PPI OmniX BTC - logo Open Frame Dual Set Point Temperature Controller
Instruction Manual

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
INPUT / OUTPUT CONFIGURATION PARAMETERS

Parameters Settings (Default Value)
Input TypePPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon Refer Table 1 (Default : Type K)
Control Logic PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 1 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 3Reverse Direct (Default :Reverse )
Setpoint Low PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 2 Min. Range to Setpoint High for the selected Input type (Default : Min. Range for the ) Selected Input Type
Setpoint High PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 75 Setpoint Low to ax. Range M for the selected Input type (Default : Max. Range for the Selected input ) Selected Input Type
Offset For PV PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 4 -1999 to 9999 or -199.9 to 999.9 (Default : 0)
Digital Filter For PVPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 6 0.5 to 25.0 Seconds (in steps of 0.5 Seconds) (Default : 1.0)
Control Output TypePPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 5 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 8 Relay (Default) SSR
Output-2 Function SelectionPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 7 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 7 (Default) None Alarm Control Blower Soak Start Output
Output 2 Type PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 7 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 8 Relay (Default) SSR

CONTROL PARAMETERS 

Parameters Settings (Default Value)
Control Mode PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 12 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 16 (Default) On-Off PID
On-Off Hysteresis PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 13 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)
Compressor Time Delay PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 14 0 to 600 Sec. (in steps of 0.5 Sec.) (Default : 0)
Cycle Time PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 15 0.5 to 120.0 Seconds (in steps of 0.5 Seconds) (Default : 20.0 Sec)
Proportional Band PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 17 0.1 to 999.9 (Default : 10.0)
Integral Time PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 18 0 to 1000 Seconds (Default : 100 Sec)
Derivative Time PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 19 0 to 250 Seconds (Default : 25 Sec)

OUTPUT-2 FUNCTION PARAMETERS

OP2 Function : Alarm 

Parameters Settings (Default Value)
Alarm Type PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 20 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 24 Process Low Process High Deviation Band Window Band End of Soak (Default : Process Low)
Alarm Inhibit PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 21 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 25 Yes No (Default : Yes)
Alarm Logic PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 22 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 27 Normal Reverse (Default : Normal)
Alarm Timer PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 23 5 to 250 (Default : 10)

OP2 Function : Control

Parameters Settings (Default Value)
Hysteresis PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 76 1 to 999 or 0.1 to 99.9 (Default : 2 or 0.2)
Control Logic PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 77 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 27 Normal Reverse (Default : Normal)

OP2 Function : Blower 

Parameters Settings (Default Value)
Blower / Compressor Hysteresis 1 to 250 or 0.1 to 25.0 (Default : 2 or 0.2)
Blower / Compressor Time Delay PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 79 0 to 600 Sec. (in steps of 0.5 Sec.) (Default : 0)

SUPERVISORY PARAMETERS

Parameters Settings (Default Value)
Self-tune Command PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 28 Yes No (Default : No) PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 29
Overshoot Inhibit Enable / Disable PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 29 Disable Enable (Default : Disable) PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 29
Overshoot Inhibit Factor PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 29 (Default : 1.2) 1.0 to 2.0
Setpoint Editing Permission on Operator Page PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 33 Disable Enable (Default : Enable) PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 36
Soak Abort Command on Operator Page PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 34 Disable Enable (Default : Enable) PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 36
Soak Time Adjustment on Operator Page PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 35 Disable Enable (Default : Enable) PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 36

OPERATOR PARAMETERS

OP2 Function : Alarm

Parameters x Settings (Default Value)
Soak Start Command  PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 40 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 44 No Yes (Default : No)
Soak Abort Command PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 40 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 44 No Yes (Default : No)
Soak Time PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 41 00.05 to 60.00 M:S or 00.05 to 99.55 H:M or 1 to 999 Hours (Default : 3 or 0.3)
Alarm Setpoint  PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 42 Minimum to Maximum Range specified for the selected Input Type (Default : 0)
Parameters Settings (Default Value)
Alarm Deviation  PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 45 -1999 to 9999 or -199.9 to 999.9 (Default : 3 or 0.3)
Alarm Band PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 46 3 to 999 or 0.3 to 99.9 (Default : 3 or 0.3)

OP2 Function : Control 

Parameters Settings (Default Value)
Auxiliary Control Setpoint PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 47 (Min. Range – SP) to (Max. Range – SP) (Default : 0)

OP2 Function : Blower 

Parameters Settings (Default Value)
Blower Control Setpoint  PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 48 0.0 to 25.0 (Default : 0)

Control Setpoint (SP) Locking

Parameters Settings (Default Value)
 Setpoint Locking PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 48 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 29 Yes No (Default : No)

SOAK TIMER PARAMETERS 

Parameters Settings (Default Value)
Soak Timer Enable PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 51 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 56 No Yes (Default : No)
Time Units  PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 52 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 57 Manse Hours: Min Hours (Default : Min: Sec)
Soak Time PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 53 00.05 to 60:00 Manse 00.05 to 99:55 Hrs: Min 1 to 999 Hours (Default : 00.10 Manse)
Soak start Band PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 54 0 to 9999 or 0.0 to 999.9 (Default : 5 or 0.5)
Holdback Strategy PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 55 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 58 None Up Down Both (Default : None)
Parameters Settings (Default Value)
Hold Band PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 59 1 to 9999 or 0.1 to 999.9 (Default : 5 or 0.5)
Switch-off Control Output At Timer End PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 602 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 62 No Yes (Default : No)
Power-fail Recovery Method PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 61 PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 63 Continue (Re)Start Abort (Default : Continue)
Option What it means  Range  (Min. to Max.)    Resolution
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 64 Type J Thermocouple 0 to+960°C 1
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 65 Type K Thermocouple -200 to+1375°C 1
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 66 3-wire, RTD Pt100 -199 to+600°C 1
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 67 3-wire, RTD Pt100   –  -199.9 to+600.0°C 0.1

FRONT PANEL LAYOUT

Display Board
Small Display Version

0.39” height, 4 Digit, Upper Row
0.39” height, 4 Digit, Lower RowPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - Display BoardLarge Display Version
0.80” height, 4 Digit, Upper Row
0.56” height, 4 Digit, Lower RowPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - Display Board 1Control BoardPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - Control BoardLayoutPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - LayoutKeys Operation

Symbol Key                         Function
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 68 PAGE Press to enter or exit set-up mode.
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 69 DOWN Press to decrease the parameter value Pressing once decreases the value by one count; holding pressed speeds up the change.
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 70 UP Press to increase the parameter value Pressing once increases the value by one count; holding pressed speeds up the change.
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 71 ENTER Press to store the set parameter value and to scroll
to the next parameter on the PAGE.

PV Error Indications

Message PV Error Type
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 72 Over-range (PV above Max. Range)
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 73 Under-range (PV below Min. Range)
PPI OmniX BTC Open Frame Dual Set Point Temperature Controller - icon 74 Open (Thermocouple / RTD broken)

ELECTRICAL CONNECTIONSPPI OmniX BTC Open Frame Dual Set Point Temperature Controller - ELECTRICAL CONNECTIONS

PPI OmniX BTC - logo101, Diamond Industrial Estate, Namghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net

Documents / Resources

PPI OmniX BTC Open Frame Dual Set Point Temperature Controller [pdf] Instruction Manual
OmniX BTC, OmniX BTC Open Frame Dual Set Point Temperature Controller, Open Frame Dual Set Point Temperature Controller, Dual Set Point Temperature Controller, Temperature Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *