Product Information

Specifications

  • Model: PART-SVN257B-EN
  • Compressor Type: Replacement Compressor
  • Refrigerant: R-410A
  • Operating Pressure: High Pressure

Installation Instructions
Restrictor
For Replacement CompressorzTRANE-SVN257B-Restrictor-Replacement-Compressor- (1)

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage.
System contains refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.

WARNING
R-410A Refrigerant under Higher
Pressure than R-22!
Failure to use proper equipment or components as described below, could result in equipment failing and possibly exploding, which could result in death, serious injury, or equipment damage.
The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Trane representative.

WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.

WARNING
Explosion Hazard and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.

WARNING
Explosion Hazard!
Failure to follow safe leak test procedures below could result in death or serious injury or equipment or property-only-damage.
Never use an open flame to detect gas leaks. Use a leak test solution for leak testing.

WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

  • Units with microchannel (MCHE) condensers table is divided as per product in Installation chapter.
  • Updated the Service part restrictor identification, IPAK 2, IPAK 1, Voyager 3, RAU Large splits, and IPAK 3 tables in Installation chapter.

Installation

Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17 provide the information for the correct location and selection of the restrictor.
The service compressor is shipped with the necessary restrictor(s) packaged in individual bags and labeled with the restrictor mnemonic part number on the outside of the bag. Another label is also included inside the bag. The X1731****** number identifies the restrictor. The restrictor is physically marked on the face with the part number extension and ID size.

Note: 51-25 stamped on the face of the restrictor. Drawing X17311040510, 51 is the extension. 25 mm is the ID.
When removing a restrictor, the restrictor in the compressor may not match the number of the restrictor shipping with the service compressor.
The restrictor part number is dependent on the product type, manufacturing location, and if originally packaged in a bag. See Table 1, p. 6 for equivalent restrictor face stamping number and mnemonic part number cross reference.

Table 1. Service part restrictor identification

 MNE  Label Restrictor
ID Size (mm) Face Stamping Number
RSR00235 X17311040510 25 51-25
RSR00348 X17311040570 22.5 57-22.5
RSR00237 X17311040530 23 53-23
RSR00238 X17311040540 27 54-27
RSR00240 X17311040560 26 56-26
RSR00244 X17311028540 26 54-26
RSR00241 X17311028510 31 51-31
RSR00242 X17311028520 33 52-33
RSR00366 X17311028560 32 56-32
RSR00355 X17311040600 15 60-15
RSR00354 X17311040590 19 59-19
RSR00353 X17311040580 22 58-22
RSR00380 X17311040680 20 68-20
  1. TRANE-SVN257B-Restrictor-Replacement-Compressor- (2) TRANE-SVN257B-Restrictor-Replacement-Compressor- (3)Install restrictor in the suction inlet of the replacement compressor.
  2. Insert the tube into the suction connection and use the tube to seat the restrictor firmly into the suction connection.
  3. Braze the suction tube to the compressor.
  4. After completing the brazing of the suction tube, attach the label included inside the bag to the compressor near the suction connection. This will enable future identification of the restrictor.

TRANE-SVN257B-Restrictor-Replacement-Compressor- (4)

The suction approach is the direction from which the unit suction piping enters the compressor tandem or trio set when viewed from the front, terminal box side. This must be determined to use Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17 it is also used in determining the correct compressor to receive the restrictor.

In addition to suction approach, verify compressor model numbers in the serviced unit match the designated CP1, CP2, and CP3 compressors in their respective circuits when referencing Table 2, p. 8, Table 3, p. 9, Table 4, p. 13, Table 5, p. 13 , Table 6, p. 14, and Table 7, p. 17. If the compressor model numbers do not match, call Trane Tech Support for assistance.

Table 2. IPAK 2 — suction restrictor size and location

 Digit 4 – Develop- ment sequence Digit 5,6,7 –

Nominal Cooling capacity

Digit 28 – Efficiency, Capacity, and Drain Pan Option  Circuit #  Compressor Position  Suct. Appr.  Restrictor Size (ID mm) and Location  Trane Part Number  Mnemonic Part Number
CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

090

 

A/C

1 CSHN250 CSHN250 Left Not Req.
2 CSHN250 CSHN250 Right Not Req.
 

W/Z

1 VZH170 CSHL169 Left Not Req.
2 CSHL169 CSHL169 CSHL169 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

 

 

105

 

A/C

1 CSHN184 CSHN184 CSHN184 Left 31 X17311028510 RSR00241
2 CSHN184 CSHN184 CSHN184 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

W/Z

1 VZH170 CSHL227 Left Not Req.
2 CSHL169 CSHL169 CSHL169 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

 

 

120

 

A/C

1 CSHN184 CSHN184 CSHN250 Left 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

2 CSHN184 CSHN184 CSHN250 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

W/Z

1 VZH170 CSHL285 Left Not Req.
2 CSHL169 CSHL169 CSHL227 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

 

 

130

 

A/C

1 CSHN240 CSHN240 CSHN240 Left 33 X17311028520 RSR00242
2 CSHN240 CSHN240 CSHN240 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

W/Z

1 VZH170 CSHL346 Left Not Req.
2 CSHL227 CSHL227 CSHL227 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

 

 

150

 

A/C

1 CSHN250 CSHN250 CSHN250 Left 33 X17311028520 RSR00242
2 CSHN250 CSHN250 CSHN250 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

W/Z

1 VZH170 CSHL346 Left Not Req.
2 CSHL227 CSHL169 CSHL346 Right 31 26 X17311028510 /

X17311028540

RSR00241 /

RSR00244

 

 

 

 

 

 

 

T

 

 

 

090

 

A/C

1 CSHP237 CSHP237 Left Not Req.
2 CSHP237 CSHP237 Right Not Req.
 

W/Z

1 VZH170 CSHP178 Left Not Req.
2 CSHP178 CSHP178 CSHP178 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

 

 

105

 

A/C

1 CSHP178 CSHP178 CSHP178 Left 31 X17311028510 RSR00241
2 CSHP178 CSHP178 CSHP178 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

W/Z

1 VZH170 CSHP237 Left Not Req.
2 CSHP178 CSHP178 CSHP178 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

Digit 4 – Develop- ment sequence

Digit 5,6,7 –

Nominal Cooling capacity

Digit 28 – Efficiency, Capacity, and Drain Pan Option  

 

 

Circuit #

 

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

120

 

A/C

1 CSHP178 CSHP178 CSHP237 Left 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

2 CSHP178 CSHP178 CSHP237 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

W/Z

1 VZH170 CSHP297 Left Not Req.
2 CSHP178 CSHP178 CSHP237 Right 32 31 X17311028560 /

X17311028510

RSR00366 /

RSR00241

 

 

 

130

 

A/C

1 CSHP227 CSHP227 CSHP227 Left 33 X17311028520 RSR00242
2 CSHP227 CSHP227 CSHP227 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

W/Z

1 VZH170 CSHP346 Left Not Req.
2 CSHP227 CSHP227 CSHP227 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

 

 

150

 

A/C

1 CSHP237 CSHP237 CSHP237 Left 33 X17311028520 RSR00242
2 CSHP237 CSHP237 CSHP237 Right 33 33 X17311028520 /

X17311028520

RSR00242 /

RSR00242

 

W/Z

1 VZH170 CSHP346 Left Not Req.
2 CSHP237 CSHP178 CSHP346 Right 31 26 X17311028510 /

X17311028540

RSR00241 /

RSR00244

Note: IPAK 2 90 to 150 ton MCHE: no change in compressors digit 10 design sequence P.

Table 3. IPAK 1 — suction restrictor size and location

 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

Digit 26 – Effiicency Options

 

 

 

Circuit #

 

 

Compressor Position

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

*20

0 1 ZP154 ZPS104 Not Req.
H 1 ZP154 ZPS104 Not Req.
V 1 VZH088 CSHD110 Not Req.
 

 

*25

0 1 CSHD075 CSHD110 CSHD110 15 X17311040600 RSR00355
H 1 ZP182 ZPS122 Not Req.
V 1 VZH088 CSHD125 Not Req.
 

 

*30

0 1 CSHD075 CSHD120 CSHD120 19 X17311040590 RSR00354
H 1 CSHD075 CSHD120 CSHD120 19 X17311040590 RSR00354
V 1 VZH117 CSHD161 Not Req.
 

 

 

 

*40

 

0

1 CSHD092 CSHD110 25 X17311040510 RSR00235
2 CSHD110 CSHD110 Not Req.
 

H

1 CSHD092 CSHD092 Not Req.
2 CSHD092 CSHD110 25 X17311040510 RSR00235
 

V

1 VZH117 Not Req.
2 CSHD110 CSHD110 Not Req.
 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

Digit 26 – Effiicency Options

 

 

 

Circuit #

 

 

Compressor Position

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

*50

 

0

1 CSHD125 CSHD125 Not Req.
2 CSHD125 CSHD125 Not Req.
 

H

1 CSHD125 CSHD142 26 X17311040560 RSR00240
2 CSHD125 CSHD142 26 X17311040560 RSR00240
 

V

1 VZH170 Not Req.
2 CSHD142 CSHD142 Not Req.
 

 

 

 

*55

 

0

1 CSHD142 CSHD161 27 X17311040540 RSR00238
2 CSHD142 CSHD161 27 X17311040540 RSR00238
 

H

1 CSHD142 CSHD142 Not Req.
2 CSHD142 CSHD142 Not Req.
 

V

1 VZH170 Not Req.
2 CSHD142 CSHD161 27 X17311040540 RSR00238
 

 

 

 

*60

 

0

1 CSHD161 CSHD161 Not Req.
2 CSHD161 CSHD161 Not Req.
 

H

1 CSHD161 CSHD161 Not Req.
2 CSHD161 CSHD183 26 X17311040560 RSR00240
 

V

1 VZH170 Not Req.
2 CSHD161 CSHD183 26 X17311040560 RSR00240
 

 

 

 

*70

 

0

1 CSHD183 CSHD183 Not Req.
2 CSHN184 CSHN250 31 X17311028510 RSR00241
 

H

1 CSHD183 CSHD183 Not Req.
2 CSHD183 CSHD183 Not Req.
 

V

1 VZH170 Not Req.
2 CSHN184 CSHN250 31 X17311028510 RSR00241
 

 

 

 

*75

 

0

1 CSHN184 CSHN250 31 X17311028510 RSR00241
2 CSHN184 CSHN250 31 X17311028510 RSR00241
 

H

1 CSHN184 CSHN250 31 X17311028510 RSR00241
2 CSHN250 CSHN250 Not Req.
 

V

1 VZH170 CSHN184 Not Req.
2 CSHD183 CSHD183 Not Req.
 

*90

 

0/H

1 CSHN250 CSHN250 Not Req.
2 CSHN250 CSHN250 Not Req.
 

*11

 

0/H

1 CSHN250 CSHN315 31 X17311028510 RSR00241
2 CSHN250 CSHN315 31 X17311028510 RSR00241
 

*12

 

0/H

1 CSHN250 CSHN315 31 X17311028510 RSR00241
2 CSHN315 CSHN315 Not Req.
 

*13

 

0/H

1 CSHN315 CSHN315 Not Req.
2 CSHN315 CSHN374 31 X17311028510 RSR00241
 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

Digit 26 – Effiicency Options

 

 

 

Circuit #

 

 

Compressor Position

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

*20

0 1 YA154 YAS104 Not Req.
H 1 YA154 YAS104 Not Req.
V 1 VZH088 CSHE113 Not Req.
 

 

*25

0 1 CSHE071 CSHE113 CSHE113 19 X17311040590 RSR00354
H 1 YA182 YAS122 Not Req.
V 1 VZH088 CSHE132 Not Req.
 

 

*30

0 1 CSHE071 CSHE127 CSHE127 19 X17311040590 RSR00354
H 1 CSHE071 CSHE117 CSHE117 19 X17311040590 RSR00354
V 1 VZH117 CSHE152 Not Req.
 

 

 

 

*40

 

0

1 CSHE104 CSHE113 Not Req.
2 CSHE104 CSHE113 Not Req.
 

H

1 CSHE088 CSHE104 25 X17311040510 RSR00235
2 CSHE088 CSHE104 25 X17311040510 RSR00235
 

V

1 VZH117 Not Req.
2 CSHE113 CSHE113 Not Req.
 

 

 

 

*50

 

0

1 CSHE117 CSHE132 26 X17311040560 RSR00240
2 CSHE117 CSHE132 26 X17311040560 RSR00240
 

H

1 CSHE117 CSHE132 26 X17311040560 RSR00240
2 CSHE132 CSHE132 Not Req.
 

V

1 VZH170 Not Req.
2 CSHE132 CSHE132 Not Req.
 

 

 

 

*55

 

0

1 CSHE132 CSHE152 27 X17311040540 RSR00238
2 CSHE152 CSHE152 Not Req.
 

H

1 CSHE132 CSHE132 Not Req.
2 CSHE132 CSHE152 27 X17311040540 RSR00238
 

V

1 VZH170 Not Req.
2 CSHE152 CSHE152 Not Req.
 

 

 

 

*60

 

0

1 CSHE152 CSHE152 Not Req.
2 CSHE152 CSHE177 26 X17311040560 RSR00240
 

H

1 CSHE152 CSHE177 26 X17311040560 RSR00240
2 CSHE152 CSHE177 26 X17311040560 RSR00240
 

V

1 VZH170 Not Req.
2 CSHE152 CSHE177 26 X17311040560 RSR00240
 

 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

 

Digit 26 – Effiicency Options

 

 

 

Circuit #

 

 

Compressor Position

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

*70

 

0

1 CSHE177 CSHE177 Not Req.
2 CSHP178 CSHP237 31 X17311028510 RSR00241
 

H

1 CSHE177 CSHE177 Not Req.
2 CSHE177 CSHE177 Not Req.
 

V

1 VZH170 Not Req.
2 CSHP227 CSHP227 Not Req.
 

 

 

 

*75

 

0

1 CSHP178 CSHP237 31 X17311028510 RSR00241
2 CSHP178 CSHP237 31 X17311028510 RSR00241
 

H

1 CSHP178 CSHP237 31 X17311028510 RSR00241
2 CSHP237 CSHP237 Not Req.
 

V

1 VZH170 CSHP178 Not Req.
2 CSHE177 CSHE177 Not Req.
 

90

 

0/H

1 CSHP237 CSHP237 Not Req.
2 CSHP237 CSHP237 Not Req.
 

*11

 

0/H

1 CSHP237 CSHP297 31 X17311028510 RSR00241
2 CSHP237 CSHP297 31 X17311028510 RSR00241
 

*12

 

0/H

1 CSHP237 CSHP297 31 X17311028510 RSR00241
2 CSHP297 CSHP297 Not Req.
 

*13

 

0/H

1 CSHP297 CSHP346 31 X17311028510 RSR00241
2 CSHP297 CSHP346 31 X17311028510 RSR00241

Notes

  1. IPAK RT G high efficiency unit—indicated by G in digit 26 of model number.
  2. IPAK RTsizes 24, 29, 36, 48, 59, 73, 80, 89 are evaporative cooled condenser models.
  3. IPAK RT 20 to 75 ton MCHE digit 10 design Sequence E.
  4. IPAK RT 90 to 130 ton MCHE: no change in compressors digit 10 design sequence D.
  5. IPAK RT V eFlex™ variable speed unit – indicated by V in digit 26 of model number.

Table 4. Voyager 3 — suction restrictor size and location

 

 

Digit 7- Major development sequence

 

 

Digit 29 – Efficiency

 

Digit 4,5,6 – Nominal Cooling capacity

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm)

 

 

Trane Part Number

 

 

Mnemonic Part Number

 

CP1

 

CP2

 

CP3

 

CP1

 

CP2

 

CP3

 

 

 

 

 

 

 

C

 

 

 

0 / J

330 CSHD075 CSHD110 CSHD110 Left 15 X17311040600 RSR00355
360 CSHD075 CSHD120 CSHD120 Left 19 X17311040590 RSR00354
420 CSHD075 CSHD136 CSHD136 Left None
480 CSHD092 CSHD155 CSHD155 Left None
600 CSHD120 CSHD183 CSHD183 Left 22 X17311040580 RSR00353
 

 

 

K / L

330 CSHD075 CSHD110 CSHD110 Left 15 X17311040600 RSR00355
360 CSHD075 CSHD120 CSHD120 Left 19 X17311040590 RSR00354
420 CSHD089 CSHD136 CSHD136 Left None
480 CSHD092 CSHD155 CSHD155 Left None
600 CSHD120 CSHD183 CSHD183 Left 22 X17311040580 RSR00353
 

 

 

D

 

 

 

0 / J / K / L

330 CSHE071 CSHE113 CSHE113 Left 15 X17311040600 RSR00355
360 CSHE071 CSHE127 CSHE127 Left 19 X17311040590 RSR00354
420 CSHE088 CSHE132 CSHE132 Left None
480 CSHE097 CSHE152 CSHE152 Left 20 X17311040680 RSR00380
600 CSHE117 CSHE177 CSHE177 Left 22 X17311040580 RSR00353

Note: Voyager 3 MCHE: no change in compressors digit 10 design sequence F.

Table 5. RA — suction restrictor size and location

 

 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

 

CP1

 

CP2

 

CP3

 

CP1

 

CP2

 

CP3

 

 

 

 

 

 

 

J

C20 CSHD120 CSHD120 Right Not Req.
C25 CSHD125 CSHD161 Right 25 X17311040510 RSR00235
C30 CSHD183 CSHD183 Right Not Req.
C40 CSHD120 CSHD120 Right Not Req.
C50 CSHD142 CSHD161 Right 27 X17311040540 RSR00238
C60 CSHD175 CSHD175 Right Not Req.
C80 CSHN176 CSHN176 CSHN176 Left 31 X17311028510 RSR00241
D10 CSHN184 CSHN184 CSHN250 Left 33 33 X17311028520 RSR00242
D12 CSHN250 CSHN250 CSHN250 Left 33 X17311028520 RSR00242
 

 

 

K

C20 YA154 YAS104 Right Not Req.
C25 YA182 YAS122 Right Not Req.
C30 CSHE088 CSHE132 CSHE132 Right Not Req.
C40 CSHE117 CSHE132 Right 26 X17311040560 RSR00240
C50 CSHE132 CSHE145 Right 27 X17311040540 RSR00238
 

 

Digit 4 – Development sequence

 

Digit 5,6,7 – Nominal Cooling capacity

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

 

CP1

 

CP2

 

CP3

 

CP1

 

CP2

 

CP3

 

 

K

C60 CSHE177 CSHE177 Right Not Req.
C80 CSHP178 CSHP178 CSHP178 Left 31 X17311028510 RSR00241
D10 CSHP178 CSHP178 CSHP237 Left 33 33 X17311028520 RSR00242
D12 CSHP237 CSHP237 CSHP237 Left 33 X17311028520 RSR00242

Notes

  1. RAUJ split system 20 to 60 ton MCHE: no change in compressors digit 10 design sequence C.
  2. RAUJ split system 20 to 120 ton MCHE: no change in compressors digit 10 design sequence B.

Table 6. IPAK 3 — suction restrictor size and location

 

Digit 12 – Develop- ment sequence

 

Digit 3,4,5 – Nominal Cooling capacity

Digit 9 – Refrigera- tion System Perform- ance  

 

 

Circuit #

 

 

Compressor Position

 

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number

 

 

Mnemonic Part Number

CP1 CP2 CP3 CP1 CP2 CP3
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

020

1 1 CSHW058 CSHW089 CSHW089 Not Req.
2 1 CSHD125 CSHD142 26 X17311040560 RSR00240
3 1 VZH088 CSHD110 Not Req.
 

 

025

1 1 CSHD075 CSHD110 CSHD110 15 X17311040600 RSR00355
2 1 CSHD142 CSHD161 27 X17311040540 RSR00238
3 1 VZH088 CSHD125 Not Req.
 

 

030

1 1 CSHD075 CSHD120 CSHD120 19 X17311040590 RSR00354
2 1 CSHD161 CSHD183 26 X17311040560 RSR00240
3 1 VZH117 CSHD161 Not Req.
 

 

 

 

040

 

1

1 CSHD110 CSHD110 Not Req.
2 CSHD110 CSHD110 Not Req.
 

2

1 CSHD110 CSHD110 Not Req.
2 CSHD110 CSHD110 Not Req.
 

3

1 VZH117 Not Req.
2 CSHD110 CSHD110 Not Req.
 

 

 

 

050

 

1

1 CSHD125 CSHD142 26 X17311040560 RSR00240
2 CSHD125 CSHD142 26 X17311040560 RSR00240
 

2

1 CSHD125 CSHD125 Not Req.
2 CSHD125 CSHD125 Not Req.
 

3

1 VZH170 Not Req.
2 CSHD142 CSHD142 Not Req.
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

055

 

1

1 CSHD142 CSHD142 Not Req.
2 CSHD142 CSHD142 Not Req.
 

2

1 CSHD125 CSHD142 26 X17311040560 RSR00240
2 CSHD125 CSHD142 26 X17311040560 RSR00240
 

3

1 VZH170 Not Req.
2 CSHD142 CSHD142 Not Req.
 

 

 

 

060

 

1

1 CSHD161 CSHD183 26 X17311040560 RSR00240
2 CSHD161 CSHD183 26 X17311040560 RSR00240
 

2

1 CSHD161 CSHD161 Not Req.
2 CSHD161 CSHD161 Not Req.
 

3

1 VZH170 Not Req.
2 CSHD183 CSHD183 Not Req.
 

 

 

 

070

 

1

1 CSHD183 CSHD183 Not Req.
2 CSHD183 CSHD183 Not Req.
 

2

1 CSHD161 CSHD183 26 X17311040560 RSR00240
2 CSHD161 CSHD183 26 X17311040560 RSR00240
 

3

1 VZH170 Not Req.
2 CSHD183 CSHD183 Not Req.
 

 

 

 

075

 

1

1 CSHD183 CSHD183 Not Req.
2 CSHD183 CSHD183 Not Req.
 

2

1 CSHD183 CSHD183 Not Req.
2 CSHD183 CSHD183 Not Req.
 

3

1 VZH170 CSHN184 Not Req.
2 CSHD161 CSHD161 Not Req.
 

 

 

 

 

 

 

 

 

B

020 3 1 VZH088 CSHE113 Not Req.
 

025

2 1 CSHE071 CSHE113 CSHE113 19 X17311040590 RSR00354
3 1 VZH088 CSHE132 Not Req.
 

 

030

1 1 CSHE071 CSHE117 CSHE117 19 X17311040590 RSR00354
2 1 CSHE071 CSHE132 CSHE132 19 X17311040590 RSR00354
3 1 VZH117 CSHE152 Not Req.
 

 

 

 

040

 

1

1 CSHE104 CSHE113 Not Req.
2 CSHE104 CSHE113 Not Req.
 

2

1 CSHE104 CSHE113 Not Req.
2 CSHE104 CSHE113 Not Req.
 

3

1 VZH117 Not Req.
2 CSHE113 CSHE113 Not Req.
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

050

 

1

1 CSHE117 CSHE132 26 X17311040560 RSR00240
2 CSHE132 CSHE132 Not Req.
 

2

1 CSHE117 CSHE132 26 X17311040560 RSR00240
2 CSHE117 CSHE132 26 X17311040560 RSR00240
 

3

1 VZH170 Not Req.
2 CSHE132 CSHE132 Not Req.
 

 

 

 

055

 

1

1 CSHE132 CSHE145 Not Req.
2 CSHE132 CSHE145 Not Req.
 

2

1 CSHE132 CSHE132 Not Req.
2 CSHE132 CSHE132 Not Req.
 

3

1 VZH170 Not Req.
2 CSHE145 CSHE145 Not Req.
 

 

 

 

060

 

1

1 CSHE152 CSHE177 26 X17311040560 RSR00240
2 CSHE152 CSHE177 26 X17311040560 RSR00240
 

2

1 CSHE152 CSHE177 26 X17311040560 RSR00240
2 CSHE152 CSHE177 26 X17311040560 RSR00240
 

3

1 VZH170 Not Req.
2 CSHE177 CSHE177 Not Req.
 

 

 

 

070

 

1

1 CSHE177 CSHE177 Not Req.
2 CSHE177 CSHE177 Not Req.
 

2

1 CSHE177 CSHE177 Not Req.
2 CSHE177 CSHE177 Not Req.
 

3

1 VZH170 CSHP178 Not Req.
2 CSHE132 CSHE132 Not Req.
 

 

 

 

075

 

1

1 CSHE177 CSHE177 Not Req.
2 CSHE177 CSHE177 Not Req.
 

2

1 CSHE177 CSHE177 Not Req.
2 CSHE177 CSHE177 Not Req.
 

3

1 VZH170 CSHP178 Not Req.
2 CSHE177 CSHE177 Not Req.

Table 7. Legacy restrictor selection and location

 

Product Line

 

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number w/Bag and Label

 

 

 

Mnemonic #

 

Clarksville

 

Clarksville

 

Clarksville

 

Clarksville

 

Clarksville

 

Macon

IPAK 2 IPAK 1 Voyager 3 Odyssey RA CSC CP1 CP2 CP3 CP1 CP2 CP3
S*HL*40 CSHD092 CSHD110 right 25 X17311040510 RSR00235
S*HL*40/48 G CSHD110 CSHD110 right Not Req.
S*HL*20/24 G CSHD125 CSHD125 right Not Req.
TTA240 F CSHD120 CSHD120 left  

Not Req.

S*HL*20 RAUJC20 RAUJC40 CSHD120 CSHD120 right
S*RF*30 S*RF*35 CSHD120 CSHD120 center Not Req.
S*HL*25 CSHD125 CSHD142 right 26 X17311040560 RSR00240
S*HL*50 CSHD120 CSHD136 right 26 X17311040560 RSR00240
S*HL25/29 G RAUJC25 CSHD125 CSHD161 right 25 X17311040510 RSR00235
S*HL*50/59 G CSHD142 CSHD142 right Not Req.
TC/TE/YC 330 CSHD142 CSHD161 left 27 X17311040540 RSR00238
S*HL*60 RAUJC50 CSHD142 CSHD161 right 27 X17311040540 RSR00238
TC/TE/YC 360 CSHD161 CSHD161 left  

Not Req.

S*HL*30 S*HL*60/73 G CSHD161 CSHD161 right
TC/TE/YC 420 CSHD161 CSHD183 left 26 X17311040560 RSR00240
S*HL*30/36 G CSHD161 CSHD183 right 26 X17311040560 RSR00240
TC/TE/YC 600 CSHD155 CSHD183 left 25 X17311040510 RSR00235
S*RF*40 CSHD183 CSHD120 center 22.5 X17311040570 RSR00348
S*HL*70/80 RAUJC30 CSHD183 CSHD183 right Not Req.
S*RF*50 CSHD183 CSHD183 center Not Req.
 

Product Line

 

 

Compressor Position

 

 

Suct. Appr.

 

Restrictor Size (ID mm) and Location

 

 

Trane Part Number w/Bag and Label

 

 

 

Mnemonic #

 

Clarksville

 

Clarksville

 

Clarksville

 

Clarksville

 

Clarksville

 

Macon

IPAK 2 IPAK 1 Voyager 3 Odyssey RA CSC CP1 CP2 CP3 CP1 CP2 CP3
S*RF*60 CSHD183 CSHD183 center Not Req.
S*WF*85 CSHD183 CSHD183 center Not Req.
RAUJC60 CSHD175 CSHD175 right Not Req.
S*HL*75/89 G CSHN184 CSHN250 right 31 X17311028510 RSR00241
S*HL*75 CSHN176 CSHN240 right 31 X17311028510 RSR00241
S*HJ090 S*HJ100 SXHK*90 CSHN250 CSHN250 left  

Not Req.

S*HJ090 S*HJ100 SXHK*90 right
S*HJ105 S*HJ118 SXHK*11 SXHK*12 CSHN250 CSHN315 left 31 X17311028510 RSR00241
S*HJ105 S*HJ118 SXHK*11 SXHK*12 right 31 X17311028510 RSR00241
S*HJ120 S*HJ128 SXHK*13 CSHN315 CSHN315 left  

Not Req.

S*HJ120 S*HJ128 SXHK*13 right
S*HJ130 S*HJ140 CSHN315 CSHN374 left 31 X17311028510 RSR00241
S*HJ130 S*HJ140 right 31 X17311028510 RSR00241
S*HJ150 S*HJ162 CSHN374 CSHN374 left  

Not Req.

S*HJ150 S*HJ162 right
RAUJD80 CSHN176 CSHN176 CSHN176 left 31 X17311028510 RSR00241
RAUJD100 CSHN184 CSHN184 CSHN250 left 33 33 X17311028520 RSR00242
RAUJD120 CSHN250 CSHN250 CSHN250 left 33 X17311028520 RSR00242

Notes

  1. IPAK RT G high efficiency air cooled unit—digit G listed in Position 21–38 in model number.
  2. IPAK RTsizes 24, 29, 36, 48, 59, 73, 80, 89 are evaporative cooled condenser models

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

PART-SVN257B-EN 24 Feb 2025
Supersedes PART-SVN257A-EN (July 2023)

Frequently Asked Questions

  • Q: Who should install and service the equipment?
    A: Only qualified personnel should install and service the equipment to ensure safety and proper operation.
  • Q: What type of refrigerant does the unit use?
    A: The unit uses R-410A refrigerant, which operates at higher pressures than R-22. It is important to use only R-410A rated service equipment with these units.
  • Q: What precautions should be taken when working with the equipment?
    A: Always observe all safety precautions, wear proper PPE, follow proper field wiring and grounding requirements, and adhere to responsible refrigerant practices to avoid hazards and ensure safe operation.