TRANE SVN257B Restrictor Panggantos Kompresor
Informasi produk
Spesifikasi
- Model: PART-SVN257B-EN
- Tipe Kompresor: Kompresor Ganti
- Refrigerant: R-410A
- Tekanan Operasi: Tekanan Tinggi
Pandhuan Instalasi
Watesan
Kanggo Panggantos Compressorz
WARNING KESELAMATAN
Mung personel qualified kudu nginstal lan layanan peralatan. Instalasi, miwiti, lan servis peralatan pemanasan, ventilasi, lan AC bisa mbebayani lan mbutuhake kawruh lan latihan khusus. Peralatan sing ora dipasang, diatur utawa diowahi dening wong sing ora nduweni kualifikasi bisa nyebabake pati utawa ciloko serius. Nalika nggarap peralatan, mirsani kabeh pancegahan ing literatur lan ing tags, stiker, lan label sing ditempelake ing peralatan.
Pambuka
Waca manual iki sak tenane sadurunge ngoperasikake utawa nglayani unit iki.
Bebaya, Ati-ati, lan Kabar
Rekomendasi safety katon ing manual iki yen dibutuhake. Keamanan pribadhi lan operasi sing tepat saka mesin iki gumantung marang patuhi pancegahan kasebut.
Telung jinis advisories ditetepake kaya ing ngisor iki:
WARNING
Nuduhake kahanan sing bisa mbebayani sing, yen ora dihindari, bisa nyebabake pati utawa ciloko serius.
AWAS
Nuduhake kahanan sing bisa mbebayani sing, yen ora dihindari, bisa nyebabake ciloko cilik utawa moderat. Bisa uga digunakake kanggo menehi tandha marang praktik sing ora aman.
WARTA
nuduhake kahanan sing bisa nyebabake kacilakan peralatan utawa mung karusakan properti.
Keprigelan Lingkungan sing Penting
Panaliten ilmiah wis nuduhake manawa bahan kimia buatan manungsa tartamtu bisa mengaruhi lapisan ozon stratosfer sing alami nalika diluncurake menyang atmosfer. Utamane, sawetara bahan kimia sing diidentifikasi sing bisa mengaruhi lapisan ozon yaiku refrigeran sing ngemot Klorin, Fluorin lan Karbon (CFC) lan sing ngemot Hidrogen, Klorin, Fluorin lan Karbon (HCFC). Ora kabeh refrigeran sing ngemot senyawa kasebut duweni potensi dampak sing padha kanggo lingkungan. Trane nyengkuyung tanggung jawab nangani kabeh refrigeran.
Praktek Refrigerant Tanggung Jawab Penting
Trane percaya yen praktik refrigeran sing tanggung jawab penting kanggo lingkungan, pelanggan, lan industri AC. Kabeh teknisi sing nangani refrigeran kudu disertifikasi miturut aturan lokal. Kanggo AS, Undhang-undhang Udara Bersih Federal (Bagian 608) nemtokake syarat kanggo nangani, mbalekake, mbalekake lan daur ulang refrigeran tartamtu lan peralatan sing digunakake ing prosedur layanan kasebut. Kajaba iku, sawetara negara utawa kotamadya bisa uga duwe syarat tambahan sing uga kudu dipatuhi kanggo manajemen refrigeran sing tanggung jawab. Ngerti hukum sing ditrapake lan tindakake.
WARNING
Wiring Lapangan lan Grounding Dibutuhake!
Gagal ngetutake kode bisa nyebabake pati utawa ciloko serius.
Kabeh kabel lapangan kudu ditindakake dening personel sing mumpuni. Kabel lapangan sing ora dipasang lan digandhengake kanthi bener nyebabake bebaya KEBAKARAN lan ELECTROCUTION. Kanggo ngindhari bebaya kasebut, sampeyan kudu ngetutake syarat kanggo instalasi kabel lapangan lan grounding kaya sing diterangake ing NEC lan kode listrik lokal / negara / nasional.
WARNING
Alat Pelindung Diri (APD) Dibutuhake!
Gagal nganggo APD sing tepat kanggo proyek sing ditindakake bisa nyebabake pati utawa ciloko serius. Teknisi, kanggo nglindhungi awake dhewe saka bebaya listrik, mekanik, lan kimia sing potensial, kudu ngetutake pancegahan ing manual iki lan ing tags, stiker, lan label, uga instruksi ing ngisor iki:
- Sadurunge nginstal / nglayani unit iki, teknisi kudu nganggo kabeh APD sing dibutuhake kanggo karya sing ditindakake (Ex.amples; sarung tangan/lengan tahan potong, sarung tangan butil, kacamata pengaman, topi keras/topi benjolan, perlindungan tiba, PPE listrik lan busana lampu kilat). Tansah waca Lembar Data Keamanan (SDS) lan pedoman OSHA sing cocog kanggo APD sing tepat.
- Nalika nggarap utawa ngubengi bahan kimia sing mbebayani, TANPA deleng pedoman SDS lan OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) sing cocog kanggo informasi babagan tingkat pajanan pribadi sing diidinake, perlindungan pernapasan lan instruksi penanganan sing tepat.
- Yen ana risiko kontak listrik, busur, utawa lampu kilat, teknisi kudu nganggo kabeh APD sing cocog karo OSHA, NFPA 70E, utawa syarat khusus negara liyane kanggo proteksi lampu kilat busur, sadurunge nglayani unit kasebut. ORA NGLAKOKE SWITCHING, DISCONNECTING, UTAWA VOLTAGE TESTING TANPA ELECTRICAL PPE lan ARC FLASH Clothing. PASTIKAN METER ELEKTRIK lan PERALATAN DIBERI RATING SESUAI KANGGO VOLTAGE.
WARNING
Tindakake Kebijakan EHS!
Gagal ngetutake instruksi ing ngisor iki bisa nyebabake pati utawa ciloko serius.
- Kabeh personel Trane kudu ngetutake kabijakan Lingkungan, Kesehatan, lan Keamanan (EHS) perusahaan nalika nindakake pakaryan kayata kerja panas, listrik, perlindungan tiba, lockout /tagmetu, penanganan refrigerant, etc. Where peraturan lokal luwih kenceng saka kawicaksanan iki, peraturan sing supersede kawicaksanan iki.
- Personel non-Trane kudu tansah ngetutake peraturan lokal.
WARNING
Refrigerant ing Tekanan Dhuwur!
Gagal ngetutake instruksi ing ngisor iki bisa nyebabake bledosan sing bisa nyebabake pati utawa ciloko serius utawa karusakan peralatan.
Sistem ngemot refrigerant ing tekanan dhuwur. Mbalekake refrigerant kanggo nyuda tekanan sadurunge mbukak sistem. Waca papan jeneng unit kanggo jinis refrigeran. Aja nggunakake refrigeran sing ora disetujoni, substitusi refrigeran, utawa aditif refrigeran.
WARNING
R-410A Refrigerant ing Higher
Tekanan saka R-22!
Gagal nggunakake peralatan utawa komponen sing tepat kaya sing diterangake ing ngisor iki, bisa nyebabake peralatan gagal lan bisa uga njeblug, sing bisa nyebabake pati, ciloko serius, utawa karusakan peralatan.
Unit sing diterangake ing manual iki nggunakake refrigeran R-410A sing beroperasi ing tekanan sing luwih dhuwur tinimbang R-22. Gunakake peralatan utawa komponen layanan sing dirating R-410A kanthi unit kasebut. Kanggo masalah penanganan khusus karo R-410A, hubungi wakil Trane lokal.
WARNING
Refrigerant A454L R-2B!
Gagal nggunakake peralatan utawa komponen sing tepat kaya sing diterangake ing ngisor iki bisa nyebabake kegagalan peralatan, lan bisa uga kobong, sing bisa nyebabake pati, ciloko serius, utawa karusakan peralatan.
Peralatan sing diterangake ing manual iki nggunakake refrigeran R-454B sing gampang kobong (A2L). Gunakake peralatan lan komponen layanan sing dirating R-454B. Kanggo masalah penanganan khusus karo R-454B, hubungi wakil lokal.
WARNING
Bebaya bledosan lan Gas Mateni!
Gagal ngetutake kabeh praktik penanganan refrigeran sing aman bisa nyebabake pati utawa ciloko serius. Aja solder, braze utawa las ing garis refrigeran utawa komponen unit apa wae sing ana ing ndhuwur tekanan atmosfer utawa ing ngendi refrigeran bisa ana. Tansah mbusak refrigerant kanthi nuruti pedoman sing ditetepake dening EPA Federal Clean Air Act utawa kode negara utawa lokal liyane sing cocog. Sawise mbusak refrigerant, gunakake nitrogen garing kanggo nggawa sistem bali menyang tekanan atmosfer sadurunge mbukak sistem kanggo ndandani. Campuran refrigeran lan hawa ing tekanan bisa dadi kobong yen ana sumber kontak sing nyebabake bledosan. Panas banget saka soldering, brazing utawa welding karo uap refrigerant saiki bisa mbentuk gas banget beracun lan asam arang banget korosif.
WARNING
Bahaya bledosan!
Gagal ngetutake prosedur tes bocor sing aman ing ngisor iki bisa nyebabake pati utawa ciloko serius utawa peralatan utawa karusakan mung properti.
Aja nggunakake geni sing mbukak kanggo ndeteksi bocor gas. Gunakake solusi tes bocor kanggo tes bocor.
WARNING
Prosedur Layanan Mbebayani!
Gagal ngetutake kabeh pancegahan ing manual iki lan ing tags, stiker, lan label bisa nyebabake pati utawa ciloko serius.
Teknisi, kanggo nglindhungi awake dhewe saka bebaya listrik, mekanik, lan kimia sing potensial, kudu ngetutake pancegahan ing manual iki lan ing tags, stiker, lan label, uga pandhuan ing ngisor iki: Yen ora ditemtokake, pedhot kabeh daya listrik kalebu pedhot remot lan copot kabeh piranti nyimpen energi kayata kapasitor sadurunge servis. Tindakake lockout sing bener/tagmetu tata cara kanggo mesthekake daya ora bisa ora sengaja energized. Yen perlu kanggo nggarap komponen listrik urip, duwe teknisi listrik sing dilisensi utawa individu liyane sing wis dilatih nangani komponen listrik langsung nindakake tugas kasebut.
Hak cipta
Dokumen iki lan informasi sing ana ing njerone minangka properti Trane, lan ora bisa digunakake utawa direproduksi kabeh utawa sebagean tanpa idin tinulis. Trane nduweni hak kanggo mbenakake publikasi iki sawayah-wayah, lan ngowahi isine tanpa kudu menehi kabar marang sapa wae babagan revisi utawa owah-owahan kasebut.
merek dagang
Kabeh merek dagang sing dirujuk ing dokumen iki minangka merek dagang sing nduweni.
Riwayat Revisi
- Unit karo microchannel (MCHE) tabel condenser dipérang minangka saben produk ing Instalasi bab.
- Nganyari identifikasi pembatasan bagean Layanan, IPAK 2, IPAK 1, Voyager 3, RAU Pisah gedhe, lan IPAK 3 tabel ing bab Instalasi.
Instalasi
Tabel 2, p. 8, Tabel 3, p. 9, Tabel 4, p. 13, Tabel 5, p. 13, Tabel 6, p. 14, lan Tabel 7, p. 17 menehi informasi kanggo lokasi sing bener lan pilihan saka watesan.
Kompresor layanan dikirim nganggo pembatas sing dibutuhake sing dikemas ing tas individu lan dicap karo nomer bagean mnemonik pembatasan ing njaba tas. Label liyane uga kalebu ing tas. Nomer X1731****** ngenali pembatasan. Watesan kasebut kanthi fisik ditandhani ing pasuryan kanthi ekstensi nomer bagean lan ukuran ID.
Cathetan: 51-25 kabamped ing pasuryan saka restrictor. Drawing X17311040510, 51 minangka extension. 25 mm minangka ID.
Nalika njabut restrictor, restrictor ing kompresor bisa uga ora cocog nomer kiriman restrictor karo kompresor layanan.
Nomer bagean pembatasan gumantung saka jinis produk, lokasi pabrik, lan yen asline dikemas ing tas. Waca Tabel 1, p. 6 kanggo padha restrictor pasuryan Stampnomer ing lan nomer bagean mnemonik referensi silang.
Tabel 1. Identifikasi pembatasan bagean layanan
MNE | Label | Watesan | |
Ukuran ID (mm) | Ngadhepi Stamping Nomer | ||
RSR00235 | X17311040510 | 25 | 51-25 |
RSR00348 | X17311040570 | 22.5 | 57-22.5 |
RSR00237 | X17311040530 | 23 | 53-23 |
RSR00238 | X17311040540 | 27 | 54-27 |
RSR00240 | X17311040560 | 26 | 56-26 |
RSR00244 | X17311028540 | 26 | 54-26 |
RSR00241 | X17311028510 | 31 | 51-31 |
RSR00242 | X17311028520 | 33 | 52-33 |
RSR00366 | X17311028560 | 32 | 56-32 |
RSR00355 | X17311040600 | 15 | 60-15 |
RSR00354 | X17311040590 | 19 | 59-19 |
RSR00353 | X17311040580 | 22 | 58-22 |
RSR00380 | X17311040680 | 20 | 68-20 |
Pasang restrictor ing inlet nyedhot saka kompresor panggantos.
- Lebokake tabung menyang sambungan nyedhot lan nggunakake tabung kanggo njagong restrictor kuwat menyang sambungan nyedhot.
- Braze tabung nyedhot menyang kompresor.
- Sawise ngrampungake brazing tabung nyedhot, pasang label sing ana ing njero tas menyang kompresor cedhak sambungan nyedhot. Iki bakal ngaktifake identifikasi pembatas ing mangsa ngarep.
Pendekatan nyedhot yaiku arah saka ngendi pipa nyedhot unit mlebu tandem kompresor utawa set trio nalika viewed saka ngarep, sisih kothak terminal. Iki kudu ditemtokake nggunakake Tabel 2, p. 8, Tabel 3, p. 9, Tabel 4, p. 13, Tabel 5, p. 13, Tabel 6, p. 14, lan Tabel 7, p. 17 uga digunakake kanggo nemtokake kompresor sing bener kanggo nampa pembatasan.
Saliyane pendekatan nyedhot, verifikasi nomer model kompresor ing unit serviced cocog kompresor CP1, CP2, lan CP3 ditetepake ing sirkuit pamilike nalika referensi Tabel 2, p. 8, Tabel 3, p. 9, Tabel 4, p. 13, Tabel 5, p. 13, Tabel 6, p. 14, lan Tabel 7, p. 17. Yen nomer model kompresor ora cocog, nelpon Trane Tech Support kanggo pitulungan.
Tabel 2. IPAK 2 - ukuran lan lokasi pembatasan nyedhot
Digit 4 - Urutan pangembangan | Angka 5,6,7 –
Kapasitas Cooling nominal |
Digit 28 - Efisiensi, Kapasitas, lan Opsi Panci Saluran | Sirkuit # | Posisi Kompresor | Suct. Appr. | Ukuran Watesan (ID mm) lan Lokasi | Nomer Bagean Trane | Nomer Bagian Mnemonic | ||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
E |
090 |
A/C |
1 | CSHN250 | CSHN250 | — | Ngiwa | Ora Req. | — | — | ||
2 | CSHN250 | CSHN250 | — | bener | Ora Req. | — | — | |||||
W/Z |
1 | VZH170 | CSHL169 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL169 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
105 |
A/C |
1 | CSHN184 | CSHN184 | CSHN184 | Ngiwa | — | — | 31 | X17311028510 | RSR00241 | |
2 | CSHN184 | CSHN184 | CSHN184 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHL227 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL169 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
120 |
A/C |
1 | CSHN184 | CSHN184 | CSHN250 | Ngiwa | 33 | 33 | — | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|
2 | CSHN184 | CSHN184 | CSHN250 | bener | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHL285 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL227 | bener | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
130 |
A/C |
1 | CSHN240 | CSHN240 | CSHN240 | Ngiwa | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHN240 | CSHN240 | CSHN240 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHL346 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHL227 | CSHL227 | CSHL227 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
150 |
A/C |
1 | CSHN250 | CSHN250 | CSHN250 | Ngiwa | 33 | — | — | X17311028520 | RSR00242 | |
2 | CSHN250 | CSHN250 | CSHN250 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHL346 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHL227 | CSHL169 | CSHL346 | bener | 31 | 26 | — | X17311028510 /
X17311028540 |
RSR00241 /
RSR00244 |
|||
T |
090 |
A/C |
1 | CSHP237 | CSHP237 | — | Ngiwa | Ora Req. | — | — | ||
2 | CSHP237 | CSHP237 | — | bener | Ora Req. | — | — | |||||
W/Z |
1 | VZH170 | CSHP178 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP178 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
105 |
A/C |
1 | CSHP178 | CSHP178 | CSHP178 | Ngiwa | — | — | 31 | X17311028510 | RSR00241 | |
2 | CSHP178 | CSHP178 | CSHP178 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHP237 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP178 | bener | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
Digit 4 - Urutan pangembangan |
Angka 5,6,7 –
Kapasitas Cooling nominal |
Digit 28 - Efisiensi, Kapasitas, lan Opsi Panci Saluran |
Sirkuit # |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
T |
120 |
A/C |
1 | CSHP178 | CSHP178 | CSHP237 | Ngiwa | 33 | 33 | — | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
2 | CSHP178 | CSHP178 | CSHP237 | bener | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHP297 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP237 | bener | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
130 |
A/C |
1 | CSHP227 | CSHP227 | CSHP227 | Ngiwa | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHP227 | CSHP227 | CSHP227 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHP346 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHP227 | CSHP227 | CSHP227 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
150 |
A/C |
1 | CSHP237 | CSHP237 | CSHP237 | Ngiwa | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHP237 | CSHP237 | CSHP237 | bener | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHP346 | — | Ngiwa | Ora Req. | — | — | ||||
2 | CSHP237 | CSHP178 | CSHP346 | bener | 31 | 26 | — | X17311028510 /
X17311028540 |
RSR00241 /
RSR00244 |
Cathetan: IPAK 2 90 nganti 150 ton MCHE: ora ana owah-owahan ing kompresor digit 10 urutan desain P.
Tabel 3. IPAK 1 - ukuran lan lokasi pembatasan nyedhot
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Digit 26 - Pilihan Efisiensi |
Sirkuit # |
Posisi Kompresor |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
M |
*20 |
0 | 1 | ZP154 | ZPS104 | — | Ora Req. | — | — | ||
H | 1 | ZP154 | ZPS104 | — | Ora Req. | — | — | ||||
V | 1 | VZH088 | CSHD110 | — | Ora Req. | — | — | ||||
*25 |
0 | 1 | CSHD075 | CSHD110 | CSHD110 | 15 | — | — | X17311040600 | RSR00355 | |
H | 1 | ZP182 | ZPS122 | — | Ora Req. | — | — | ||||
V | 1 | VZH088 | CSHD125 | — | Ora Req. | — | — | ||||
*30 |
0 | 1 | CSHD075 | CSHD120 | CSHD120 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | CSHD075 | CSHD120 | CSHD120 | 19 | — | — | X17311040590 | RSR00354 | ||
V | 1 | VZH117 | CSHD161 | — | Ora Req. | — | — | ||||
*40 |
0 |
1 | CSHD092 | CSHD110 | — | 25 | — | — | X17311040510 | RSR00235 | |
2 | CSHD110 | CSHD110 | — | Ora Req. | — | — | |||||
H |
1 | CSHD092 | CSHD092 | — | Ora Req. | — | — | ||||
2 | CSHD092 | CSHD110 | — | 25 | — | — | X17311040510 | RSR00235 | |||
V |
1 | VZH117 | — | — | Ora Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | Ora Req. | — | — |
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Digit 26 - Pilihan Efisiensi |
Sirkuit # |
Posisi Kompresor |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
M |
*50 |
0 |
1 | CSHD125 | CSHD125 | — | Ora Req. | — | — | ||
2 | CSHD125 | CSHD125 | — | Ora Req. | — | — | |||||
H |
1 | CSHD125 | CSHD142 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHD125 | CSHD142 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | Ora Req. | — | — | |||||
*55 |
0 |
1 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |
2 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |||
H |
1 | CSHD142 | CSHD142 | — | Ora Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |||
*60 |
0 |
1 | CSHD161 | CSHD161 | — | Ora Req. | — | — | |||
2 | CSHD161 | CSHD161 | — | Ora Req. | — | — | |||||
H |
1 | CSHD161 | CSHD161 | — | Ora Req. | — | — | ||||
2 | CSHD161 | CSHD183 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHD161 | CSHD183 | — | 26 | — | — | X17311040560 | RSR00240 | |||
*70 |
0 |
1 | CSHD183 | CSHD183 | — | Ora Req. | — | — | |||
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHD183 | CSHD183 | — | Ora Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*75 |
0 |
1 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | ||
2 | CSHN250 | CSHN250 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | CSHN184 | — | Ora Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | Ora Req. | — | — | |||||
*90 |
0/H |
1 | CSHN250 | CSHN250 | — | Ora Req. | — | — | |||
2 | CSHN250 | CSHN250 | — | Ora Req. | — | — | |||||
*11 |
0/H |
1 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*12 |
0/H |
1 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN315 | CSHN315 | — | Ora Req. | — | — | |||||
*13 |
0/H |
1 | CSHN315 | CSHN315 | — | Ora Req. | — | — | |||
2 | CSHN315 | CSHN374 | — | 31 | — | — | X17311028510 | RSR00241 |
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Digit 26 - Pilihan Efisiensi |
Sirkuit # |
Posisi Kompresor |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
P |
*20 |
0 | 1 | YA154 | YAS104 | — | Ora Req. | — | — | ||
H | 1 | YA154 | YAS104 | — | Ora Req. | — | — | ||||
V | 1 | VZH088 | CSHE113 | — | Ora Req. | — | — | ||||
*25 |
0 | 1 | CSHE071 | CSHE113 | CSHE113 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | YA182 | YAS122 | — | Ora Req. | — | — | ||||
V | 1 | VZH088 | CSHE132 | — | Ora Req. | — | — | ||||
*30 |
0 | 1 | CSHE071 | CSHE127 | CSHE127 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | CSHE071 | CSHE117 | CSHE117 | 19 | — | — | X17311040590 | RSR00354 | ||
V | 1 | VZH117 | CSHE152 | — | Ora Req. | — | — | ||||
*40 |
0 |
1 | CSHE104 | CSHE113 | — | Ora Req. | — | — | |||
2 | CSHE104 | CSHE113 | — | Ora Req. | — | — | |||||
H |
1 | CSHE088 | CSHE104 | — | 25 | — | — | X17311040510 | RSR00235 | ||
2 | CSHE088 | CSHE104 | — | 25 | — | — | X17311040510 | RSR00235 | |||
V |
1 | VZH117 | — | — | Ora Req. | — | — | ||||
2 | CSHE113 | CSHE113 | — | Ora Req. | — | — | |||||
*50 |
0 |
1 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | |||
H |
1 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE132 | CSHE132 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | Ora Req. | — | — | |||||
*55 |
0 |
1 | CSHE132 | CSHE152 | — | 27 | — | — | X17311040540 | RSR00238 | |
2 | CSHE152 | CSHE152 | — | Ora Req. | — | — | |||||
H |
1 | CSHE132 | CSHE132 | — | Ora Req. | — | — | ||||
2 | CSHE132 | CSHE152 | — | 27 | — | — | X17311040540 | RSR00238 | |||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHE152 | CSHE152 | — | Ora Req. | — | — | |||||
*60 |
0 |
1 | CSHE152 | CSHE152 | — | Ora Req. | — | — | |||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | |||
H |
1 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 |
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Digit 26 - Pilihan Efisiensi |
Sirkuit # |
Posisi Kompresor |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
P |
*70 |
0 |
1 | CSHE177 | CSHE177 | — | Ora Req. | — | — | ||
2 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHE177 | CSHE177 | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | — | — | Ora Req. | — | — | ||||
2 | CSHP227 | CSHP227 | — | Ora Req. | — | — | |||||
*75 |
0 |
1 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | ||
2 | CSHP237 | CSHP237 | — | Ora Req. | — | — | |||||
V |
1 | VZH170 | CSHP178 | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | Ora Req. | — | — | |||||
90 |
0/H |
1 | CSHP237 | CSHP237 | — | Ora Req. | — | — | |||
2 | CSHP237 | CSHP237 | — | Ora Req. | — | — | |||||
*11 |
0/H |
1 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*12 |
0/H |
1 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP297 | CSHP297 | — | Ora Req. | — | — | |||||
*13 |
0/H |
1 | CSHP297 | CSHP346 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP297 | CSHP346 | — | 31 | — | — | X17311028510 | RSR00241 |
Cathetan
- IPAK RT G unit efisiensi dhuwur-dituduhake dening G ing digit 26 nomer model.
- IPAK RT ukuran 24, 29, 36, 48, 59, 73, 80, 89 minangka model kondensor pendingin evaporatif.
- IPAK RT 20 to 75 ton MCHE digit 10 design Sequence E.
- IPAK RT 90 nganti 130 ton MCHE: ora ana owah-owahan ing kompresor digit 10 urutan desain D.
- Unit kacepetan variabel IPAK RT V eFlex™ – dituduhake V ing digit 26 nomer model.
Tabel 4. Voyager 3 - ukuran restrictor nyedhot lan lokasi
Digit 7- Urutan pangembangan utama |
Digit 29 - Efisiensi |
Digit 4,5,6 - Kapasitas Cooling Nominal |
Posisi Kompresor |
Suct. Appr. |
Ukuran Restrictor (ID mm) |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
||||||
C |
0 / J |
330 | CSHD075 | CSHD110 | CSHD110 | Ngiwa | 15 | — | — | X17311040600 | RSR00355 |
360 | CSHD075 | CSHD120 | CSHD120 | Ngiwa | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHD075 | CSHD136 | CSHD136 | Ngiwa | ora ana | — | — | ||||
480 | CSHD092 | CSHD155 | CSHD155 | Ngiwa | ora ana | — | — | ||||
600 | CSHD120 | CSHD183 | CSHD183 | Ngiwa | 22 | — | — | X17311040580 | RSR00353 | ||
K / L |
330 | CSHD075 | CSHD110 | CSHD110 | Ngiwa | 15 | — | — | X17311040600 | RSR00355 | |
360 | CSHD075 | CSHD120 | CSHD120 | Ngiwa | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHD089 | CSHD136 | CSHD136 | Ngiwa | ora ana | — | — | ||||
480 | CSHD092 | CSHD155 | CSHD155 | Ngiwa | ora ana | — | — | ||||
600 | CSHD120 | CSHD183 | CSHD183 | Ngiwa | 22 | — | — | X17311040580 | RSR00353 | ||
D |
0 / J / K / L |
330 | CSHE071 | CSHE113 | CSHE113 | Ngiwa | 15 | — | — | X17311040600 | RSR00355 |
360 | CSHE071 | CSHE127 | CSHE127 | Ngiwa | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHE088 | CSHE132 | CSHE132 | Ngiwa | ora ana | — | — | ||||
480 | CSHE097 | CSHE152 | CSHE152 | Ngiwa | 20 | — | — | X17311040680 | RSR00380 | ||
600 | CSHE117 | CSHE177 | CSHE177 | Ngiwa | 22 | — | — | X17311040580 | RSR00353 |
Cathetan: Voyager 3 MCHE: ora ana owah-owahan ing kompresor digit 10 urutan desain F.
Tabel 5. RA - ukuran restrictor nyedhot lan lokasi
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
|||||
J |
C20 | CSHD120 | CSHD120 | — | bener | Ora Req. | — | — | ||
C25 | CSHD125 | CSHD161 | — | bener | 25 | — | — | X17311040510 | RSR00235 | |
C30 | CSHD183 | CSHD183 | — | bener | Ora Req. | — | — | |||
C40 | CSHD120 | CSHD120 | — | bener | Ora Req. | — | — | |||
C50 | CSHD142 | CSHD161 | — | bener | 27 | — | — | X17311040540 | RSR00238 | |
C60 | CSHD175 | CSHD175 | — | bener | Ora Req. | — | — | |||
C80 | CSHN176 | CSHN176 | CSHN176 | Ngiwa | — | — | 31 | X17311028510 | RSR00241 | |
D10 | CSHN184 | CSHN184 | CSHN250 | Ngiwa | 33 | 33 | — | X17311028520 | RSR00242 | |
D12 | CSHN250 | CSHN250 | CSHN250 | Ngiwa | — | — | 33 | X17311028520 | RSR00242 | |
K |
C20 | YA154 | YAS104 | — | bener | Ora Req. | — | — | ||
C25 | YA182 | YAS122 | — | bener | Ora Req. | — | — | |||
C30 | CSHE088 | CSHE132 | CSHE132 | bener | Ora Req. | — | — | |||
C40 | CSHE117 | CSHE132 | — | bener | 26 | — | — | X17311040560 | RSR00240 | |
C50 | CSHE132 | CSHE145 | — | bener | 27 | — | — | X17311040540 | RSR00238 |
Digit 4 - Urutan pangembangan |
Digit 5,6,7 - Kapasitas Cooling Nominal |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
|||||
K |
C60 | CSHE177 | CSHE177 | — | bener | Ora Req. | — | — | ||
C80 | CSHP178 | CSHP178 | CSHP178 | Ngiwa | — | — | 31 | X17311028510 | RSR00241 | |
D10 | CSHP178 | CSHP178 | CSHP237 | Ngiwa | 33 | 33 | — | X17311028520 | RSR00242 | |
D12 | CSHP237 | CSHP237 | CSHP237 | Ngiwa | — | — | 33 | X17311028520 | RSR00242 |
Cathetan
- Sistem pamisah RAUJ 20 nganti 60 ton MCHE: ora ana owah-owahan ing kompresor digit 10 urutan desain C.
- Sistem pamisah RAUJ 20 nganti 120 ton MCHE: ora ana owah-owahan ing kompresor digit 10 urutan desain B.
Tabel 6. IPAK 3 - ukuran lan lokasi pembatasan nyedhot
Digit 12 - Urutan pangembangan |
Digit 3,4,5 - Kapasitas Cooling Nominal |
Digit 9 - Kinerja Sistem Pendingin |
Sirkuit # |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane |
Nomer Bagian Mnemonic |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
A |
020 |
1 | 1 | CSHW058 | CSHW089 | CSHW089 | — | Ora Req. | — | — | ||
2 | 1 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
3 | 1 | VZH088 | CSHD110 | — | — | Ora Req. | — | — | ||||
025 |
1 | 1 | CSHD075 | CSHD110 | CSHD110 | — | 15 | — | — | X17311040600 | RSR00355 | |
2 | 1 | CSHD142 | CSHD161 | — | — | 27 | — | — | X17311040540 | RSR00238 | ||
3 | 1 | VZH088 | CSHD125 | — | — | Ora Req. | — | — | ||||
030 |
1 | 1 | CSHD075 | CSHD120 | CSHD120 | — | 19 | — | — | X17311040590 | RSR00354 | |
2 | 1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
3 | 1 | VZH117 | CSHD161 | — | — | Ora Req. | — | — | ||||
040 |
1 |
1 | CSHD110 | CSHD110 | — | — | Ora Req. | — | — | |||
2 | CSHD110 | CSHD110 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHD110 | CSHD110 | — | — | Ora Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH117 | — | — | — | Ora Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | — | Ora Req. | — | — | |||||
050 |
1 |
1 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHD125 | CSHD125 | — | — | Ora Req. | — | — | ||||
2 | CSHD125 | CSHD125 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | — | Ora Req. | — | — |
A |
055 |
1 |
1 | CSHD142 | CSHD142 | — | — | Ora Req. | — | — | ||
2 | CSHD142 | CSHD142 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHD125 | CSHD142 | — | — | 26 | — | X17311040560 | RSR00240 | |||
2 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | — | Ora Req. | — | — | |||||
060 |
1 |
1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHD161 | CSHD161 | — | — | Ora Req. | — | — | ||||
2 | CSHD161 | CSHD161 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||||
070 |
1 |
1 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||
2 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHD161 | CSHD183 | — | — | 26 | — | X17311040560 | RSR00240 | ||||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||||
075 |
1 |
1 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||
2 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | CSHN184 | — | — | Ora Req. | — | — | ||||
2 | CSHD161 | CSHD161 | — | — | Ora Req. | — | — | |||||
B |
020 | 3 | 1 | VZH088 | CSHE113 | — | — | Ora Req. | — | — | ||
025 |
2 | 1 | CSHE071 | CSHE113 | CSHE113 | — | 19 | — | — | X17311040590 | RSR00354 | |
3 | 1 | VZH088 | CSHE132 | — | — | Ora Req. | — | — | ||||
030 |
1 | 1 | CSHE071 | CSHE117 | CSHE117 | — | 19 | — | — | X17311040590 | RSR00354 | |
2 | 1 | CSHE071 | CSHE132 | CSHE132 | — | 19 | — | — | X17311040590 | RSR00354 | ||
3 | 1 | VZH117 | CSHE152 | — | — | Ora Req. | — | — | ||||
040 |
1 |
1 | CSHE104 | CSHE113 | — | — | Ora Req. | — | — | |||
2 | CSHE104 | CSHE113 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHE104 | CSHE113 | — | — | Ora Req. | — | — | ||||
2 | CSHE104 | CSHE113 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH117 | — | — | — | Ora Req. | — | — | ||||
2 | CSHE113 | CSHE113 | — | — | Ora Req. | — | — |
B |
050 |
1 |
1 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 |
2 | CSHE132 | CSHE132 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Ora Req. | — | — | |||||
055 |
1 |
1 | CSHE132 | CSHE145 | — | — | Ora Req. | — | — | |||
2 | CSHE132 | CSHE145 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHE132 | CSHE132 | — | — | Ora Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHE145 | CSHE145 | — | — | Ora Req. | — | — | |||||
060 |
1 |
1 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||||
070 |
1 |
1 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | CSHP178 | — | — | Ora Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Ora Req. | — | — | |||||
075 |
1 |
1 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||||
2 |
1 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — | |||||
3 |
1 | VZH170 | CSHP178 | — | — | Ora Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Ora Req. | — | — |
Tabel 7. Pamilihan lan lokasi pembatasan warisan
Lini produk |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane w/Tas lan Label |
Mnemonic # |
|||||||||
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Macon |
|||||||||
IPAK 2 | IPAK 1 | Voyager 3 Kab | Odyssey | RA | CSC | CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||
— | S*HL*40 | — | — | — | — | CSHD092 | CSHD110 | — | bener | — | 25 | — | X17311040510 | RSR00235 |
— | S*HL*40/48 G | — | — | — | — | CSHD110 | CSHD110 | — | bener | Ora Req. | — | — | — | |
— | S*HL*20/24 G | — | — | — | — | CSHD125 | CSHD125 | — | bener | Ora Req. | — | — | — | |
— | — | — | TTA240 F | — | — | CSHD120 | CSHD120 | — | ngiwa |
Ora Req. |
— | — | — | |
— | S*HL*20 | — | — | RAUJC20 RAUJC40 | — | CSHD120 | CSHD120 | — | bener | — | — | — | ||
— | — | — | — | — | S*RF*30 S*RF*35 | CSHD120 | CSHD120 | — | tengah | Ora Req. | — | — | — | |
— | S*HL*25 | — | — | — | — | CSHD125 | CSHD142 | — | bener | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL*50 | — | — | — | — | CSHD120 | CSHD136 | — | bener | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL25/29 G | — | — | RAUJC25 | — | CSHD125 | CSHD161 | — | bener | 25 | — | — | X17311040510 | RSR00235 |
— | S*HL*50/59 G | — | — | — | — | CSHD142 | CSHD142 | — | bener | Ora Req. | — | — | — | |
— | — | TC/TE/YC 330 | — | — | — | CSHD142 | CSHD161 | — | ngiwa | 27 | — | — | X17311040540 | RSR00238 |
— | S*HL*60 | — | — | RAUJC50 | — | CSHD142 | CSHD161 | — | bener | 27 | — | — | X17311040540 | RSR00238 |
— | — | TC/TE/YC 360 | — | — | — | CSHD161 | CSHD161 | — | ngiwa |
Ora Req. |
— | — | — | |
— | S*HL*30 S*HL*60/73 G | — | — | — | — | CSHD161 | CSHD161 | — | bener | — | — | — | ||
— | — | TC/TE/YC 420 | — | — | — | CSHD161 | CSHD183 | — | ngiwa | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL*30/36 G | — | — | — | — | CSHD161 | CSHD183 | — | bener | 26 | — | — | X17311040560 | RSR00240 |
— | — | TC/TE/YC 600 | — | — | — | CSHD155 | CSHD183 | — | ngiwa | 25 | — | — | X17311040510 | RSR00235 |
— | — | — | — | — | S*RF*40 | CSHD183 | CSHD120 | — | tengah | 22.5 | — | X17311040570 | RSR00348 | |
— | S*HL*70/80 | — | — | RAUJC30 | — | CSHD183 | CSHD183 | — | bener | Ora Req. | — | — | — | |
— | — | — | — | — | S*RF*50 | CSHD183 | CSHD183 | — | tengah | Ora Req. | — | — | — |
Lini produk |
Posisi Kompresor |
Suct. Appr. |
Ukuran Watesan (ID mm) lan Lokasi |
Nomer Bagean Trane w/Tas lan Label |
Mnemonic # |
|||||||||
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Macon |
|||||||||
IPAK 2 | IPAK 1 | Voyager 3 Kab | Odyssey | RA | CSC | CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||
— | — | — | — | — | S*RF*60 | CSHD183 | CSHD183 | — | tengah | Ora Req. | — | — | — | |
— | — | — | — | — | S*WF*85 | CSHD183 | CSHD183 | — | tengah | Ora Req. | — | — | — | |
— | — | — | — | RAUJC60 | — | CSHD175 | CSHD175 | — | bener | Ora Req. | — | — | — | |
— | S*HL*75/89 G | — | — | — | — | CSHN184 | CSHN250 | — | bener | 31 | — | — | X17311028510 | RSR00241 |
— | S*HL*75 | — | — | — | — | CSHN176 | CSHN240 | — | bener | 31 | — | — | X17311028510 | RSR00241 |
S*HJ090 S*HJ100 | SXHK*90 | — | — | — | — | CSHN250 | CSHN250 | — | ngiwa |
Ora Req. |
— | — | — | |
S*HJ090 S*HJ100 | SXHK*90 | — | — | — | — | — | — | — | bener | — | — | — | ||
S*HJ105 S*HJ118 | SXHK*11 SXHK*12 | — | — | — | — | CSHN250 | CSHN315 | — | ngiwa | 31 | — | — | X17311028510 | RSR00241 |
S*HJ105 S*HJ118 | SXHK*11 SXHK*12 | — | — | — | — | — | — | — | bener | 31 | — | — | X17311028510 | RSR00241 |
S*HJ120 S*HJ128 | SXHK*13 | — | — | — | — | CSHN315 | CSHN315 | — | ngiwa |
Ora Req. |
— | — | — | |
S*HJ120 S*HJ128 | SXHK*13 | — | — | — | — | — | — | — | bener | — | — | — | ||
S*HJ130 S*HJ140 | — | — | — | — | — | CSHN315 | CSHN374 | — | ngiwa | 31 | — | — | X17311028510 | RSR00241 |
S*HJ130 S*HJ140 | — | — | — | — | — | — | — | — | bener | 31 | — | — | X17311028510 | RSR00241 |
S*HJ150 S*HJ162 | — | — | — | — | — | CSHN374 | CSHN374 | — | ngiwa |
Ora Req. |
— | — | — | |
S*HJ150 S*HJ162 | — | — | — | — | — | — | — | — | bener | — | — | — | ||
— | — | — | — | RAUJD80 | — | CSHN176 | CSHN176 | CSHN176 | ngiwa | — | — | 31 | X17311028510 | RSR00241 |
— | — | — | — | RAUJD100 | — | CSHN184 | CSHN184 | CSHN250 | ngiwa | 33 | 33 | X17311028520 | RSR00242 | |
— | — | — | — | RAUJD120 | — | CSHN250 | CSHN250 | CSHN250 | ngiwa | — | — | 33 | X17311028520 | RSR00242 |
Cathetan
- IPAK RT G unit pendingin udara efisiensi dhuwur-digit G sing kadhaptar ing Posisi 21–38 ing nomer model.
- IPAK RTsizes 24, 29, 36, 48, 59, 73, 80, 89 minangka model kondensor pendingin evaporatif
Trane lan American Standard nggawe lingkungan njero ruangan sing nyaman lan efisien energi kanggo aplikasi komersial lan omah. Kanggo informasi luwih lengkap, bukak trane.com or americanstandardair.com.
Trane lan American Standard duwe kabijakan kanggo nambah data produk lan produk sing terus-terusan lan nduweni hak kanggo ngganti desain lan spesifikasi tanpa kabar. Kita setya nggunakake praktik cetak sadar lingkungan.
PART-SVN257B-EN 24 Feb 2025
Ngganti PART-SVN257A-EN (Juli 2023)
Pitakonan sing Sering Ditakoni
- P: Sapa sing kudu nginstal lan nglayani peralatan kasebut?
A: Mung personel qualified kudu nginstal lan layanan peralatan kanggo njamin safety lan operasi sing tepat. - P: Apa jinis refrigeran sing digunakake ing unit kasebut?
A: Unit nggunakake refrigeran R-410A, sing beroperasi ing tekanan sing luwih dhuwur tinimbang R-22. Penting mung nggunakake peralatan layanan sing dirating R-410A karo unit kasebut. - P: Apa pancegahan sing kudu ditindakake nalika nggarap peralatan?
A: Tansah mirsani kabeh pancegahan safety, nyandhang PPE sing tepat, tindakake kabel lapangan lan syarat grounding sing tepat, lan netepi praktik refrigeran sing tanggung jawab kanggo ngindhari bebaya lan njamin operasi sing aman.
Dokumen / Sumber Daya
![]() |
TRANE SVN257B Restrictor Panggantos Kompresor [pdf] Pandhuan Instalasi PART-SVN257B-EN, SVN257B Kompresor Pengganti Restrictor, Kompresor Pengganti Restrictor, Kompresor Ganti, Kompresor |