63/4 | 221/16 | 157/8 | 181/16 | 203/8 |
1410, 2410, 2416 | 157/16 | 281/16 | 237/8 | 63/4 | 301/16 | 237/8 | 157/16 | 173/4 |
1910 | 223/4 | 201/16 | 157/8 | 63/4 | 221/16 | 157/8 | 223/4 | 251/16 |
PRESSURE DROP CHART
This chart details the static pressure drop (in. w.c.) for various AprilAire air filters across a range of airflow capacities (CFM). The filters are categorized by MERV rating and their effectiveness against specific contaminants like odors, allergens, and general dust.
FILTER MODEL | STATIC PRESSURES AT VARIABLE CFM (in. w.c.)* | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
200 | 400 | 600 | 800 | 1000 | 1200 | 1400 | 1600 | 1800 | 2000 | 2200 | 2400 | 2600 | 2800 | 3000 | |
216 (MERV 16) | 0.06 | 0.09 | 0.13 | 0.17 | 0.23 | 0.29 | 0.36 | ||||||||
416 (MERV 16) | 0.07 | 0.10 | 0.13 | 0.18 | 0.24 | 0.31 | |||||||||
516 (MERV 16) | 0.04 | 0.05 | 0.07 | 0.09 | 0.10 | 0.13 | 0.15 | 0.18 | 0.21 | 0.24 | 0.27 | 0.31 | |||
213CBN (MERV 13) | 0.04 | 0.07 | 0.10 | 0.13 | 0.17 | 0.21 | 0.25 | 0.30 | 0.35 | ||||||
413CBN (MERV 13) | 0.04 | 0.07 | 0.10 | 0.14 | 0.19 | 0.24 | 0.29 | 0.36 | 0.43 | ||||||
513CBN (MERV 13) | 0.03 | 0.04 | 0.05 | 0.07 | 0.08 | 0.10 | 0.12 | 0.15 | 0.17 | 0.20 | 0.22 | 0.25 | 0.29 | 0.32 | |
113 (MERV 13) | 0.03 | 0.07 | 0.11 | 0.16 | 0.22 | 0.29 | |||||||||
213 (MERV 13) | 0.02 | 0.04 | 0.06 | 0.09 | 0.12 | 0.15 | 0.19 | 0.23 | 0.27 | 0.31 | |||||
313 (MERV 13) | 0.03 | 0.05 | 0.09 | 0.13 | 0.17 | 0.23 | |||||||||
413 (MERV 13) | 0.02 | 0.05 | 0.07 | 0.10 | 0.14 | 0.17 | 0.22 | 0.26 | 0.31 | 0.37 | |||||
513 (MERV 11) | 0.01 | 0.02 | 0.04 | 0.05 | 0.05 | 0.07 | 0.08 | 0.10 | 0.11 | 0.13 | 0.15 | 0.17 | 0.18 | 0.20 | 0.23 |
613 (MERV 11) | 0.02 | 0.05 | 0.07 | 0.10 | 0.14 | 0.17 | 0.22 | 0.26 | 0.31 | 0.37 | |||||
813 (MERV 11) | 0.02 | 0.04 | 0.06 | 0.09 | 0.12 | 0.15 | 0.19 | 0.23 | 0.27 | 0.31 | |||||
913 (MERV 11) | 0.04 | 0.07 | 0.10 | 0.13 | 0.17 | 0.22 | 0.25 | 0.30 | 0.35 | ||||||
110 (MERV 11) | 0.02 | 0.05 | 0.06 | 0.10 | 0.14 | 0.20 | |||||||||
210 (MERV 11) | 0.02 | 0.03 | 0.04 | 0.06 | 0.08 | 0.11 | 0.13 | 0.16 | 0.19 | 0.22 | |||||
310 (MERV 11) | 0.02 | 0.04 | 0.06 | 0.10 | 0.14 | 0.19 | |||||||||
410 (MERV 11) | 0.02 | 0.03 | 0.05 | 0.07 | 0.09 | 0.12 | 0.15 | 0.19 | 0.22 | 0.27 | |||||
510 (MERV 11) | 0.02 | 0.02 | 0.03 | 0.04 | 0.04 | 0.05 | 0.06 | 0.07 | 0.09 | 0.10 | 0.12 | 0.14 | 0.15 | 0.17 | 0.19 |
610 (MERV 11) | 0.02 | 0.03 | 0.05 | 0.07 | 0.09 | 0.12 | 0.15 | 0.19 | 0.22 | 0.27 | |||||
810 (MERV 11) | 0.02 | 0.03 | 0.04 | 0.06 | 0.08 | 0.11 | 0.13 | 0.16 | 0.19 | 0.22 | |||||
910 (MERV 11) | 0.03 | 0.05 | 0.07 | 0.09 | 0.12 | 0.15 | 0.18 | 0.22 | 0.27 |
*Highest value shown is maximum recommended airflow capacity.
INSTALL THE AIR CLEANER CABINET
LOCATING THE AIR CLEANER
- Leave sufficient space in front of the air cleaner for the removal of the filter (see FIGURE 1).
- DO NOT INSTALL DOWNSTREAM OF A UV LIGHT. UV lamps will cause degradation of the filtering media.
- FIGURES 2-4 show typical applications.
Diagram illustrating the required clearance for filter removal, referencing Dimension E on page 2.
Diagram showing horizontal installation with airflow and indicating a maximum angle of 30 degrees for ductwork on either side.
Diagram illustrating a highboy platform installation, showing airflow and the plenum box.
Diagram detailing a typical upflow installation configuration, showing airflow, plenum box, and maximum angle recommendations of 30 degrees and 45 degrees for connected ductwork.
INSTALLATION
- Disconnect power to the furnace or air handler at the electrical service panel.
- Remove the air cleaner door from the outer housing and pull out the filter (see FIGURE 5).
- If replacing an existing filter or air cleaner, remove the old unit from the system and thoroughly clean the blower compartment.
- Cut an opening in the furnace/air handler to match the inside opening of the air cleaner outer housing. Ensure the opening in the furnace/air handler is entirely within the blower compartment.
- Use screws (field supplied) to mount the outer housing to the furnace/air handler. There is no inlet or outlet side on the outer housing (the outer housing can be mounted on the left or right side of the furnace/air handler).
NOTE FOR UPFLOW INSTALLATIONS: Provide support under the outer housing to ensure the quality of the seals (see FIGURE 6).
- Mount the return ductwork to the outer housing.
- Seal all connections using mastic, foil tape, or silicone based caulk.
- Install the filter (see FIGURE 7).
- Install the door.
- Reconnect power to the furnace or air handler at the electrical service panel.
- Make a cooling or heating call to test the system and make sure it operates as desired. Ensure there are no air leaks in the air cleaner or return ductwork joints.
Illustration of removing the air cleaner door and pulling out the filter.
Illustration showing how to provide support under the outer housing for upflow installations to ensure seal quality.
Demonstrates the correct method for inserting the air filter. The filter should be oriented with the airflow indicator pointing towards the furnace or air handler. The filter slides into place within the top and bottom rails before the door is reinstalled.
[Warning]
ELECTRIC SHOCK HAZARD: 120 volts may cause serious injury from electric shock. Disconnect electrical power to the HVAC system before starting installation or servicing. Leave power disconnected until installation/service is completed.
OPERATION
Choosing a genuine AprilAire Whole-House Air Cleaner means choosing Healthy Air. This air cleaner is engineered to work with AprilAire Air Filters to remove harmful particulates like mold, pet dander, airborne viruses, pollen, and odors. The AprilAire Pure Fit Promise ensures a perfect fit with Self-Seal Technology, reducing bypass and improving filter performance. The Interlock Rail System means the filter works without assembly or extra reinforcements.
AprilAire filters also protect your HVAC equipment from dirt and dust buildup, which can hinder performance. AprilAire offers a Clean-Coil Commitment: for 10 years, AprilAire will pay $100 toward the cost of professional cleaning of your indoor air conditioner coil if it requires it due to the effectiveness of the air cleaner. For details, visit aprilaire.com/cleancoil or call 800.334.6011.
Please read this manual to familiarize yourself with the product features and routine maintenance. Register your product at aprilaire.com/warranty.
PERFORMANCE
An AprilAire Whole-House Air Cleaner is installed as part of your home's heating, ventilation, and air conditioning (HVAC) system. As air circulates through your home, it passes through the air cleaner, where airborne contaminants are removed. These contaminants include natural sources like dust and pollen, and man-made sources like tobacco smoke or exhaust. Removing these particles not only keeps HVAC equipment clean but also ensures Healthy Air throughout your home.
For continuous air cleaning, set your thermostat to "Fan On". If continuous cleaning is not required, set the thermostat to "Fan Auto".
MAINTENANCE
Regular filter replacement is crucial for maintaining a clean HVAC system and preventing damage. For effective whole-home air purification, use genuine AprilAire Replacement Filters.
AprilAire recommends replacing your filter every 6-12 months. Your HVAC contractor may suggest more frequent replacement based on your home's usage, the number of occupants, pets, smokers, and local pollution levels.
CHANGING THE FILTERS
Replace the filter with genuine AprilAire Filters designed for your unit. Ensure the filter is installed in the correct orientation: the outlet side is indicated by the expanded metal.
The model number for your replacement filter is located on the label inside the air cleaner door (see FIGURE 8).
IMPORTANT: Turn the thermostat mode to off and the fan to auto before removing the air cleaner door.
Shows the filter replacement label found on the inside of the air cleaner door.
REPLACEMENT FILTERS
AprilAire offers a range of filters designed for different needs:
Healthy Air 16: Removes up to 99%* of Allergy and Asthma Triggers
AIR CLEANER MODEL | 1110 | 1210 1620 | 1310 | 1410 1610 | 1510 | 1910 | 2210 | 2216 | 2310 | 2410 | 2416 | 2516 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
FILTER MODEL | n/a | 216 | n/a | 416 | 516 | n/a | 216 | 216 | n/a | 416 | 416 | 516 |
Healthy Air 13+: Removes Pet & Cooking Odors, VOCs & Particulate
AIR CLEANER MODEL | 1110 | 1210 1620 | 1310 | 1410 1610 | 1510 | 1910 | 2210 | 2216 | 2310 | 2410 | 2416 | 2516 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
FILTER MODEL | n/a | 213CBN | n/a | 413CBN | 513CBN | n/a | 213CBN | 213CBN | n/a | 413CBN | 413CBN | 513CBN |
Healthy Air 13: Removes Most Common Allergens
AIR CLEANER MODEL | 1110 | 1210 1620 | 1310 | 1410 1610 | 1510 | 1910 | 2210 | 2216 | 2310 | 2410 | 2416 | 2516 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
FILTER MODEL | 113 | 213 | 313 | 413 | 513 | 913 | 213 | 213 | 313 | 413 | 413 | 513 |
Healthy Air 11: Vacuum and Dust Less Often
AIR CLEANER MODEL | 1110 | 1210 1620 | 1310 | 1410 1610 | 1510 | 1910 | 2210 | 2216 | 2310 | 2410 | 2416 | 2516 |
---|---|---|---|---|---|---|---|---|---|---|---|---|
FILTER MODEL | 110 | 210 | 310 | 410 | 510 | 910 | 210 | 210 | 310 | 410 | 410 | 510 |
*Contaminants removed based on air passing through the filtering system.
REMOVAL EFFICIENCY (BASED ON PARTICLE SIZE)
0.3-1.0 Microns | 1.0-3.0 Microns | 3.0-10.0 Microns | |
---|---|---|---|
MERV 16 | 95% | 98% | 99% |
MERV 13 | 63% | 88% | 93% |
MERV 11 | 37% | 67% | 92% |
Test Method: MERV 10-16 - ASHRAE 52.2.2017, EAC - AHRI 680-2017
APRILAIRE 10-YEAR CLEAN COIL COMMITMENT
Should your indoor air conditioner coil require professional cleaning within 10 years, AprilAire will pay $100 toward the cost when cleaned by a licensed contractor. This guarantee is offered due to the effectiveness of AprilAire Air Cleaners in removing harmful particles and contaminants.
For full details, visit aprilaire.com/cleancoil or call 800.334.6011.
LIMITED WARRANTY
Terms of Coverage
Your AprilAire® Air Cleaner is warranted to be free from defects in materials or workmanship for five (5) years from the date of purchase.
What Is Covered
AprilAire will, at its discretion, supply a replacement for any defective component or product without charge. Defective parts will be replaced with genuine AprilAire parts. Defective products will be replaced with new AprilAire products of similar features if the original is discontinued.
Not Covered by the Limited Warranty
- Consumable or maintenance products (e.g., Air Filters, Humidifier Water Panels).
- Labor charges, shipping costs, removal fees, service fees, or reinstallation costs.
- Damage caused by misuse, abuse, or improper installation not following instructions.
- Damage to HVAC equipment due to improper installation or misapplication.
- Modifications, changes, or alterations to the AprilAire product.
- Extended warranties or satisfaction guarantees from third parties.
- Cosmetic damage or normal wear and tear that does not impede mechanical function.
- Damage caused by acts of nature (fire, collision, flood, wind, power surge, lightning, mold).
- Damage during transit.
- Damage during installation due to failure to follow local, state, or federal laws, codes, or ordinances.
- Defects in materials furnished by the installer.
Limit of Liability
Implied warranties of merchantability or fitness for a particular purpose are limited to the duration of this express warranty. AprilAire is not liable for incidental or consequential damages, except for personal injuries, resulting from any breach of implied or express warranties.
This Limited Warranty is void if defects result from failure to install the product according to AprilAire installation instructions. Some states may have different limitations on implied warranties or consequential damages.
Register Your AprilAire® Product
Register your product at aprilaire.com/warranty to receive important updates and notifications, and to streamline the claims process.
Make a Warranty Claim
For warranty questions or to initiate a claim, contact AprilAire Customer Service at 1.800.334.6011 (Monday-Friday, 7:00 a.m. - 5:00 p.m. Central Time).
AprilAire may require product return, contractor service, product testing, or submission of pictures as a condition for reviewing a claim or providing a replacement.