HT Instruments MACROEVTEST Professional Installation Safety Tester
ELECTRICAL SPECIFICATIONS
- Accuracy is indicated as ± (% readings + no. of digits*resolution) at 23°C ± 5°C, <80%RH
Voltage (RCD, LOOP, Phase sequence)
Range [V] | Resolution [V] | Accuracy |
15 ÷ 460 | 1 | ±(3.0% rdg + 2dgt) |
Frequency
Range [Hz] | Resolution [Hz] | Accuracy |
47.0 ÷ 63.6 | 0.1 | ±(0.1% rdg + 1dgt) |
Continuity test on protective and equalizing conductors
Range [WΩ] | Resolution [Ω] | Accuracy (*) |
0.01 ÷ 99.99 | 0.01 | ±(5.0%rdg + 3dgt) |
(*) calibrate the cables to null their resistance
- Test current: > 200mA DC for R≤5Ω (calibration included) ; Resolution for DC current :1mA
- Open-circuit voltage: 4V ≤ V0 ≤ 12V
Insulation resistance (DC voltage)
Test voltage[V] | Range [MΩ] | Resolution [MΩ] | Accuracy |
50 | 0.01 ÷ 9.99 | 0.01 | ±(2.0%rdg + 2dgt) |
10.0 ÷ 49.9 | 0.1 | ||
50.0 ÷ 99.9 | 0.1 | ±(5.0%rdg + 2dgt) | |
100 | 0.01 ÷ 9.99 | 0.01 | ±(2.0%rdg + 2dgt) |
10.0 ÷99.9 | 0.1 | ||
100.0 ÷ 199.9 | 0.1 | ±(5.0%rdg + 2dgt) | |
250 | 0.01 ÷ 9.99 | 0.01 | ±(2.0%rdg + 2dgt) |
10.0 ÷ 99.9 | 0.1 | ||
100 ÷ 499 | 1 | ±(5.0%rdg + 2dgt) | |
500 | 0.01 ÷ 9.99 | 0.01 | ±(2.0%rdg + 2dgt) |
10.0 ÷ 199.9 | 0.1 | ||
200 ÷ 499 | 1 | ||
500 ÷999 | 1 | ±(5.0%rdg + 2dgt) | |
1000 | 0.01 ÷ 9.99 | 0.01 | ±(2.0%rdg + 2dgt) |
10.0 ÷ 199.9 | 0.1 | ||
200 ÷ 999 | 1 | ||
1000 ÷
1999 | 1 | ±(5.0%rdg + 2dgt) |
- Open-circuit voltage: nominal test voltage –0% +10%
- Short circuit current: <6.0mA at 500V test voltage
- Nominal test current: >1mA if load= 1kΩ*Vnom (Vnom=50V, 100V, 250V, 500V, 1000V)
- Safety protection: the display shows an error message for input voltage >10V
Z Line (Line-Line, Line-Neutral, Line-PE)
Range [Ω] | Resolution [Ω] | Accuracy |
0.00 ¸ 199.9 mΩ (*) | 0.1 mΩ (*) | ±(5.0% rdg + 1mΩ) (*) |
200 ¸ 1999 mΩ (*) | 1 mΩ (*) | |
0.01 ¸ 9.99 Ω | 0.01 Ω | ±(5.0% rdg + 3dgt) |
10.0 ¸ 199.9 Ω | 0.1 Ω |
(*) By means of the IMP57 optional accessory
- Maximum test current: 5.81A (at 265V); 10.10A (at 457V)
- Test voltage ranges: 100÷265V (Line-Neutral) / 100÷460V (Line-Line); 50/60Hz ± 5%
- Protection type: MCB (B, C, D, K), Fuse (gG, aM)
- Insulation materials: PVC, Rubber butyl, EPR, XLPE
First fault current (IT systems)
Range (mA) | Resolution (mA) | Accuracy |
0.1 ¸ 0.9 | 0.1 | ±(5.0% rdg + 1dgt) |
1 ¸ 999 | 1 | ±(5.0% rdg + 3dgt) |
- Limit contact voltage (ULIM) : 25V, 50V
RCD test (Molded case type)
- RCD type: AC (
), A (
), B(
) – General (G), Selective (S) and Delayed (
)
- Rated tripping currents (I
N):: 6mA, 10mA, 30mA, 100mA, 300mA, 500mA, 650mA, 1000mA
- Line-PE, Line-N voltage: 100V÷ 265V RCD type AC and A, 190V÷ 265V RCD type B
- Frequency: 50/60Hz ± 5%
RCD tripping current (Molded case type – RCD General)
RCD type | I![]() | Range I![]() | Resolution [mA] | Accuracy I![]() |
AC, A, B | 6mA,10mA | (0.2 ÷1.1) I | £ 0.1 I | – 0%, +10%I![]() |
AC, A, B | 30mA ≤I![]() | – 0%, +5%I![]() | ||
AC, A | 500mA ≤I![]() |
RCD molded-type tripping time range [ms] (TT/TN system)
x 1/2 | x 1 | x 2 | x 5 | AUTO | ![]() | AUTO+![]() | ||||||||||||||||
\ | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | |
6mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | |||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | ||||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | |||||||||||||||
10mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | |||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | ||||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | |||||||||||||||
30mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | |||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | ||||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | |||||||||||||||
100mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ||||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | |||||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | |||||||||||||||
300mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ||||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | |||||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | |||||||||||||||
500mA 650mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ||||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 310 | |||||||||||||
B | ||||||||||||||||||||||
1000mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | |||||||||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | ||||||||||||||||
B |
Resolution: 1ms, Accuracy: ±(2.0%rdg + 2dgt)
RCD Molded type tripping time range [ms] (IT system)
x 1/2 | x 1 | x 2 | x 5 | AUTO | ![]() | AUTO+![]() | ||||||||||||||||
\ | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | |
6mA 10mA 30mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ![]() | |||||||
A | ||||||||||||||||||||||
B | ||||||||||||||||||||||
100mA 300mA 500mA 650mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | 50 | 150 | ![]() | ![]() | 310 | ||||||||
A | ||||||||||||||||||||||
B | ||||||||||||||||||||||
1000mA | AC | 999 | 999 | 999 | 999 | 999 | 999 | 160 | 210 | |||||||||||||
A | ||||||||||||||||||||||
B |
- Resolution: 1ms, Accuracy: ± (2.0%rdg + 2dgt)
Test on earth leakage delay tester RCDs (with RCDX10 optional accessory)
- RCD type: AC (
), A (
), B(
) – General (G), Selective (S) and Delayed ( )
- Rated tripping currents (I
N): 0.3A ÷ 10A
- Line-PE, Line-N voltage: 100V÷ 265V RCD type AC and A, 190V÷265V RCD type B
- Frequency: 50/60Hz ± 5%
Earth leakage delay tester RCDs tripping current (RCD General)
RCD type | IDN | Range IDN [mA] | Resolution [mA] | Accuracy IDN |
AC, A, B | 300mA ≤IDN £1A | (0.3 ÷ 1.1) IDN | ≤ 0.1I![]() | – 0%, +5%I![]() |
AC, A | 1.1A ≤IDN £10A |
Earth leakage delay tester RCDs trip out time range [ms] (TT/TN system)
x 1/2 | x 1 | x 2 | x 5 | AUTO | ![]() | AUTO+![]() | |||||||||||||
\ | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | G | S | ![]() | |
0.3A ÷ 1.0A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | |||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | ||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | 310 | ||||||||||||
1.1A ÷ 3.0A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | |||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | ||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | |||||||||||||
3.1A ÷ 6.5A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | |||||
A | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | ||||||
B | 999 | 999 | 999 | 999 | 999 | 999 | |||||||||||||
6.6A ÷ 10.0A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | ||||||||||
A | 999 | 999 | 999 | 999 | 999 | 999 | |||||||||||||
B |
Resolution: 1ms, Accuracy: ±(2.0%rdg + 2dgt)
Earth leakage delay tester RCDs trip out time range [ms] (IT system)
x 1/2 | x 1 | x 2 | x 5 | AUTO | |||||||||||||||
\ | G | S | G | S | G | S | G | S | G | S | G | S | |||||||
0.3A ÷ 3.0A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | |||||
A | |||||||||||||||||||
B | |||||||||||||||||||
3.1A ÷ 6.5A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | 50 | 150 | ![]() | ![]() | 310 | |||||
A | |||||||||||||||||||
B | |||||||||||||||||||
6.6A ÷ 10.0A | AC | 999 | 999 | 999 | 999 | 999 | 999 | 200 | 250 | ||||||||||
A | |||||||||||||||||||
B |
Resolution: 1ms, Accuracy: ±(2.0rdg + 2dgt)
NoTripTest – Non-trip earth loop impedance
- Test voltage: 100÷265V (Line-PE), 50/60Hz ± 5%
NoTripTest – Systems with Neutral wire
Range [Ω] | Resolution [Ω] | Accuracy (*) |
0.01 ÷ 9.99 | 0.01 | ±(5% reading + N/10) |
10.0 ÷ 199.9 | 0.1 | ±(5% reading + N) |
200 ÷ 1999 | 1 | ±(5% reading + 3N) |
- If I
N <30mA, test current = I
N/2 and N[Ω]=30/I
N Ω; if I
N ≥ 30mA, test current <15mA and N=1Ω
NoTripTest – Systems without Neutral wire
Range [Ω] | Resolution [Ω] | Accuracy (*) |
1 ÷ 1999 | 1 | -0%, +(5.0% lettura +N) |
Contact voltage (RCD and NoTripTest) | ||
Range [V] | Resolution [V] | Accuracy |
0 ÷ Utlim | 0.1 | -0%, +(5.0% rdg + 3V) |
Contact voltage (EARTH test – TT system) | ||
Range [V] | Resolution [V] | Accuracy |
0 ÷ 99.9 | 0.1 | -0%, +(5.0% rdg + 3V) |
Contact voltage (EARTH test – TN system) | ||
Range [V] | Resolution [V] | Accuracy |
0 ÷ 99.9 | 0.1 | -0%, +(5.0% rdg + 3V) |
100 ÷ 999 | 1 |
Ground resistance with 3-wire method | ||
Range [Ω] | Resolution [Ω] | Accuracy (*) |
0.01 ÷ 9.99 | 0.01 | ±(5.0% rdg + 3dgt) |
10.0 ÷ 99.9 | 0.1 | |
100 ÷ 999 | 1 | |
1.00k ÷ 49.99k | 0.01k |
- Test current: <10mA – 77.5Hz, Open-circuit voltage: < 20Vrms
- (*) Add 5% to the accuracy if the probe resistances (Rs or Rh) > 100 x Rmeas
Soil resistivity with 4-wire Wenner method | ||
Range [Ωm] | Resolution [Ωm] | Accuracy (*) |
0.06 ÷ 9.99 | 0.01 |
±(5.0% rdg + 3dgt) |
10.0 ÷ 99.9 | 0.1 | |
100 ÷ 999 | 1 | |
1.00k ÷ 9.99k | 0.01k | |
10.0k ÷ 99.9k | 0.1k | |
100k ÷ 999k | 1k | |
1.00M ÷ 3.14M | 0.01M |
(*) with distance d=10m, Distance “d” range: 1 ÷ 10m
Test current: <10mA – 77.5Hz, Open-circuit voltage: < 20Vrms
Phase sequence rotation with 1-wire method | |
Voltage range P-N, P-PE[V] | Frequency range |
100 ÷ 265 | 50Hz/60Hz ± 5% |
Measurement is only carried out by direct contact with metal live parts (not on insulation sheath)
Voltage drop on main power lines (DV%) | ||
Range (%) | Resolution (%) | Accuracy |
0 ÷ 100 | 0.1 | ±(10.0% rdg + 4dgt) |
Leakage current (by HT96U optional clamp transducer) | ||
Range [mA] | Resolution [mA] | Accuracy |
0.5 ÷ 999.9 | 0.1 | ±(5.0% rdg + 2dgt) |
Environmental parameters (AUX function) | |||
Parameter | Range | Resolution | Accuracy |
Temperature [°C] | -20°C ¸ 80°C | 0.1 °C |
±(2.0%rdg+2dgt) |
Temperature [°F] | -4°F ¸ 176°F | 0.1 °F | |
Relative humidity [%HR] | 0 ¸ 100%HR | 0.1% UR | |
DC output voltage | 0.1mV ¸ 1.0V | 0.1mV | |
Illuminance [Lux] | 0.001Lux ¸ 20.00 Lux (*) | 0.001 ¸ 0.02 Lux | |
0.1 Lux ¸ 2000 Lux (*) | 0.1 ¸ 2 Lux | ||
1 Lux ¸ 20 kLux (*) | 1 ¸ 20 Lux |
- (*) Accuracy of HT53 lux probe is according to Class AA
Measurement of main parameters and harmonics (PQA)
AC TRMS Voltage
Range [V] | Resolution [V] | Accuracy |
15.0 ÷ 459.9 | 0.1V | ±(1.0%rdg + 1dgt) |
- Allowed crest factor ≤ 1,5 ; Frequency: 42.5 ÷ 69.0 Hz
Frequency
Range [Hz] | Resolution [Hz] | Accuracy |
42.5 ÷ 69.0 | 0.01 | ±(2.0%rdg + 2dgt) |
- Allowed voltage: 15.0 ÷ 459.9V ; Allowed current: 5%FS clamp ÷ FS clamp
AC TRMS Current
FS clamp | Range [A] | Resolution [A] | Accuracy |
≤ 10A | 5% FS ÷ 9.99 | 0.01 | 1Ph: ±(1.0%rdg + 3 dgt) 3Ph: ±(2.0%rdg + 5 dgt) |
10A ≤ FS ≤ 200 | 5% FS ÷ 199.9 | 0.1 | |
200A ≤ FS ≤ 3000 | 5% FS ÷ 2999 | 1 |
- Range: 5 ÷ 999.9 mV; Values under 5mV are zeroed
- Allowed crest factor ≤ 3; Frequency: 42.5 ÷ 69.0 Hz
Active power (@ 230V in 1Ph systems, 400V in 3Ph systems, cosθ=1, f=50.0Hz)
FS clamp | Range [kW] | Resolution [kW] | Accuracy |
≤10A | 0.000 ÷ 9.999 | 0.001 | 1Ph: ±(2.0%rdg + 5 dgt) 3Ph: ±(2.5%rdg + 8 dgt) |
10A ≤ FS ≤ 200 | 0.00 ÷ 999.99 | 0.01 | |
200A ≤ FS ≤ 1000 | 0.0 ÷ 999.9 | 0.1 | |
1000A ≤ FS ≤ 3000 | 0 ÷ 9999 | 1 |
Reactive power (@ 230V in 1Ph systems, 400V in 3Ph systems, cosθ=0, f=50.0Hz)
FS clamp | Range [kVAr] | Resolution [kVAr] | Accuracy |
≤ 10A | 0.000 ÷ 9.999 | 0.001 | 1Ph: ±(2.0%rdg + 7 dgt) 3Ph: ±(3.0%rdg + 8 dgt) |
10A ≤ FS ≤ 200 | 0.00 ÷ 999.99 | 0.01 | |
200A ≤ FS ≤ 1000 | 0.0 ÷ 999.9 | 0.1 | |
1000A ≤ FS ≤ 3000 | 0 ÷ 9999 | 1 |
Power factor (@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range | Resolution | Accuracy |
0.70c ¸ 1.00 ¸ 0.70i | 0.01 | ±(4.0%rdg + 10dgt) if I £ 10%FS ±(2.0%rdg + 3dgt) if I > 10%FS |
cosθ (@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range | Resolution | Accuracy |
0.70c ÷ 1.00 ÷ 0.70i | 0.01 | ±(4.0%rdg + 10dgt) if I £ 10%FS ±(1.0%rdg + 7dgt) if I > 10%FS |
Voltage harmonics (@ 230V in 1Ph systems, 400V in 3Ph systems, f=50.0Hz)
Range [%] | Resolution [%] | Order | Accuracy |
0.1 ÷ 100.0 | 0.1 | 01 ÷ 25 | ±(5.0%rdg + 5dgt) |
- Frequency of fundamental: 42.5 ÷ 69.0 Hz, DC accuracy not declared
Current harmonics (f=50Hz)
Range [%] | Resolution [%] | Order | Accuracy |
0.1 ¸ 100.0 | 0.1 | 01 ÷ 9 | ±(5.0%rdg + 5dgt) |
10 ÷ 17 | ±(10.0%rdg + 5dgt) | ||
18 ÷ 25 | ±(15.0%rdg + 10dgt) |
GENERAL SPECIFICATIONS
DISPLAY AND MEMORY
- Features: Touch screen, color graphic LCD, 320x240mm
- Memory: 999 locations, 3 marker levels
- Communication: Optical-USB and built-in WiFi
POWER SUPPLY
- Batteries: 6 x 1.2V(rechargeable) type AA or 6 x 1.5V type AA
- Battery life: > 500 test for each funtions
- Auto Power OFF: after 5 min of idleness (disabled)
MECHANICAL FEATURES
- Dimensions (L x W x H): 225 x 165 x 75mm
- Weight (included batteries): 1.2kg
WORKING ENVIRONMENTAL CONDITIONS
- Reference temperature: 23°C ± 5°C
- Working temperature: 0°C ÷ 40°C
- Relative humidity: <80%RH
- Storage temperature: -10°C ÷ 60°C
- Storage humidity: <80%RH
TEST VERIFIES REFERENCE STANDARDS
- Continuity test with 200mA: IEC/EN61557-4
- Insulation resistance: IEC/EN61557-2
- Earth resistance: IEC/EN61557-5
- Fault loop impedance: IEC/EN61557-3
- RCD test: IEC/EN61557-6
- Phase sequence: IEC/EN61557-7
- Multifunction: IEC/EN61557-10
- Prospective short circuit current: EN60909-0
- Earth resistance on TN systems: EN61936-1 + EN50522
- Test on EVSE devices: IEC/EN61851-1, IEC/EN60364-7-722 (with EV-TEST100)
GENERAL REFERENCE STANDARDS
- Safety of measuring instruments: IEC/EN61010-1, IEC/EN61010-031, IEC/EN61010-2-032
- Product type standard: IEC/EN61557-1
- Technical documentation: IEC/EN61187
- Insulation: double insulation
- Pollution degree: 2
- Encapsulation: IP40
- Overvoltage category: CAT IV 300V∼ (to ground), max 415V between inputs
- Max height of use: 2000m
This instrument satisfies the requirements of Low Voltage Directive 2014/35/EU (LVD) and of EMC Directive 2014/35/EU This instrument satisfies the requirements of European Directive 2011/65/EU (RoHS) and 2012/19/EU (WEEE)
- Rivium 2e straat 12 2909 LG Capelle a/d IJssel
- T: 010-2 888 OOO
- F: 010-2 888 010
- verkoop@euro-index.nl
- www.euro-index.nl
Frequently Asked Questions
Q: What should I do if the tester displays an error message for input voltage?
A: If the input voltage exceeds 10V, disconnect the tester immediately to prevent damage and ensure safety.
Q: How do I select the appropriate test voltage range for insulation resistance testing?
A: Refer to the insulation materials used and choose the corresponding test voltage range as per the specifications provided.
Q: What are the recommended safety protections for conducting electrical tests?
A: Use MCB (B, C, D, K) or Fuse (gG, aM) as safety protection measures during testing to prevent electrical hazards.