JOY SR 5DO | EC AO2DO | EC 3AO RS485 Modbus

Electronic Fancoil Thermostat (from Version 2.6.x)

Brand: Thermokon

Application

This product is intended for use as part of an automation solution for (functional) buildings. It transmits sensor data within a building over short distances unencrypted by radio to suitable receivers. No personal data or location data is transmitted. The product cannot communicate directly with the Internet and is not intended for applications that use the Internet to forward unprocessed sensor data. Automation stations that forward data via the Internet, e.g. to visualise the building status, must ensure that the data to be forwarded is encrypted as required by law.

JOY SR Fancoil 5DO RS485 Modbus (85..260 V ~)

Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial and residential buildings. It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves. The device combines a modern design with a 2.5" LCD and a touch-sensitive surface, 3 time program options each with 4 time periods options.

JOY SR Fancoil EC AO2DO RS485 Modbus (85..260 V ~)

Modern fan coil room thermostat to control fan coil units with EC fans. It is suitable for 2- and 4-pipe systems. It has 2 relays and 1 analogue output 0-10V (heating valve, cooling valve and EC fan). The device combines a modern design with a 2.5" LCD and a touch-sensitive surface, 3 time program options each with 4 time periods options.

JOY SR Fancoil EC 3AO RS485 Modbus (24 V ~/=)

Modern design, flush mounting fan coil room thermostat. Used for individual control of temperature in commercial, industrial and residential buildings. It is tailored for two-pipe and four-pipe fan coil units with two-wire electric valves or controlling a 6-way valve. The device combines a modern design with a 2.5" LCD and a touch-sensitive surface, 3 time program options each with 4 time periods options.

Product Testing and Certification

Declaration of conformity: The declaration of conformity of the products can be found on our website https://www.thermokon.de/direct/en-gb/categories/joy-fancoil

Security Advice – Caution

The installation and assembly of electrical equipment should only be performed by authorized personnel.

The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.

CAUTION! Risk of electric shock due to live components within the enclosure, especially devices with mains voltage supply (usually between 90..265 V).

Please comply with:

Application Notice

Software

Software description on https://www.thermokon.de/

MicroSD-Card

Bootloader

A MicroSD card bootloader for applications (update, upgrade) or configurations is integrated in the device. Active bootloader = ring illumination flashes (1 sec. cycle), display is not activated.

Firmware Update

Device Configuration

Note: The parameters for the display, the setpoints and the controller can only be changed via the configuration software.

Enocean Configuration

Save Enocean Configuration on MicroSD-Card

Note: EasySens receivers (SAB valve actuators or actuators, SRC/STC-x) still require the ID of the transmitter (Joy) via manually triggered teach-in telegram.

Update Function Advice

An update of the device software is only possible within the version main numbers.

Version compatibility: 3.0.2 ↔ 3.0.11, 2.6.6 ↔ 2.3.0, 2.x ↔ 3.x, 2.x ↔ 1.x

Technical Data

SpecificationValue
Measuring valuestemperature, humidity (optional)
Network technologyRS485 Modbus RTU, Fail-safe Biasing required
Radio technologyEnOcean (IEC 14543-3-10), transmission power <10 mW
Measuring range temp.0..+50 °C
Accuracy temperature±1 K (typ. at 21 °C)
Measuring range humidity (optional)0..100% rH non-condensing
Accuracy humidity (optional)±2% between 10..90% rH (typ. at 21 °C)
Control functionsetpoint adjustment 0..+50 °C, fan stages
DisplayLCD 2.5", 240x160 px, white backlighting
Functionsintegrated PI-controller, 2nd control loop: 2-point controller, MSG server for 2nd control loop via radio
EnclosurePC and glass, optional black or white
ProtectionIP30 according to EN 60529
Connection electricalTerminal 1..8 terminal block max. 1.5 mm² | Terminal 9..12 terminal block max. 1.0 mm²
Ambient condition0..+50 °C, max. 85% rH non-condensing
Weight195 g
Mountingflush mounted with standard EU box (Ø=60 mm)
Notesthere are 20 EnOcean transmit / receive channels available for various functions
Joy Fancoil 5DO
Output switch contact3x normally open contacts (fan speed), 240 V, load max. 3 A
Power supply85..260 V ~
Power consumptionmax. 3 VA (260 V ~)
InputsDI1 input for NTC 10 K or floating contact | DI2 digital input for non-floating contact
JOY Fancoil EC AO2DO
Output voltage1x 0..10 V, max. load 5 mA, EC FAN control
Output switch contact2x normally open contacts (heating/cooling), 240 V, load max. 500 mA
Power supply85..260 V ~
Power consumptionmax. 3 VA (260 V ~)
InputsDI1 input for NTC 10 K or floating contact | DI2 digital input for non-floating contact
JOY Fancoil 3AO
Ausgang Spannung3x 0..10 V, max. Last 5 mA, Ansteuerung EC Lüfter, Heizen & Kühlen oder Ansteuerung 6-Wege-Ventil (konfigurierbar via Software)
Spannungsversorgung24 V = (±10%) oder 24 V ~ (±10%) SELV
Leistungsaufnahmemax. 2.5 W (24 V =)
EingängeDI 1 Eingang für NTC10k oder potentialfreien Kontakt | Di 2 Eingang digital, für potentialfreien Kontakt
*Power supplyWhen several BUS devices are supplied by one 24 V AC voltage supply, it is to be ensured that all "positive" operating voltage input terminals (+) of the field devices are connected with each other and all "negative" operating voltage input terminals (-) (=reference potential) are connected together (in-phase connection of field devices). In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. The consequential short-circuit current flowing through this field my cause damage to it. Therefore, pay attention to correct wiring.

Mounting Advise Room Sensors

The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.

During Assembly:

Assembly not recommended in...

Mounting Advices JOY

Plasterboard boxes shall be covered by wall paper or paint to avoid that the plasterboard box's front rim will be partially visible underneath JOY. Maybe consider using white plasterboard boxes (i.e. Kaiser 9063-77)

Connection Plan

JOY Fancoil 5DO (85..260 V ~)

Diagram description: Shows terminals 9-12 for Modbus A/B and GND DI 1, and terminals 1-8 for fan speed, cooling, heating, digital input 2, L, and N. A simplified wiring diagram is shown.

TerminalFunction
1Fan Speed 3
2Fan Speed 2
3Fan Speed 1
4Cooling
5Heating
6Digitaler Input 2 (230 V)
7L
8N
9Digital Input 1 (or NTC10K)
10GND DI 1
11Modbus A
12Modbus B

JOY Fancoil EC AO2DO (85..260 V ~)

Diagram description: Shows terminals 9-12 for Modbus A/B and GND DI 1, and terminals 1-8 for EC Fan GND, EC Fan (0..10 V), Cooling, Heating, Digital Input 2, L, and N. A simplified wiring diagram is shown.

TerminalFunction
1EC Fan GND
2EC Fan (0..10 V)
3(Not specified in diagram, assumed unused or part of 0-10V output)
4Cooling
5Heating
6Digital Input 2 (230V)
7L
8N
9Digital Input 1 (or NTC10K)
10GND DI 1
11Modbus A
12Modbus B

JOY Fancoil EC 3AO (24 V ~/=)

Diagram description: Shows terminals 9-12 for Modbus A/B and GND DI 1, and terminals 1-8 for Digital Input 2, EC Fan (0..10 V), Cooling (0..10 V) or 6-way valve, Heating (0..10 V) or 6-way valve, GND DI 2, GND, 24 V = (±10%) or 24 V ~ (±10%), and GND. A simplified wiring diagram is shown.

TerminalFunction
1Digital Input 2
2EC Fan (0..10 V)
3Cooling (0..10 V) or 6-way valve
4Heating (0..10 V) or 6-way valve
5GND DI 2
6GND
724 V = (±10%) or 24 V ~ (±10%)
8GND
9Digital Input 1 (or NTC10K)
10GND DI 1
11Modbus A
12Modbus B

Note: Parallel connection of the potential-loaded inputs is not permitted! If the operating mode (change-over DI) of several devices is to be switched together by one contact, the potential-free 230V input must be used (DI2, only possible with the 230V version). It must be ensured that the same phase is used for jointly switched devices.

Function Description – Controller/Fan Stages

JOY Fancoil 5DO (85..260 V ~)

Controller: PI controller (PWM) & 2-point/3-point controller (configurable)

JOY Fancoil EC AO2DO (85..260 V ~)

Controller: PI controller (PWM) & 2-point/3-point controller (configurable)

JOY Fancoil EC 3AO (24 V ~/=)

Controller: PI controller (0..10 V)

Fan stages (all types)

In automatic mode the fan speed is linked to the controller. The assignment of the fan stage to the control (heating / cooling, only heating, only cooling) is freely selectable. To ensure that the fan motor starts reliably, a period of time can be configured in which the fan starts with maximal value. Using one or more time channels, the fan control have to be set per timechannel and per period. Via the touch surface the user has the option to override the settings of the device every time. When the next time channel starts, the fan speed is set to the configured value. The fan is set to automatic mode when the user changes the occupancy state (occupied/unoccupied).

Heating/ cooling with PI-controller (PWM) (only 5DO and EC AO2DO)

The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error, the P portion immediately changes the position value proportionally to the error variable, while the integral portion takes effect after a certain time. The resulting actuating variable is output as a pulse-width-modulated signal directly to the outputs.

Heating/ cooling with 2-point-/ 3-point-controller (only 5DO and EC AO2DO)

In the case of temperature control, the 2-point controller only knows the switching states heating ON and heating OFF. The 3-point controller also knows the switching state of cooling. Two - and three-point controller work with a hysteresis.

Heating/ cooling with PI-controller (0..10 V) (only EC 3AO)

The time response of the PI control loop depends on the control parameters xp for the proportional area and tn for the reset time of the integral range. In case of an error variable, the P portion immediately changes the position value proportionally to the error variable, while the integral portion takes effect after a certain time. The resulting manipulated variable is output as an analogue 0..10 V signal directly to the outputs.

EC Fan automatic mode with PI-controller (only EC 3AO and EC AO2DO)

(for EC AO2DO with two-point/three-point controller, the temperature range for controlling the 0..10 V EC fan is parameterised separately)

The 0..10 V (0..100%) control of the fan is proportional to the calculated manipulated variable of the PI controller.

i.E.: Calculated actuating variable 65% → Fan control with 6.5 V | Calculated actuating variable 22% → Fan control with 2.2 V

EC Fan manual with PI-controller (only EC 3AO and EC AO2DO)

Up to 5 steps (steps) can be set using the configuration software. The set number of steps is divided linearly to the manipulated variable of 0..100%.

i.E.: Max. steps (stages) = 5 | Stage 1 = 20% | Stage 2 = 40% | Stage 3 = 60% | Stage 4 = 80% | Stage 5 = 100%

Max. steps (stages) = 3 | Stage 1 = 33% | Stage 2 = 66% | Stage 3 = 100%

Display

Value Screen

Internal sensor values: ...

External sensor values (configurable): ...

(additional humidity value optionally configurable)

Header (value/ symbol display)

Time, weekday, date, ECO symbol (mode dependent). Alarm symbol (higher priority than ECO-Symbol).

Footer (symbol display)

Symbols for heating/cooling mode, occupancy, window contact, etc. The symbol "Timechannel active" is only shown when a time channel is active.

Symbols: Occupancy [?], Window contact/dew point [?], Fan stage [?], Timechannel active [?]

Function Description – Buttons

On the touch surface, there are adjustment options for setpoint and fan speed regulation. While pressing these buttons, the white ring-LED of the Power-button lights up for visual feedback.

Fan speed adjustment: "fan speed up" / "fan speed down"

Setpoint change: (setpoint range ± 3 °C, default, configurable).

Power button: for Standbymode, or Presence key*

*If the key is used as a presence key at the same time, the key must be pressed for at least 3s, in all other cases a short press is sufficient.

3 seconds without any interaction, the display returns back to main screen.

Standby mode: (not compatible with Keycard-switch function) In standby mode the display and all outputs are switched off (controller deactivated). The frost and heat protection monitoring remains active. The Modbus registers can still be read out (e.g. room temperature).

Navigation Parametermenu: (up, down, left, right)

Open submenu: (right)

Confirmation: In header left to leave the submenu

Diagnostics Menu

To access the diagnostics menu, select the header in the startscreen of the parameter menu, and press the ENTER key. Here you will find various information, such as device type, software version, state of the inputs and outputs and controller state (current manipulated variable).

Parameter Menu – Modbus Interface

The configuration menu is activated by simultaneously pressing the buttons "up" (A) and "down" (C) for at least 5 seconds. The menu is enabled during the first 60 minutes after switching on the supply voltage as long as the device is not actively involved in Modbus communication. As soon as the device receives a valid request addressed to the device from a DDC, access to the menu is blocked. Without valid communication, access is blocked after 60 minutes!

Modbus settings

SettingValue
Address32
Baudrate19200
ParityEven

Address (default: 32): Adjustable address (1-247)

Baud rate (default: 19200): 9600Bd | 19200Bd | 38400Bd | 57600Bd

Parity (default: even): Non | odd | even

Configuration

Configuration via uConfig | MicroSD-Card or Modbus

Configuration software: uConfig | Windows 10 is required to use the uConfig configuration software

The JOY room thermostat can be parameterised using the uConfig configuration software. An SD card is used to transfer the created configuration file to the device. For BUS devices, a live configuration can also be performed via the BUS interface.

The online installer for the configuration software can be found in our download center. The installer retrieves all necessary files and plug-ins from our web server. In this version an update function is integrated in the software.

Download Online-Installer

ParameterMenu

Access to Parametermenu: Press buttons for 3 seconds simultaneously

If no entry is made for 8 minutes, the parameter menu is left automatically.

Menu → Time Channels

Up to 3 time channels with 4 time periods each can be parameterized. The time channels are prioritized, channel 3 has the highest priority.

TimechannelTimechannels/Timer1Periods/Period 1
Timechannel 1Mo - FrStart: 06:00h, Fan: AUTO, Temp: 22.0°
ECO-Mode
Timechannel 2Start: 08:30h - 1 - 20.0°
Timechannel 3Start: 16:00h - A - 22.0°
Start: 22:30h - 0 - 22.0°ECO V

Time Channel

Time period within one week configuration - / + via button left / right. 4 periods.

Periods

Menu → Time/Date

In the Time/ Date menu the time, date and the display format can be configured.

MenuDatetime setting/TimeDatetime setting/DateDefault settings:
TimechannelHour: 13, Minute: 41, 12h/24h: 24h, Daylight saving: CETDay: 07, Month: 08, Year: 15, Presentation: T.M.J24h display format, Daylight savings settings (CET), Date presentation Day.Month.Year
Time/Date
Sensor settings
Common settings
EnOcean list
EnOcean configuration

Menu → Sensor Settings

Offset correction settings for internal and external sensor value. Value display of internal and external temperature sensors

MenuOffset int.Value int.Offset ext.Value ext.Unit
Sensor settings0.6 K22.1°C0.2 K22.1°CCelsius
Timechannel
Time/Date
Common settings
EnOcean list
EnOcean configuration

Unit - Setting the temperature unit in celsius / fahrenheit.

Menu → Common Settings

Common device settings:

Brightness: Configuration of the LCD brightness/ LED ring brightness during button operation/ usage.

Valve protection: A valve protection function actuates the heating and cooling valves regularly to prevent locking during non-usage times. The function is executed Fridays at 11:00 (heating valve) and 11:15 (cooling valve). The corresponding valve is triggered for 5 minutes, if not activated during the last 96 hours.

ECO deadband: The dead band can be adjusted (default 10.0 K)

Factory setting: By selecting "Factory setting", the room thermostat will be reset and restore the device to factory default settings.

Menu → EnOcean List

In this list, all channels with the taught-in sensors or actuators are displayed.

After selecting a device further information are displayed.

Menu → EnOcean Configuration

In this menu item, the radio channels can be configured and individual information can be called up.

Note: The access to the menu <EnOcean configuration> can be protected with a password via Modbus. The login remains unlocked in the EnOcean menu until 10 minutes after the last key press. Default password: 2030

More detailed information for the configuration of the EnOcean channels can be found in the specification.

There are 20 channels available that can be assigned different functions. A channel can be configured as a receive channel, as a send channel or as a message server (SAB communication). 6 channels can be configured with SAB valve actuator, one of these can be set with the bath function. For the SAB with the bath function, an additional setpoint offset can be set. If SAB valve actuators are learned in, the analogue outputs to the internal controller remain active and can also be used.

Functional Overview SAB

The profiles used are divided into functional groups:

Information about EasySens® (Radio) / airConfig General Usage

Basic information about EasySens® radio and about general usage of our airConfig software, please download from our website.

Overview of the Radio Telegrams

EEP: The structure of the data contained in the telegram can be found in the EEP (EnOcean equipment profile) list provided by the EnOcean Alliance.

Supported Profiles

Receiving profiles

EnOcean-EEPTypeDirectionDescriptionThermokon DevicesMax. QuantityLCD/Funktion s-gruppe
F6-02-01RPSRxEnOcean buttonDiverse1RPS
D5-00-011BSRxWindows contactsSRW01max.5SRW
F6-10-00RPSRxWindows handleSRG02SRG
A5-02-064BSRxTemperature 0-50°CSR65 VFG, SR65 TF, SR65 AKF, SR651VFG
A5-02-164BSRxTemperature 0-80°CVFGVFG
A5-02-054BSRxRoom Sensor (Temperature 0-40°C)SR04, LC-SR04, SR07, SR651EXT
A5-10-034BSRx(Room Operating Panel) Temperatur, Set PointSR07P, SR04P, SR06 2T/2T+WRF
A5-07-014BSRxRoom Sensor (Occupancy)SR-MDS Solar, SR-MOC Solar, SR-MOW Solarmax. 3OCC
A5-08-014BSRxRoom Sensor (Occupancy, Light, Temperature)SR-MDSOCC
F6-04-01RPSRxKeycardSR-KCS02, SR-KCS1KEY
A5-20-014BSRx/TxSABSAB+, SAB05max. 6SAB
A5-20-124BSRxSuperior Control Unit (Fan. Set Point, Controller, Energy Hold OFF/Dew point, Occup)1SUP

Transmitting profiles

EnOcean EEPTypeDirectionDescriptionMax. QuantityLCD
A5-10-02 (V2.1.1 +)4BSTxValid from Version 2.1.1 (up to 2.1.0: A5-10-01) Room operating panel (Fan,Temp, Sollwert, Occup)1WRF
A5-10-06 (V2.1.1 +)4BSTxValid from Version 2.1.1 (up to 2.1.0: A5-10-05) Room operating panel (Temp, Sollwert, Occup)
A5-11-024BSTxTemperature Controller (Fan, Set point, alarming, Controller state, Energy Hold OFF, Occup)1OUT
A5-20-014BSRx/TxSABmax. 5+1SAB

Inputs

Up to 2 inputs are configurable for functions such as windows contact, dew point, occupancy, change-over or external sensor option. The overview of possible combinations can be found in the software specification of the JOY.

Dimensions (mm)

Diagram description: The diagram shows the front and side views with key dimensions labeled. Front view shows a rectangular device with a circular display area and buttons. Key dimensions include height (134mm), width (100mm), depth (17mm), and mounting hole spacing (60mm, 78mm). Side view shows depth and mounting details.

Accessories (Optional)

Notes on Disposal

The crossed-out wheelie bin symbol [?️] indicates that the product or removable batteries must not be disposed of with household or commercial waste. Within the EU, you are legally obliged to dispose of the product separately and appropriately in accordance with the national laws of your country. Alternatively, please contact your supplier or Thermokon Sensortechnik GmbH. Further information can be found at: www.thermokon.com

PDF preview unavailable. Download the PDF instead.

JOY SR Fancoil Modbus Datasheet en Adobe PDF Library 25.1.97

Related Documents

Preview Thermokon JOY SR Fancoil Thermostat Datasheet
Technical datasheet for Thermokon JOY SR Fancoil thermostats, including models JOY SR 5DO, EC AO2DO, and EC 3AO with RS485 Modbus communication. Covers features, applications, technical specifications, installation, and configuration.
Preview Thermokon JOY Fancoil Modbus Datasheet: EC AO2DO, EC 3AO
Datasheet for Thermokon's JOY Fancoil Modbus series, including JOY 5DO, EC AO2DO, and EC 3AO models. Details technical specifications, application, mounting, functions, and connection plans for these fan coil room thermostats.
Preview Thermokon JOY Fancoil Modbus RS485 Data Sheet
Technical data sheet for Thermokon JOY Fancoil 5DO, EC AO2DO, and EC 3AO RS485 Modbus fan coil thermostats. Includes application, safety, installation, technical specifications, and function descriptions.
Preview Thermokon JOY HC AO2DO/HC 3AO RS485 Modbus Room Controller Datasheet
Technical datasheet for the Thermokon JOY HC AO2DO and JOY HC 3AO room controllers, featuring RS485 Modbus communication. Details technical specifications, application, safety instructions, installation, and configuration.
Preview Thermokon JOY Fancoil RS485 BACnet Data Sheet
Technical data sheet for Thermokon JOY Fancoil controllers with RS485 BACnet interface, including models 5DO, EC AO2DO, and EC 3AO. Details specifications, application, safety, installation, and configuration.
Preview Thermokon JOY HC AO2DO/HC 3AO RS485 BACnet Room Regulator Datasheet
Datasheet for Thermokon's JOY HC AO2DO and JOY HC 3AO room regulators with RS485 BACnet connectivity. Details technical specifications, application, mounting advice, functions, and connection plans.
Preview Thermokon JOY KNX Room Operating Unit Manual
Comprehensive manual for the Thermokon JOY KNX room operating unit, covering installation, configuration, functional descriptions, operating modes, and KNX specifications.
Preview Thermokon LCF02 QTouch AO5DO Fancoil-Regler Datenblatt
Umfassendes Datenblatt für den Thermokon LCF02 QTouch AO5DO Fancoil-Regler. Erfahren Sie mehr über Raumtemperaturregelung, Echtglas-Display, CO2-Sensorik und Modbus-Konnektivität für 2- und 4-Rohr-Systeme.