TRANE SVN257B Restrictor Replacement Compressor
Product Information
Specifications
- Model: PART-SVN257B-EN
- Compressor Type: Replacement Compressor
- Refrigerant: R-410A
- Operating Pressure: High Pressure
Installation Instructions
Restrictor
For Replacement Compressorz
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
- Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
- When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
- If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
- All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage.
System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
WARNING
R-410A Refrigerant under Higher
Pressure than R-22!
Failure to use proper equipment or components as described below, could result in equipment failing and possibly exploding, which could result in death, serious injury, or equipment damage.
The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Trane representative.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
WARNING
Explosion Hazard and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
WARNING
Explosion Hazard!
Failure to follow safe leak test procedures below could result in death or serious injury or equipment or property-only-damage.
Never use an open flame to detect gas leaks. Use a leak test solution for leak testing.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
- Units with microchannel (MCHE) condensers table is divided as per product in Installation chapter.
- Updated the Service part restrictor identification, IPAK 2, IPAK 1, Voyager 3, RAU Large splits, and IPAK 3 tables in Installation chapter.
Installation
Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17 provide the information for the correct location and selection of the restrictor.
The service compressor is shipped with the necessary restrictor(s) packaged in individual bags and labeled with the restrictor mnemonic part number on the outside of the bag. Another label is also included inside the bag. The X1731****** number identifies the restrictor. The restrictor is physically marked on the face with the part number extension and ID size.
Note: 51-25 stamped on the face of the restrictor. Drawing X17311040510, 51 is the extension. 25 mm is the ID.
When removing a restrictor, the restrictor in the compressor may not match the number of the restrictor shipping with the service compressor.
The restrictor part number is dependent on the product type, manufacturing location, and if originally packaged in a bag. See Table 1, p. 6 for equivalent restrictor face stamping number and mnemonic part number cross reference.
Table 1. Service part restrictor identification
MNE | Label | Restrictor | |
ID Size (mm) | Face Stamping Number | ||
RSR00235 | X17311040510 | 25 | 51-25 |
RSR00348 | X17311040570 | 22.5 | 57-22.5 |
RSR00237 | X17311040530 | 23 | 53-23 |
RSR00238 | X17311040540 | 27 | 54-27 |
RSR00240 | X17311040560 | 26 | 56-26 |
RSR00244 | X17311028540 | 26 | 54-26 |
RSR00241 | X17311028510 | 31 | 51-31 |
RSR00242 | X17311028520 | 33 | 52-33 |
RSR00366 | X17311028560 | 32 | 56-32 |
RSR00355 | X17311040600 | 15 | 60-15 |
RSR00354 | X17311040590 | 19 | 59-19 |
RSR00353 | X17311040580 | 22 | 58-22 |
RSR00380 | X17311040680 | 20 | 68-20 |
Install restrictor in the suction inlet of the replacement compressor.
- Insert the tube into the suction connection and use the tube to seat the restrictor firmly into the suction connection.
- Braze the suction tube to the compressor.
- After completing the brazing of the suction tube, attach the label included inside the bag to the compressor near the suction connection. This will enable future identification of the restrictor.
The suction approach is the direction from which the unit suction piping enters the compressor tandem or trio set when viewed from the front, terminal box side. This must be determined to use Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17 it is also used in determining the correct compressor to receive the restrictor.
In addition to suction approach, verify compressor model numbers in the serviced unit match the designated CP1, CP2, and CP3 compressors in their respective circuits when referencing Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17. If the compressor model numbers do not match, call Trane Tech Support for assistance.
Table 2. IPAK 2 — suction restrictor size and location
Digit 4 – Develop- ment sequence | Digit 5,6,7 –
Nominal Cooling capacity |
Digit 28 – Efficiency, Capacity, and Drain Pan Option | Circuit # | Compressor Position | Suct. Appr. | Restrictor Size (ID mm) and Location | Trane Part Number | Mnemonic Part Number | ||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
E |
090 |
A/C |
1 | CSHN250 | CSHN250 | — | Left | Not Req. | — | — | ||
2 | CSHN250 | CSHN250 | — | Right | Not Req. | — | — | |||||
W/Z |
1 | VZH170 | CSHL169 | — | Left | Not Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL169 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
105 |
A/C |
1 | CSHN184 | CSHN184 | CSHN184 | Left | — | — | 31 | X17311028510 | RSR00241 | |
2 | CSHN184 | CSHN184 | CSHN184 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHL227 | — | Left | Not Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL169 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
120 |
A/C |
1 | CSHN184 | CSHN184 | CSHN250 | Left | 33 | 33 | — | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|
2 | CSHN184 | CSHN184 | CSHN250 | Right | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHL285 | — | Left | Not Req. | — | — | ||||
2 | CSHL169 | CSHL169 | CSHL227 | Right | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
130 |
A/C |
1 | CSHN240 | CSHN240 | CSHN240 | Left | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHN240 | CSHN240 | CSHN240 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHL346 | — | Left | Not Req. | — | — | ||||
2 | CSHL227 | CSHL227 | CSHL227 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
150 |
A/C |
1 | CSHN250 | CSHN250 | CSHN250 | Left | 33 | — | — | X17311028520 | RSR00242 | |
2 | CSHN250 | CSHN250 | CSHN250 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHL346 | — | Left | Not Req. | — | — | ||||
2 | CSHL227 | CSHL169 | CSHL346 | Right | 31 | 26 | — | X17311028510 /
X17311028540 |
RSR00241 /
RSR00244 |
|||
T |
090 |
A/C |
1 | CSHP237 | CSHP237 | — | Left | Not Req. | — | — | ||
2 | CSHP237 | CSHP237 | — | Right | Not Req. | — | — | |||||
W/Z |
1 | VZH170 | CSHP178 | — | Left | Not Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP178 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
105 |
A/C |
1 | CSHP178 | CSHP178 | CSHP178 | Left | — | — | 31 | X17311028510 | RSR00241 | |
2 | CSHP178 | CSHP178 | CSHP178 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHP237 | — | Left | Not Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP178 | Right | 32 | — | 31 | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
Digit 4 – Develop- ment sequence |
Digit 5,6,7 –
Nominal Cooling capacity |
Digit 28 – Efficiency, Capacity, and Drain Pan Option |
Circuit # |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
T |
120 |
A/C |
1 | CSHP178 | CSHP178 | CSHP237 | Left | 33 | 33 | — | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
2 | CSHP178 | CSHP178 | CSHP237 | Right | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
W/Z |
1 | VZH170 | CSHP297 | — | Left | Not Req. | — | — | ||||
2 | CSHP178 | CSHP178 | CSHP237 | Right | 32 | 31 | — | X17311028560 /
X17311028510 |
RSR00366 /
RSR00241 |
|||
130 |
A/C |
1 | CSHP227 | CSHP227 | CSHP227 | Left | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHP227 | CSHP227 | CSHP227 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHP346 | — | Left | Not Req. | — | — | ||||
2 | CSHP227 | CSHP227 | CSHP227 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
150 |
A/C |
1 | CSHP237 | CSHP237 | CSHP237 | Left | — | — | 33 | X17311028520 | RSR00242 | |
2 | CSHP237 | CSHP237 | CSHP237 | Right | 33 | — | 33 | X17311028520 /
X17311028520 |
RSR00242 /
RSR00242 |
|||
W/Z |
1 | VZH170 | CSHP346 | — | Left | Not Req. | — | — | ||||
2 | CSHP237 | CSHP178 | CSHP346 | Right | 31 | 26 | — | X17311028510 /
X17311028540 |
RSR00241 /
RSR00244 |
Note: IPAK 2 90 to 150 ton MCHE: no change in compressors digit 10 design sequence P.
Table 3. IPAK 1 — suction restrictor size and location
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Digit 26 – Effiicency Options |
Circuit # |
Compressor Position |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
M |
*20 |
0 | 1 | ZP154 | ZPS104 | — | Not Req. | — | — | ||
H | 1 | ZP154 | ZPS104 | — | Not Req. | — | — | ||||
V | 1 | VZH088 | CSHD110 | — | Not Req. | — | — | ||||
*25 |
0 | 1 | CSHD075 | CSHD110 | CSHD110 | 15 | — | — | X17311040600 | RSR00355 | |
H | 1 | ZP182 | ZPS122 | — | Not Req. | — | — | ||||
V | 1 | VZH088 | CSHD125 | — | Not Req. | — | — | ||||
*30 |
0 | 1 | CSHD075 | CSHD120 | CSHD120 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | CSHD075 | CSHD120 | CSHD120 | 19 | — | — | X17311040590 | RSR00354 | ||
V | 1 | VZH117 | CSHD161 | — | Not Req. | — | — | ||||
*40 |
0 |
1 | CSHD092 | CSHD110 | — | 25 | — | — | X17311040510 | RSR00235 | |
2 | CSHD110 | CSHD110 | — | Not Req. | — | — | |||||
H |
1 | CSHD092 | CSHD092 | — | Not Req. | — | — | ||||
2 | CSHD092 | CSHD110 | — | 25 | — | — | X17311040510 | RSR00235 | |||
V |
1 | VZH117 | — | — | Not Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | Not Req. | — | — |
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Digit 26 – Effiicency Options |
Circuit # |
Compressor Position |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
M |
*50 |
0 |
1 | CSHD125 | CSHD125 | — | Not Req. | — | — | ||
2 | CSHD125 | CSHD125 | — | Not Req. | — | — | |||||
H |
1 | CSHD125 | CSHD142 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHD125 | CSHD142 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | Not Req. | — | — | |||||
*55 |
0 |
1 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |
2 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |||
H |
1 | CSHD142 | CSHD142 | — | Not Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHD142 | CSHD161 | — | 27 | — | — | X17311040540 | RSR00238 | |||
*60 |
0 |
1 | CSHD161 | CSHD161 | — | Not Req. | — | — | |||
2 | CSHD161 | CSHD161 | — | Not Req. | — | — | |||||
H |
1 | CSHD161 | CSHD161 | — | Not Req. | — | — | ||||
2 | CSHD161 | CSHD183 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHD161 | CSHD183 | — | 26 | — | — | X17311040560 | RSR00240 | |||
*70 |
0 |
1 | CSHD183 | CSHD183 | — | Not Req. | — | — | |||
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHD183 | CSHD183 | — | Not Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*75 |
0 |
1 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHN184 | CSHN250 | — | 31 | — | — | X17311028510 | RSR00241 | ||
2 | CSHN250 | CSHN250 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | CSHN184 | — | Not Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | Not Req. | — | — | |||||
*90 |
0/H |
1 | CSHN250 | CSHN250 | — | Not Req. | — | — | |||
2 | CSHN250 | CSHN250 | — | Not Req. | — | — | |||||
*11 |
0/H |
1 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*12 |
0/H |
1 | CSHN250 | CSHN315 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHN315 | CSHN315 | — | Not Req. | — | — | |||||
*13 |
0/H |
1 | CSHN315 | CSHN315 | — | Not Req. | — | — | |||
2 | CSHN315 | CSHN374 | — | 31 | — | — | X17311028510 | RSR00241 |
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Digit 26 – Effiicency Options |
Circuit # |
Compressor Position |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
P |
*20 |
0 | 1 | YA154 | YAS104 | — | Not Req. | — | — | ||
H | 1 | YA154 | YAS104 | — | Not Req. | — | — | ||||
V | 1 | VZH088 | CSHE113 | — | Not Req. | — | — | ||||
*25 |
0 | 1 | CSHE071 | CSHE113 | CSHE113 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | YA182 | YAS122 | — | Not Req. | — | — | ||||
V | 1 | VZH088 | CSHE132 | — | Not Req. | — | — | ||||
*30 |
0 | 1 | CSHE071 | CSHE127 | CSHE127 | 19 | — | — | X17311040590 | RSR00354 | |
H | 1 | CSHE071 | CSHE117 | CSHE117 | 19 | — | — | X17311040590 | RSR00354 | ||
V | 1 | VZH117 | CSHE152 | — | Not Req. | — | — | ||||
*40 |
0 |
1 | CSHE104 | CSHE113 | — | Not Req. | — | — | |||
2 | CSHE104 | CSHE113 | — | Not Req. | — | — | |||||
H |
1 | CSHE088 | CSHE104 | — | 25 | — | — | X17311040510 | RSR00235 | ||
2 | CSHE088 | CSHE104 | — | 25 | — | — | X17311040510 | RSR00235 | |||
V |
1 | VZH117 | — | — | Not Req. | — | — | ||||
2 | CSHE113 | CSHE113 | — | Not Req. | — | — | |||||
*50 |
0 |
1 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | |||
H |
1 | CSHE117 | CSHE132 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE132 | CSHE132 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | Not Req. | — | — | |||||
*55 |
0 |
1 | CSHE132 | CSHE152 | — | 27 | — | — | X17311040540 | RSR00238 | |
2 | CSHE152 | CSHE152 | — | Not Req. | — | — | |||||
H |
1 | CSHE132 | CSHE132 | — | Not Req. | — | — | ||||
2 | CSHE132 | CSHE152 | — | 27 | — | — | X17311040540 | RSR00238 | |||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHE152 | CSHE152 | — | Not Req. | — | — | |||||
*60 |
0 |
1 | CSHE152 | CSHE152 | — | Not Req. | — | — | |||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | |||
H |
1 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 | |||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHE152 | CSHE177 | — | 26 | — | — | X17311040560 | RSR00240 |
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Digit 26 – Effiicency Options |
Circuit # |
Compressor Position |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | ||||||
P |
*70 |
0 |
1 | CSHE177 | CSHE177 | — | Not Req. | — | — | ||
2 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHE177 | CSHE177 | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | — | — | Not Req. | — | — | ||||
2 | CSHP227 | CSHP227 | — | Not Req. | — | — | |||||
*75 |
0 |
1 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | |||
H |
1 | CSHP178 | CSHP237 | — | 31 | — | — | X17311028510 | RSR00241 | ||
2 | CSHP237 | CSHP237 | — | Not Req. | — | — | |||||
V |
1 | VZH170 | CSHP178 | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | Not Req. | — | — | |||||
90 |
0/H |
1 | CSHP237 | CSHP237 | — | Not Req. | — | — | |||
2 | CSHP237 | CSHP237 | — | Not Req. | — | — | |||||
*11 |
0/H |
1 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |||
*12 |
0/H |
1 | CSHP237 | CSHP297 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP297 | CSHP297 | — | Not Req. | — | — | |||||
*13 |
0/H |
1 | CSHP297 | CSHP346 | — | 31 | — | — | X17311028510 | RSR00241 | |
2 | CSHP297 | CSHP346 | — | 31 | — | — | X17311028510 | RSR00241 |
Notes
- IPAK RT G high efficiency unit—indicated by G in digit 26 of model number.
- IPAK RTsizes 24, 29, 36, 48, 59, 73, 80, 89 are evaporative cooled condenser models.
- IPAK RT 20 to 75 ton MCHE digit 10 design Sequence E.
- IPAK RT 90 to 130 ton MCHE: no change in compressors digit 10 design sequence D.
- IPAK RT V eFlex™ variable speed unit – indicated by V in digit 26 of model number.
Table 4. Voyager 3 — suction restrictor size and location
Digit 7- Major development sequence |
Digit 29 – Efficiency |
Digit 4,5,6 – Nominal Cooling capacity |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
||||||
C |
0 / J |
330 | CSHD075 | CSHD110 | CSHD110 | Left | 15 | — | — | X17311040600 | RSR00355 |
360 | CSHD075 | CSHD120 | CSHD120 | Left | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHD075 | CSHD136 | CSHD136 | Left | None | — | — | ||||
480 | CSHD092 | CSHD155 | CSHD155 | Left | None | — | — | ||||
600 | CSHD120 | CSHD183 | CSHD183 | Left | 22 | — | — | X17311040580 | RSR00353 | ||
K / L |
330 | CSHD075 | CSHD110 | CSHD110 | Left | 15 | — | — | X17311040600 | RSR00355 | |
360 | CSHD075 | CSHD120 | CSHD120 | Left | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHD089 | CSHD136 | CSHD136 | Left | None | — | — | ||||
480 | CSHD092 | CSHD155 | CSHD155 | Left | None | — | — | ||||
600 | CSHD120 | CSHD183 | CSHD183 | Left | 22 | — | — | X17311040580 | RSR00353 | ||
D |
0 / J / K / L |
330 | CSHE071 | CSHE113 | CSHE113 | Left | 15 | — | — | X17311040600 | RSR00355 |
360 | CSHE071 | CSHE127 | CSHE127 | Left | 19 | — | — | X17311040590 | RSR00354 | ||
420 | CSHE088 | CSHE132 | CSHE132 | Left | None | — | — | ||||
480 | CSHE097 | CSHE152 | CSHE152 | Left | 20 | — | — | X17311040680 | RSR00380 | ||
600 | CSHE117 | CSHE177 | CSHE177 | Left | 22 | — | — | X17311040580 | RSR00353 |
Note: Voyager 3 MCHE: no change in compressors digit 10 design sequence F.
Table 5. RA — suction restrictor size and location
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
|||||
J |
C20 | CSHD120 | CSHD120 | — | Right | Not Req. | — | — | ||
C25 | CSHD125 | CSHD161 | — | Right | 25 | — | — | X17311040510 | RSR00235 | |
C30 | CSHD183 | CSHD183 | — | Right | Not Req. | — | — | |||
C40 | CSHD120 | CSHD120 | — | Right | Not Req. | — | — | |||
C50 | CSHD142 | CSHD161 | — | Right | 27 | — | — | X17311040540 | RSR00238 | |
C60 | CSHD175 | CSHD175 | — | Right | Not Req. | — | — | |||
C80 | CSHN176 | CSHN176 | CSHN176 | Left | — | — | 31 | X17311028510 | RSR00241 | |
D10 | CSHN184 | CSHN184 | CSHN250 | Left | 33 | 33 | — | X17311028520 | RSR00242 | |
D12 | CSHN250 | CSHN250 | CSHN250 | Left | — | — | 33 | X17311028520 | RSR00242 | |
K |
C20 | YA154 | YAS104 | — | Right | Not Req. | — | — | ||
C25 | YA182 | YAS122 | — | Right | Not Req. | — | — | |||
C30 | CSHE088 | CSHE132 | CSHE132 | Right | Not Req. | — | — | |||
C40 | CSHE117 | CSHE132 | — | Right | 26 | — | — | X17311040560 | RSR00240 | |
C50 | CSHE132 | CSHE145 | — | Right | 27 | — | — | X17311040540 | RSR00238 |
Digit 4 – Development sequence |
Digit 5,6,7 – Nominal Cooling capacity |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 |
CP2 |
CP3 |
CP1 |
CP2 |
CP3 |
|||||
K |
C60 | CSHE177 | CSHE177 | — | Right | Not Req. | — | — | ||
C80 | CSHP178 | CSHP178 | CSHP178 | Left | — | — | 31 | X17311028510 | RSR00241 | |
D10 | CSHP178 | CSHP178 | CSHP237 | Left | 33 | 33 | — | X17311028520 | RSR00242 | |
D12 | CSHP237 | CSHP237 | CSHP237 | Left | — | — | 33 | X17311028520 | RSR00242 |
Notes
- RAUJ split system 20 to 60 ton MCHE: no change in compressors digit 10 design sequence C.
- RAUJ split system 20 to 120 ton MCHE: no change in compressors digit 10 design sequence B.
Table 6. IPAK 3 — suction restrictor size and location
Digit 12 – Develop- ment sequence |
Digit 3,4,5 – Nominal Cooling capacity |
Digit 9 – Refrigera- tion System Perform- ance |
Circuit # |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number |
Mnemonic Part Number |
||||
CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||||||
A |
020 |
1 | 1 | CSHW058 | CSHW089 | CSHW089 | — | Not Req. | — | — | ||
2 | 1 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
3 | 1 | VZH088 | CSHD110 | — | — | Not Req. | — | — | ||||
025 |
1 | 1 | CSHD075 | CSHD110 | CSHD110 | — | 15 | — | — | X17311040600 | RSR00355 | |
2 | 1 | CSHD142 | CSHD161 | — | — | 27 | — | — | X17311040540 | RSR00238 | ||
3 | 1 | VZH088 | CSHD125 | — | — | Not Req. | — | — | ||||
030 |
1 | 1 | CSHD075 | CSHD120 | CSHD120 | — | 19 | — | — | X17311040590 | RSR00354 | |
2 | 1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
3 | 1 | VZH117 | CSHD161 | — | — | Not Req. | — | — | ||||
040 |
1 |
1 | CSHD110 | CSHD110 | — | — | Not Req. | — | — | |||
2 | CSHD110 | CSHD110 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHD110 | CSHD110 | — | — | Not Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH117 | — | — | — | Not Req. | — | — | ||||
2 | CSHD110 | CSHD110 | — | — | Not Req. | — | — | |||||
050 |
1 |
1 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHD125 | CSHD125 | — | — | Not Req. | — | — | ||||
2 | CSHD125 | CSHD125 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | — | Not Req. | — | — |
A |
055 |
1 |
1 | CSHD142 | CSHD142 | — | — | Not Req. | — | — | ||
2 | CSHD142 | CSHD142 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHD125 | CSHD142 | — | — | 26 | — | X17311040560 | RSR00240 | |||
2 | CSHD125 | CSHD142 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHD142 | CSHD142 | — | — | Not Req. | — | — | |||||
060 |
1 |
1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHD161 | CSHD161 | — | — | Not Req. | — | — | ||||
2 | CSHD161 | CSHD161 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||||
070 |
1 |
1 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||
2 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHD161 | CSHD183 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHD161 | CSHD183 | — | — | 26 | — | X17311040560 | RSR00240 | ||||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||||
075 |
1 |
1 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||
2 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | ||||
2 | CSHD183 | CSHD183 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | CSHN184 | — | — | Not Req. | — | — | ||||
2 | CSHD161 | CSHD161 | — | — | Not Req. | — | — | |||||
B |
020 | 3 | 1 | VZH088 | CSHE113 | — | — | Not Req. | — | — | ||
025 |
2 | 1 | CSHE071 | CSHE113 | CSHE113 | — | 19 | — | — | X17311040590 | RSR00354 | |
3 | 1 | VZH088 | CSHE132 | — | — | Not Req. | — | — | ||||
030 |
1 | 1 | CSHE071 | CSHE117 | CSHE117 | — | 19 | — | — | X17311040590 | RSR00354 | |
2 | 1 | CSHE071 | CSHE132 | CSHE132 | — | 19 | — | — | X17311040590 | RSR00354 | ||
3 | 1 | VZH117 | CSHE152 | — | — | Not Req. | — | — | ||||
040 |
1 |
1 | CSHE104 | CSHE113 | — | — | Not Req. | — | — | |||
2 | CSHE104 | CSHE113 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHE104 | CSHE113 | — | — | Not Req. | — | — | ||||
2 | CSHE104 | CSHE113 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH117 | — | — | — | Not Req. | — | — | ||||
2 | CSHE113 | CSHE113 | — | — | Not Req. | — | — |
B |
050 |
1 |
1 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 |
2 | CSHE132 | CSHE132 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE117 | CSHE132 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Not Req. | — | — | |||||
055 |
1 |
1 | CSHE132 | CSHE145 | — | — | Not Req. | — | — | |||
2 | CSHE132 | CSHE145 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHE132 | CSHE132 | — | — | Not Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHE145 | CSHE145 | — | — | Not Req. | — | — | |||||
060 |
1 |
1 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |
2 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
2 |
1 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | ||
2 | CSHE152 | CSHE177 | — | — | 26 | — | — | X17311040560 | RSR00240 | |||
3 |
1 | VZH170 | — | — | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||||
070 |
1 |
1 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | CSHP178 | — | — | Not Req. | — | — | ||||
2 | CSHE132 | CSHE132 | — | — | Not Req. | — | — | |||||
075 |
1 |
1 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||||
2 |
1 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — | |||||
3 |
1 | VZH170 | CSHP178 | — | — | Not Req. | — | — | ||||
2 | CSHE177 | CSHE177 | — | — | Not Req. | — | — |
Table 7. Legacy restrictor selection and location
Product Line |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number w/Bag and Label |
Mnemonic # |
|||||||||
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Macon |
|||||||||
IPAK 2 | IPAK 1 | Voyager 3 | Odyssey | RA | CSC | CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||
— | S*HL*40 | — | — | — | — | CSHD092 | CSHD110 | — | right | — | 25 | — | X17311040510 | RSR00235 |
— | S*HL*40/48 G | — | — | — | — | CSHD110 | CSHD110 | — | right | Not Req. | — | — | — | |
— | S*HL*20/24 G | — | — | — | — | CSHD125 | CSHD125 | — | right | Not Req. | — | — | — | |
— | — | — | TTA240 F | — | — | CSHD120 | CSHD120 | — | left |
Not Req. |
— | — | — | |
— | S*HL*20 | — | — | RAUJC20 RAUJC40 | — | CSHD120 | CSHD120 | — | right | — | — | — | ||
— | — | — | — | — | S*RF*30 S*RF*35 | CSHD120 | CSHD120 | — | center | Not Req. | — | — | — | |
— | S*HL*25 | — | — | — | — | CSHD125 | CSHD142 | — | right | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL*50 | — | — | — | — | CSHD120 | CSHD136 | — | right | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL25/29 G | — | — | RAUJC25 | — | CSHD125 | CSHD161 | — | right | 25 | — | — | X17311040510 | RSR00235 |
— | S*HL*50/59 G | — | — | — | — | CSHD142 | CSHD142 | — | right | Not Req. | — | — | — | |
— | — | TC/TE/YC 330 | — | — | — | CSHD142 | CSHD161 | — | left | 27 | — | — | X17311040540 | RSR00238 |
— | S*HL*60 | — | — | RAUJC50 | — | CSHD142 | CSHD161 | — | right | 27 | — | — | X17311040540 | RSR00238 |
— | — | TC/TE/YC 360 | — | — | — | CSHD161 | CSHD161 | — | left |
Not Req. |
— | — | — | |
— | S*HL*30 S*HL*60/73 G | — | — | — | — | CSHD161 | CSHD161 | — | right | — | — | — | ||
— | — | TC/TE/YC 420 | — | — | — | CSHD161 | CSHD183 | — | left | 26 | — | — | X17311040560 | RSR00240 |
— | S*HL*30/36 G | — | — | — | — | CSHD161 | CSHD183 | — | right | 26 | — | — | X17311040560 | RSR00240 |
— | — | TC/TE/YC 600 | — | — | — | CSHD155 | CSHD183 | — | left | 25 | — | — | X17311040510 | RSR00235 |
— | — | — | — | — | S*RF*40 | CSHD183 | CSHD120 | — | center | 22.5 | — | X17311040570 | RSR00348 | |
— | S*HL*70/80 | — | — | RAUJC30 | — | CSHD183 | CSHD183 | — | right | Not Req. | — | — | — | |
— | — | — | — | — | S*RF*50 | CSHD183 | CSHD183 | — | center | Not Req. | — | — | — |
Product Line |
Compressor Position |
Suct. Appr. |
Restrictor Size (ID mm) and Location |
Trane Part Number w/Bag and Label |
Mnemonic # |
|||||||||
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Clarksville |
Macon |
|||||||||
IPAK 2 | IPAK 1 | Voyager 3 | Odyssey | RA | CSC | CP1 | CP2 | CP3 | CP1 | CP2 | CP3 | |||
— | — | — | — | — | S*RF*60 | CSHD183 | CSHD183 | — | center | Not Req. | — | — | — | |
— | — | — | — | — | S*WF*85 | CSHD183 | CSHD183 | — | center | Not Req. | — | — | — | |
— | — | — | — | RAUJC60 | — | CSHD175 | CSHD175 | — | right | Not Req. | — | — | — | |
— | S*HL*75/89 G | — | — | — | — | CSHN184 | CSHN250 | — | right | 31 | — | — | X17311028510 | RSR00241 |
— | S*HL*75 | — | — | — | — | CSHN176 | CSHN240 | — | right | 31 | — | — | X17311028510 | RSR00241 |
S*HJ090 S*HJ100 | SXHK*90 | — | — | — | — | CSHN250 | CSHN250 | — | left |
Not Req. |
— | — | — | |
S*HJ090 S*HJ100 | SXHK*90 | — | — | — | — | — | — | — | right | — | — | — | ||
S*HJ105 S*HJ118 | SXHK*11 SXHK*12 | — | — | — | — | CSHN250 | CSHN315 | — | left | 31 | — | — | X17311028510 | RSR00241 |
S*HJ105 S*HJ118 | SXHK*11 SXHK*12 | — | — | — | — | — | — | — | right | 31 | — | — | X17311028510 | RSR00241 |
S*HJ120 S*HJ128 | SXHK*13 | — | — | — | — | CSHN315 | CSHN315 | — | left |
Not Req. |
— | — | — | |
S*HJ120 S*HJ128 | SXHK*13 | — | — | — | — | — | — | — | right | — | — | — | ||
S*HJ130 S*HJ140 | — | — | — | — | — | CSHN315 | CSHN374 | — | left | 31 | — | — | X17311028510 | RSR00241 |
S*HJ130 S*HJ140 | — | — | — | — | — | — | — | — | right | 31 | — | — | X17311028510 | RSR00241 |
S*HJ150 S*HJ162 | — | — | — | — | — | CSHN374 | CSHN374 | — | left |
Not Req. |
— | — | — | |
S*HJ150 S*HJ162 | — | — | — | — | — | — | — | — | right | — | — | — | ||
— | — | — | — | RAUJD80 | — | CSHN176 | CSHN176 | CSHN176 | left | — | — | 31 | X17311028510 | RSR00241 |
— | — | — | — | RAUJD100 | — | CSHN184 | CSHN184 | CSHN250 | left | 33 | 33 | X17311028520 | RSR00242 | |
— | — | — | — | RAUJD120 | — | CSHN250 | CSHN250 | CSHN250 | left | — | — | 33 | X17311028520 | RSR00242 |
Notes
- IPAK RT G high efficiency air cooled unit—digit G listed in Position 21–38 in model number.
- IPAK RTsizes 24, 29, 36, 48, 59, 73, 80, 89 are evaporative cooled condenser models
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
PART-SVN257B-EN 24 Feb 2025
Supersedes PART-SVN257A-EN (July 2023)
Frequently Asked Questions
- Q: Who should install and service the equipment?
A: Only qualified personnel should install and service the equipment to ensure safety and proper operation. - Q: What type of refrigerant does the unit use?
A: The unit uses R-410A refrigerant, which operates at higher pressures than R-22. It is important to use only R-410A rated service equipment with these units. - Q: What precautions should be taken when working with the equipment?
A: Always observe all safety precautions, wear proper PPE, follow proper field wiring and grounding requirements, and adhere to responsible refrigerant practices to avoid hazards and ensure safe operation.
Documents / Resources
![]() |
TRANE SVN257B Restrictor Replacement Compressor [pdf] Installation Guide PART-SVN257B-EN, SVN257B Restrictor Replacement Compressor, Restrictor Replacement Compressor, Replacement Compressor, Compressor |