Seri FDV maksimal
Pasokan Daya Tunggal
Kontrol Daya Akses (PTC)
Guide Instalasi
Pengontrol Daya Akses Maximal7FDV
Model kalebu:
Maksimal3FDV
- 12VDC @ 4.6A utawa 24VDC @ 5.2A.
- Nembelas (16) output sing dilindhungi PTC.
Maksimal5FDV
- 12VDC @ 8.6A.
- Nembelas (16) output sing dilindhungi PTC.
Maksimal7FDV
- 24VDC @ 9.2A.
- Nembelas (16) output sing dilindhungi PTC.
Pdt. SFDV031115
Perusahaan Instal: _______________
Jeneng Service Rep.: ________________
Alamat : ________________________________
Nomer Telpon: _______________________
Seri MaximalFDV Swaraview:
Altronix MaximalFDV Access Power / Kontroler nyebarake lan ngalih daya kanggo ngakses sistem kontrol lan aksesoris. Padha ngowahi 220VAC (makarya sawetara 198VAC - 256VAC), 50 / 60Hz input menyang nembelas (16) independen kontrol 12VDC utawa 24VDC PTC output dilindhungi. Output diaktifake dening sink kolektor mbukak utawa biasane mbukak (NO) input pemicu garing saka Sistem Kontrol Akses, Keypad, Tombol Push, REX PIR, lan sapiturute. Unit bakal ngarahake daya menyang macem-macem piranti hardware kontrol akses kalebu: Kunci Mag , Serangan Listrik, Pemegang Door Magnetik, lsp. Antarmuka FACP mbisakake Egress Darurat, Pemantauan Alarm, utawa bisa digunakake kanggo micu piranti tambahan liyane. Fitur pedhot weker geni bisa dipilih kanthi individu kanggo siji utawa kabeh saka nembelas (16) output.
Bagan Konfigurasi Seri MaximalFDV:
Unit iki cocok kanggo daya: sensor, piranti elektro-mekanik (contone, serangan lawang listrik).
Fitur Seri MaximalFDV:
Modul Kontrol Daya Akses ACM8CB:
- Nembelas (16) kanthi mandiri micu output sing dikontrol. Pilihan Output:
a) Nembelas (16) output daya saring Gagal-Aman.
b) Nembelas (16) output daya saring Gagal-Aman.
c) Sembarang kombinasi saka ndhuwur. - Nembelas (16) input pemicu Sistem Kontrol Akses. Pilihan pemicu input:
a) Nembelas (16) input pemicu garing biasane mbukak (NO).
b) Nembelas (16) input kolektor mbukak.
c) Sembarang kombinasi saka ndhuwur. - Nembelas (16) aux disaring sing ora diowahi. output daya (output dirating @ 2.5A).
- LED abang ing Papan ACM8CB nuduhake output individu micu (relay energized).
- Pedhot Alarm Kebakaran (latching utawa non-latching) bisa dipilih kanthi individu kanggo saben utawa kabeh saka nembelas (16) output.
Pilihan pemicu input Alarm Kebakaran:
a) Input pemicu garing biasane mbukak (NO) utawa biasane ditutup (NC).
b) Input pembalikan polaritas saka sirkuit sinyal FACP. - LED ijo ing papan ACM8CB nuduhake pedhot FACP dipicu.
- Relay output FACP nuduhake yen input FACP dipicu (bentuk kontak "C" dirating @ 1A/28VDC).
- Papan eFlow Power Supply / Charger nyedhiyakake daya umum kanggo papan Kontrol Daya Akses ACM8CB (kabel pabrik) lan kabeh piranti kontrol akses sing disambungake (kabel lapangan).
- Sekring utama papan ACM8CB dirating @ 10A. Output PTC dirating @ 2.5A.
Sumber Daya / Pengisi Daya eFlow:
- Input: 220VAC (rentang kerja 198VAC - 256VAC), 50/60Hz.
- Kanggo output voltage lan sumber saiki deleng Bagan Konfigurasi seri MaximalFDV, pg. 3.
- Output tambahan dirating @ 1A (unswitched).
- Overvoltage Proteksi.
- Pangisi daya internal kanggo batere asam timbal utawa gel sing ditutup.
- Pangisian daya maksimum saiki 1.54A.
- Ganti otomatis batere siyap nalika AC gagal.
Transfer menyang daya baterei siyaga langsung tanpa gangguan. - Diawasi Fire Alarm pedhot (latching utawa non-latching) 10K EOL resistor. Makaryakke ing pemicu biasane mbukak (NO) utawa biasane ditutup (NC).
- Pengawasan gagal AC (bentuk kontak "C").
- Baterei gagal lan pengawasan ngarsane (wujud "C" kontak).
- mateni daya kurang. Mateni terminal output DC yen baterei voltage mudhun ing ngisor 71-73% kanggo unit 12V lan 70-75% kanggo unit 24V (gumantung saka sumber daya). Ngalangi discharge baterei jero.
- Kanggo rating sekring deleng Bagan Konfigurasi Seri MaximalFDV, pg. 3.
- LED Daya AC Hijau nuduhake 220VAC saiki.
- Indikator LED input AC lan output DC.
- Short circuit lan pangayoman kakehan.
- Enclosure nampung nganti papat (4) baterei 12VDC / 12AH.
Ukuran kandang (H x W x D): 26" x 19" x 6.25" (660.4mm x 482.6mm x 158.8mm).
Pandhuan Instalasi MaximalFDV:
Cara pengkabelan kudu sesuai karo Kode Listrik Nasional / NFPA 70 / ANSI, Kode Listrik Kanada, Part I, Part II lan kabeh kode lan panguwasa lokal sing duwe yurisdiksi. Produk dimaksudake mung kanggo panggunaan njero ruangan.
Diagnostik LED Papan Pasokan Daya | (kaca 6) |
Akses Power Controller LED Diagnostik | (kaca 6) |
Identifikasi Terminal Papan Pasokan Daya | (kaca 6) |
Identifikasi Terminal Kontrol Daya Akses | (kaca 7) |
Spesifikasi Baterai Stand-by Papan Pasokan Daya | (kaca 7) |
Power Supply Papan Output Voltage Setelan | (kaca 7) |
Diagram Aplikasi Khas Kontrol Daya Akses | (kaca 8) |
FACP/Diagram Pancing Sumber Daya Opsional | (kaca 11) |
- Pasang unit ing lokasi sing dikarepake. Tandhani lan predrill bolongan ing tembok kanggo baris munggah karo telung keyholes ndhuwur ing pager. Pasang telung fasteners ndhuwur lan ngawut-awut ing tembok karo kepala meneng protruding. Selehake keyholes ndhuwur pager liwat telung ngawut-awut ndhuwur, tingkat lan aman. Tandhani posisi telung bolongan ngisor. Copot pager. Pengeboran bolongan ngisor lan pasang telung fasteners. Selehake bolongan tombol ndhuwur pager liwat telung sekrup ndhuwur. Pasang telung ngawut-awut ngisor lan priksa manawa kanggo ngencengi kabeh ngawut-awut (Dimensi Enclosure, pg. 12).
- Sambungake daya AC unswitched (220VAC 50/60Hz) kanggo terminal ditandhani [L, N] (Fig. 3, pg. 9). Aja nggunakake terminal sing ditandhani [G]. Gunakake 14 AWG utawa luwih gedhe kanggo kabeh sambungan daya. Kabel lemah sing aman timbal menyang lug lemah.
Supaya kabel daya winates kapisah saka non daya winates wiring.
Jarak minimal 0.25" kudu diwenehake.
AWAS: Aja ndemek bagean logam sing katon. Mateni daya sirkuit cabang sadurunge nginstal utawa nglayani peralatan. Ora ana bagean sing bisa digunakake pangguna ing njero. Rujuk instalasi lan servis menyang personel layanan sing mumpuni. - Pilih output DC sing dikarepake voltage kanthi nyetel SW1 menyang posisi cocok ing sumber daya Maximal3FDV (Fig. 1a, pg. 7). Sumber daya Maximal5FDV disetel pabrik ing 12VDC lan sumber daya Maximal7FDV disetel pabrik ing 24VDC.
- Ukur output voltage saka unit sadurunge nyambungake piranti kanggo mesthekake operasi sing bener. Vol ora cocog utawa dhuwurtage bakal ngrusak piranti kasebut.
- Pilihan output (Gbr. 2, pg. 8):
Unit kasebut bakal nyedhiyakake enem belas (16) output daya sing diuripake, nembelas (16) output "C" sing garing, utawa kombinasi apa wae saka output daya sing diuripake lan output "C".
(a) Output Daya Ngalih sing Gagal Aman:
Kanggo operasi Gagal-Aman, sambungake input positif (+) saka piranti kontrol akses menyang terminal sing ditandhani [NC]. Sambungake input negatif (-) piranti kontrol akses menyang terminal sing ditandhani [COM].
(b) Output Daya Saklar Aman-Gagal:
Kanggo operasi Fail-Secure sambungake input positif (+) saka piranti kontrol akses menyang terminal sing ditandhani [NO]. Sambungake input negatif (-) piranti kontrol akses menyang terminal sing ditandhani [COM]. - Output Daya Tambahan ACM8CB (ora ngalih):
Sambungake piranti kontrol akses sing mbutuhake daya konstan menyang terminal sing ditandhani [C] positif (+) lan [COM] negatif (-). Output bisa digunakake kanggo nyedhiyani daya kanggo maca kertu, keypads, etc.
Output tambahan eFlow (ora ngalih):
Kanggo sambungan piranti tambahan, output iki ora bakal kena pengaruh Low Power Disconnect utawa Fire Alarm Interface. Sambungake piranti menyang terminal sing ditandhani [+ AUX –] (Gbr. 3, pg. 9). - Pilihan pemicu input (Gbr. 2, pg. 8):
(a) Biasane mbukak pemicu input [NO]:
Input 1-8 diaktifake kanthi input sink kolektor sing biasane mbukak utawa mbukak. Sambungake output panel kontrol akses, keypad, tombol push, REX PIRs, lan sapiturute menyang terminal ditandhani [IN] lan [GND].
(b) Input Sink Kolektor Terbuka:
Sambungake panel kontrol akses mbukak kolektor sink positif (+) menyang terminal ditandhani [IN] lan negatif (-) kanggo terminal ditandhani [GND]. - Pilihan Antarmuka Alarm Kebakaran ACM8CB (Gambar 5-9, pg. 11):
Pemicu input [NC] utawa biasane mbukak [NO] saka panel kontrol weker geni utawa input pembalikan polaritas saka sirkuit sinyal FACP bakal mengaruhi output sing dipilih.
Kanggo ngaktifake FACP Disconnect kanggo output, mateni saklar sing cocog [SW1-SW8] ing saben papan ACM8CB. Kanggo mateni FACP pedhot kanggo output, nguripake saklar sing cocog (e) [SW1-SW8] ing saben Papan ACM8CB.
(a) Biasane mbukak input [NO]:
Kanggo non-latching hook-up deleng Fig. 6, pg. 11. Kanggo latching hook-up deleng Fig. 7, pg. 11.
(b) Input [NC] Biasane Ditutup:
Kanggo non-latching hook-up deleng Fig. 8, pg. 11. Kanggo latching hook-up deleng Fig. 9, pg. 11.
(c) Pemicu input Sirkuit Sinyal FACP:
Sambungake positif (+) lan negatif (-) saka output sirkuit sinyal FACP menyang terminal sing ditandhani [+ INP –]. Sambungake FACP EOL menyang terminal sing ditandhani [+ RET –] (polaritas dirujuk ing kondisi weker). Jumper dumunung ing jejere TRG LED kudu Cut (Fig. 5, pg. 11). - Output "C" formulir garing FACP (Gbr. 2b, pg. 8):
Kontak formulir "C" FACP bisa digunakake kanggo micu piranti pelapor utawa sinyal.
Kontak kasebut ngalih marang pemicu input weker geni menyang papan ACM8CB. - Sambungan Baterei Stand-by (Gbr. 3, pg. 9):
Kanggo aplikasi Kontrol Akses, baterei opsional. Nalika baterei ora digunakake, mundhut saka AC bakal kasil mundhut saka output voltage. Nalika nggunakake baterei stand-by dikarepake, padha kudu asam timbal utawa jinis gel. Sambungake baterei menyang terminal sing ditandhani [– BAT +] (Gbr. 3, pg. 9). Gunakake rong (2) baterei 12VDC disambungake ing seri kanggo operasi 24VDC (baterei ndadékaké klebu). Gunakake baterei - baterei Casil CL1270 (12V / 7AH), CL12120 (12V / 12AH), CL12400 (12V / 40AH), CL12650 (12V / 65AH) utawa baterei BAZR2 lan BAZR8 sing diakoni UL kanthi rating sing cocog. - Output Pengawasan Baterei lan AC (Gbr. 3, pg. 9):
Sampeyan kudu nyambungake piranti laporan masalah pengawasan menyang output sing ditandhani [AC Fail, BAT Fail] output relay pengawas sing ditandhani [NC, C, NO] menyang piranti notifikasi visual sing cocog.
Gunakake 22 AWG nganti 18 AWG kanggo laporan AC Gagal & Kurang/Ora Ana Baterei. - Kanggo tundha laporan AC sajrone 2 jam, setel switch DIP [Tundha AC] menyang posisi OFF (Gambar 3, pg. 9).
Kanggo tundha laporan AC kanggo 1 min., Setel ngalih DIP [Tundha AC] menyang posisi ON (Fig. 3, pg. 9). - Pedhot Alarm Kebakaran (Gbr. 3, pg. 9):
Kanggo ngaktifake Fire Alarm Disconnect, atur switch DIP [Shutdown] menyang posisi ON.
Kanggo mateni Alarm Kebakaran Pedhot setel saklar DIP [Shutdown] menyang posisi OFF. - Pemasangan tamper switch (Gbr. 3b, pg. 9):
Gunung UL Listed tampngalih er (Altronix Model TS112 utawa padha) ing ndhuwur pager. Geser tamper ngalih krenjang menyang pojok pager kira-kira 2 "saka sisih tengen (Fig. 3b, pg. 9).
Nyambung tampngalih kabel menyang input Panel Kontrol Akses utawa piranti laporan UL Listed sing cocog. Kanggo ngaktifake sinyal weker, bukak lawang pager. - Input sumber daya akeh (Gambar 2, pg. 8):
Nalika nggunakake sumber daya external tambahan, jumper J1 lan J2 dumunung ing Papan ACM8 cocog kudu Cut (Fig. 2c, 2d, pg. 8). Sambungake sumber daya kontrol akses eksternal menyang terminal sing ditandhani [– Control +] (Terminal iki sejajar karo terminal [– Power +]). Nalika nggunakake sumber daya DC, polaritas kudu diamati. Nalika nggunakake sumber daya AC, polaritas ora perlu diamati.
(Fig. 2d, pg. 8) Kabeh sambungan wiring lapangan kudu digawe nggunakake cocok gauge CM utawa FPL jacketed kabel utawa sulih padha (Fig. 4a, pg. 10).
Pangopènan:
Pangopènan: Unit kudu dites paling ora sepisan taun kanggo operasi sing tepat kaya ing ngisor iki:
Pengawasan FACP: Kanggo mesthekake sambungan sing tepat lan operasi saka hookup pedhot Fire Alarm, tindakake prosedur sing cocog ing ngisor iki: Biasane Open Input: Nempatake cendhak antarane terminal ditandhani [T] lan [+ INP] bakal micu Fire Alarm Disconnect. Copot singkat kanggo ngreset.
Input Biasane Ditutup: Mbusak kabel saka terminal sing ditandhani [INP –] bakal micu Pedhot Alarm Kebakaran. Ganti kabel menyang terminal sing ditandhani [INP –] kanggo ngreset.
Input Sirkuit Sinyal FACP: Sampeyan kudu micu Sistem Alarm Kebakaran. Ing kabeh skenario ndhuwur bakal TRG LED ijo saka ACM8s madhangi. Kabeh output sing dipilih kanggo Fire Alarm Disconnect bakal ngaktifake ngeculake piranti ngunci.
Cathetan: Kabeh output [OUT 1 – OUT 8] kudu ing kondisi normal (de-energized) sadurunge testing. Nalika unit dikonfigurasi kanggo Biasane Bukak (Fig. 7, pg. 11) utawa Biasane Ditutup (Fig. 9, pg. 11) operasi latching perlu kanggo ngreset Fire Alarm Disconnect kanthi ngaktifake ngalih reset Biasane Ditutup.
Output Voltage Test: Ing kondisi mbukak normal, DC output voltage kudu dipriksa kanggo vol sing tepattage level (ndeleng Bagan Konfigurasi seri MaximalFDV, pg. 3).
Test baterei: Ing kahanan mbukak normal priksa manawa baterei wis kebak, mriksa tartamtu voltage ing terminal baterei lan ing terminal Papan ditandhani [+ BAT –] kanggo mesthekake yen ana break ing kabel sambungan baterei.
Cathetan: Saiki pangisian daya maksimal yaiku 1.54A. Umur baterei sing dikarepake yaiku 5 taun; Nanging, dianjurake kanggo ngganti baterei ing 4 taun utawa kurang yen perlu.
Diagnostik LED Papan Pasokan Daya:
Abang (DC) | Ijo (AC/AC1) | Status Pasokan Daya |
ON | ON | Kondisi operasi normal. |
ON | OFF | Mundhut AC. Daya panyedhiya baterei stand-by. |
OFF | ON | Ora ana output DC. |
OFF | OFF | Mundhut AC. Baterei kosong utawa ora ana stand-by. Ora ana output DC. |
Abang (Kelawar) | Status baterei |
ON | Kondisi operasi normal. |
OFF | Baterei gagal / baterei sithik. |
Diagnostik LED Kontrol Daya Akses:
LED | ON | OFF |
LED 1- LED 8 (Abang) | Output relay (s) energized. | Output relay (s) de-energized. |
Trg (Ijo) | Input FACP dipicu (kondisi weker). | FACP normal (kondisi non-alarm). |
Identifikasi Terminal Papan Sumber Daya:
Katrangan Terminal | Fungsi/Deskripsi |
L, N | Sambungake 220VAC 50/60Hz menyang terminal iki: L kanggo panas, N kanggo netral. Aja nggunakake terminal sing ditandhani [G] |
+ DC - | Pabrik disambungake menyang papan ACM8. |
Pemicu EOL Diawasi |
Fire Alarm Interface micu input saka singkat utawa FACP. Input pemicu bisa normal mbukak, biasane ditutup saka sirkuit output FACP (Fig. 3, pg. 9). |
Ora, GND RESET | FACP antarmuka latching utawa non-latching (Fig. 3, pg. 9). |
+ AUX - | Output tambahan dirating 0 1A (unswitched) (Fig. 3, pg. 9). |
AC GAGAL NC, C, NO |
Nuduhake mundhut daya AC, contone, nyambung menyang piranti sing bisa dirungokake utawa panel weker. Relay biasane diuripake nalika daya AC ana. Rating kontak 1A 0 30VDC (Fig. 3, pg. 9). |
BAT GAGAL NC, C, NO |
Nuduhake kahanan baterei sithik, contone, nyambung menyang panel weker. Relay biasane energi nalika daya DC saiki. Rating kontak 1A 0 30VDC. Baterei sing dicopot dilaporake sajrone 5 menit. Sambungan maneh baterei dilaporake sajrone 1 menit (Fig. 3, pg. 9). |
+ BAT— | Sambungan baterei stand-by. Pangisian daya maksimum saiki 1.54A (Fig. 3, pg. 9). |
Identifikasi Terminal Kontrol Daya Akses:
Katrangan Terminal | Fungsi/Deskripsi |
- Daya + | 12VDC utawa 24VDC saka sumber daya / pangisi daya (pabrik disambungake). Terminal iki padha karo terminal [- Control +]. |
- Kontrol + | Terminal iki sejajar karo terminal [- Power +]. Terminal kasebut bisa disambungake menyang sumber daya kontrol akses eksternal kanggo nyedhiyakake daya operasi terisolasi kanggo piranti. Jumper J1 lan J2 kudu dibusak. |
INPUT TRIGGER 1 - INPUT 8 IN, GND |
Saka input pemicu sink kolektor sing biasane mbukak lan / utawa mbukak (panyuwunan kanggo metu tombol, metu PIRs, etc.) |
OUTPUT 1- OUTPUT 8 NC, C, NO, COM |
Output kontrol pemicu 12VDC nganti 24VDC dirating ing 2.5A. Maximal3FDV - 10.0-13.2VDC 0 4.6A utawa 20.19-26.4VDC 0 5.2A. Maksimal5FDV - 10.03-13.2VDC 0 8.6A. Maksimal7FDV - 20.17-26.4VDC 0 9.2A. Gagal-Aman [NC positif (+) & COM Negatif (-)], Gagal-Aman [NO positif (+) & COM Negatif (—)], Output tambahan [C positif (+) & COM Negatif (—)]. Nalika nggunakake sumber daya AC polaritas ora perlu diamati. Kontak sing ditampilake ing negara sing ora dipicu. |
ANTARA FACP T, + INPUT - |
Fire Alarm Interface micu input saka FACP. Input pemicu bisa biasane mbukak, biasane ditutup saka output sirkuit signaling FACP (Fig. 5-9, pg. 11). |
ANTARA FACP NC, C, NO |
Kontak relay Formulir "C" dirating @ 1A 28VDC kanggo laporan weker. |
Spesifikasi Baterai Stand-by Papan Catu Daya:
Baterei | Maksimal3FDV | Maksimal5FDV | Maksimal7FDV |
7AH | 10 Menit/6A | 5 Menit/10A | 5 Menit/10A |
12AH | 30 Menit/6A | 30 Menit/10A | 30 Menit/10A |
40AH | Luwih saka 4 Jam / 6A | Luwih saka 2 Jam / 10A | Luwih saka 2 Jam / 10A |
65AH | Luwih saka 4 Jam / 6A | Luwih saka 4 Jam / 10A | Luwih saka 4 Jam / 10A |
Power Supply Papan Output Voltage Setelan:
Diagram Aplikasi Khas Pengontrol Daya Akses (kanggo saben ACM8CB):
Gambar 3 - Maximal3FDV, Maximal5FDV, lan Maximal7FDV
AWAS: Nalika papan sumber daya disetel kanggo 12VDC nggunakake mung siji (1) 12VDC stand-by baterei.
Tetep kabel winates daya kapisah saka non daya winates.
Gunakake spasi minimal 0.25″.
Baterei sing bisa diisi ulang 12AH minangka baterei paling gedhe sing bisa dipasang ing kandang iki. Enclosure baterei eksternal kudu digunakake yen nggunakake baterei 40AH utawa 65AH.
NEC Power-Limited Wiring Requirements:
Wiring sirkuit winates daya lan non-daya kudu tetep dipisahake ing kabinet. Kabeh kabel sirkuit winates daya kudu tetep paling sethithik 0.25" adoh saka kabel sirkuit sing ora winates. Salajengipun, kabeh kabel sirkuit winates daya lan kabel sirkuit non-daya kudu mlebu lan metu saka kabinet liwat saluran sing beda.
Salah sijine mantanample iki kapacak ing ngisor iki. Aplikasi khusus sampeyan mbutuhake knockout saluran sing beda kanggo digunakake. Sembarang knockout saluran bisa digunakake. Kanggo aplikasi daya-winates nggunakake conduit iku opsional. Kabeh sambungan kabel lapangan kudu digawe nggunakake ukuran cocok CM utawa kabel jaket FPL (utawa sulih padha).
Enclosure baterei UL Listed opsional kudu dipasang ing jejere sumber daya liwat metode kabel Kelas 1.
Kanggo instalasi Canadian nggunakake wiring shielded kanggo kabeh sambungan.
Cathetan: Deleng gambar nangani kabel ing ngisor iki kanggo cara sing bener kanggo nginstal kabel jaket CM utawa FPL (Fig. 4a).
FACP Hook-Up Diagram:
Fig. 5 Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker): | Fig. 6 Biasane Dibukak: Input pemicu FACP Non-Latching: |
![]() |
![]() |
Fig. 7 Biasane Bukak FACP Latching input pemicu kanthi ngreset (Output iki durung dievaluasi dening UL): | Fig. 8 Biasane Ditutup: Input pemicu FACP Non-Latching: |
![]() |
![]() |
Fig. 9 Biasane Ditutup: Nempelake input pemicu FACP kanthi reset (Output iki durung dievaluasi dening UL): | ![]() |
Ukuran Enclosure (H x W x D kira-kira):
26" x 19" x 6.25" (660.4mm x 482.6mm x 158.8mm)
Altronix ora tanggung jawab kanggo kesalahan tipografi.
140 58th Street, Brooklyn, New York 11220 USA | telpon: 718-567-8181 | fax: 718-567-9056
websitus: www.altronix.com | e-mail: info@altronix.com | Garansi seumur hidup
IIMaximal3FDV/5FDV/7FDV Series
H13U
Pandhuan Instalasi Maximal3FDV/5FDV/7FDV Series (PTC).
Dokumen / Sumber Daya
![]() |
Altronix Maximal7FDV Akses Power Controllers [pdf] Instruksi Manual Pengontrol Daya Akses Maximal7FDV, Pengontrol Daya Akses Maximal7FDV, Pengontrol Daya Akses, Pengontrol Daya, Pengontrol |