Some functions of the basic DIM ILD Programmer can also be used with Tridonic sensors. A summary table can be found at other the end of this document under “Operating basic DIM ILD with other sensors

basic DIM ILD Programmer can be used to set parameters for the basic DIM ILD module. The following parameters are available:

Basic functions
Icon Designation Description
Icon ON Switch luminaires on
Icon OFF Increase current dimming leve
Icon Dim up Decrease current dimming level
Icon Dim down Change to automatic mode Dimming is started
Icon Automatic mode Store the brightness level currently measured by the sensor as target value for constant light
Icon Set current light level Store the brightness level currently measured by the sensor as target value for constant light control
Push to make switch functions

The abbreviation PTM stands for “push to make switch”.

Icon Designation Description
Icon PTM Set ON PTM Set ON Enable storage of target level via push to make switch input double clicking the push to make switch at the push to make switch input allows storing the brightness level currently measured by the sensor as target level for constant light control
Icon PTM Set OFF Disable storage of target level via push to make switch input storing the target level via push to make switch input is not  possible
Constant light control settings

NOTICE
The light levels indicated are based on a standard room situation and may  differ from the levels actually measured in the task area.

  • Try all three light levels and select the one most suitable!
Icon Designation Description
Icon Light level low Set ambient light control to a level of approx. 150 lx
Icon Light level middle Set ambient light control to a level of approx. 300 lx
Icon Light level high Set ambient light control to a level of approx. 500 lx
Offset settings

Use the Offset settings to specify and define in detail differences in brightness between the two channels.

Icon Designation Description
Icon Offset Value 0 % Set the difference in brightness between channel 2 and channel 1 to 0 %
Icon Offset Value -30 % Set the difference in brightness between channel 2 and channel 1 to -30 %
Icon Offset Value -50 % Set the difference in brightness between channel 2 and channel 1 to -50 %
Icon Offset Mode Converging Reduce the difference in brightness between channel 2 and channel 1 at increased or reduced dimming level. For example: at an offset value of -30 %, one channel’s dimming level is 30 % lower than the other’s (e.g
Icon Offset Mode Fixed Maintain the difference in brightness between channel 2 and channel 1 at increased or reduced For example: at an offset value of -30 %, one channel’s dimming level is 30 % lower than the other’s (e.g. channel 2: 40 %; channel 1: 70 %). When dimmed up, channel 2 will remain at a level of 70 % as soon as channel 1 has reached the dimming level of 100 %.
Bright Out settings

The Bright Out function defines how the ambient light control system will respond to additional illumination by sunlight or other light

Icon Designation Description
Icon Bright Out ON Switch on Bright Out: if the measured light level exceeds 150 % of the target level for more than 10 minutes, the light is switched off. If the measured light level falls below 100% of the target level, the PHASED light is switched back on again.

basicDIM ILD Programmer: Functions and Parameters | 12-2018 | en

Icon Bright Out OFF Switch off Bright Out: The light remains switched on at all times, irrespective of the light level measured.
Presence detection profile settings

The abbreviation P.I.R. stands for “passive infrared”. This function is used to control presence detection.

Icon Designation Description
Icon P.I.R. inactive Disable presence detection Run-on time is automatically set to “infinite”
Icon P.I.R. off only Presence detection responds only to absence light must be switched on manually (push to make switch, remote control) if no persons are detected, light is switched off automatically Run-on time is au
Icon P.I.R. active Enable presence detection light is switched on and off automatically based on the presence/absence of a person Run
Icon Time delay 1min 1 minute after the last presence was detected, light is dimmed to Sec. Level
Icon Time delay 10min n-on time to 10 minutes 10 minutes after the last presence was detected, light is dimmed to Sec. Level
Icon Time delay 20min 20 minutes after the last presence was detected, light is dimmed to Sec. Level

basicDIM ILD Programmer: Functions and Parameters | 12-2018 | en

Icon If vacant 0min. Set switch-off delay to 0 minutes light is switched off immediately after run-on time has expired
Icon If vacant 1min. Set switch-off delay to 1 minute light is switched off 1 minute after run-on time has expired
Icon If vacant 30min. Set switch-off delay to 30 minute light is switched off 30 minutes after run-on tim has
Icon If vacant continuous Set switch-off delay to “infinite” (neverOFF) light is not switched off after
Icon Sec. Level 1% Set the absence level to 1 % = dimming level to which the light is dimmed after the run-on time has expired
Icon Sec. Level 10% Set the absence level to 10 % = dimming level to which the light is dimmed after the run-on time has expired; applies only if “if vacant” 0min
Icon Sec. Level 30% Set the absence level to 30 % = dimming level to which the light is dimmed after the run-on time has expired; applies only if “if vacant” 0min
Sec. Level 50% Set the absence level to 50 % = dimming level to which the light is dimmed after the run-on time has expired; applies only if “if vacant” 0min

basicDIM ILD Programmer: Functions and Parameters | 12-2018 | en

Icon Designation Description
Icon DALI Select DALI Broadcast as interface operating mode
DSI Select DSI as interface operating mode
Icon Designation Description
Icon Power Up ON luminaire is switched on again after a mains break
Icon Power off luminaire is switched on again after a mains break

Operating basic DIM ILD with other sensors

Basic functions
Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19f DSI PTM
Icon ON Icon Icon Icon Icon
Icon OFF Icon Icon Icon Icon
Icon Dim up Icon Icon Icon Icon
Icon Dim down Icon Icon Icon Icon
Icon Automatic mode Icon Icon Icon Icon
Icon Set current light level Icon Icon Icon Icon
Push to make switch functions

The abbreviation PTM stands for “push to make switch”

Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19fe DSI PTM
Icon PTM Set ON Icon Icon
Icon PTM Set OFF Icon Icon
Constant light control settings
Icon Designation DALI MSensor 02 / basicDIM DGC SMART Sensor 5-10DPI 19fe DSI-SMART PTM
Icon Light level low Icon Icon
Light level middle Icon Icon
Light High   Icon   Icon
Offset settings
Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19fe DSI-SMART PTM
Icon Offset Value 0 % Icon
Icon Offset Value -30 % Icon
Icon Offset Value -50 %
Icon Offset Mode Converging
Icon Offset Mode Fixed  
Bright Out settings
Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19fe PTM
Icon Bright Out ON Icon
Icon Bright Out OFF Icon    
Presence detection profile settings
Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19fe PTM
Icon P.I.R. inactive Icon Icon
Icon P.I.R. off only Icon Icon
Icon P.I.R. active Icon Icon
Icon Time delay 1min. Icon Icon
Icon Time delay 10min. Icon Icon
Icon 20min Icon Icon
Icon If vacant 0min Icon Icon
Icon If vacant 1min.   Icon   Icon
Icon If vacant 30min.   Icon   Icon
Icon If vacant continuous Icon Icon
Icon Sec. Level 1% Icon Icon
Icon Sec. Level 10% Icon Icon
Icon Sec. Level 30% Icon Icon
Icon Sec. Level 50%   Icon   Icon
Interface operating mode settings
Icon Designation DALI MSensor 02 / MSensor 5DPI 14 basicDIM DGC SMART Sensor 5-10DPI 19fe PTM
Icon DALI Icon Icon
Icon DSI Icon Icon
Return of power settings
Icon Designation DALI MSensor 02 / MSensor basicDIM SMART Sensor 5-10DPI 19fe DSI-SMART PTM
Icon Power Up ON Icon Icon
Icon Power Up OFF Icon Icon