Lennox V36D012S6-5P VRF 360 Cassette
Submittal Data
General Information
- The system features comfort humidity control, utilizing an integral humidity sensor to optimize indoor unit coil temperature according to the dew point, maximizing energy savings while providing space dehumidification and occupant comfort.
- The indoor unit includes an integral condensate pump with a maximum 29" lift from the bottom of the unit, equipped with a check valve and float switch to disable the unit in case of condensate overflow.
- The indoor unit fascia panel has a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.
Construction
- Insulated, HIPS chassis and fascia panel certified to UL94 V0.
- Includes a knock-out for outside air capability (booster fan connection).
- All heat exchangers are mechanically bonded aluminum fin to copper tube.
Refrigerant System
- The system utilizes low-GWP R-32 refrigerant.
- Refrigerant flow is controlled by an electronic expansion valve at the indoor unit.
- The indoor unit includes an R32 alarm output plug for simple notification of R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Features three fan speed settings and an auto setting.
- Includes a washable filter as standard.
- The indoor unit has LED indicator lights and an infrared receiver.
- The indoor unit design prevents air louvers or blades from allowing full airflow without restriction.
- Air direction control is achieved by creating a low-pressure area near the air outlet, causing discharge air to change direction angle.
- Fixed or auto-swing air direction is possible with local and central controller options (10° – 60° angle).
- Independent air distribution control is possible with wireless or premium wired controllers (three directions, 10° – 60° angle).
Controls
- Control wiring is 2 X 16 AWG.
- The unit can be operated via a wireless or wired remote control with DDC-type signal (purchased separately).
- Supports dual set temperature when connected to supported controllers.
- No additional interface modules/adapters are required when connecting to Samsung central control options.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality allows configuration of fan operation during auxiliary heat, defrost, and emergency heat operations (VSTAT10P-1 accessory required).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality enables the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
- Emergency Temperature Output (ETO) function: When the indoor unit is in an error status or when room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer).
Specifications
V36D012S6-5P | |
---|---|
Indoor Unit Model Number | V36D012S6-5P |
Nominal Capacity Cooling (Btu/h) | 12,000 |
Nominal Capacity Heating (Btu/h) | 13,500 |
Voltage Ø / V / Hz | 1 / 208-230 / 60 |
Operating Current (max.) Cooling (A) | 0.18 |
Operating Current (max.) Heating (A) | 0.18 |
MCA (A) | 0.4 |
MOP (A) | 15 |
Evaporator Fan Type | BLDC (1) With Turbo Type Fan (1) |
Evaporator Fan Output (Watts) | 65 |
Airflow Cooling (CFM) | 494 / 530 / 565 |
Airflow Heating (CFM) | 494 / 530 / 565 |
Refrigerant Type | R-32 |
Refrigerant A2L Leak Detection | Integral |
Pipe Connections High side (in.) | 1/4 |
Pipe Connections Low side (in.) | 1/2 |
Condensate (in.) | 1 1/4 in. OD, 1 in. ID |
Dimensions W X H X D (in.) | 37 1/4 X 11 1/16 X 37 1/4 |
Weight (lbs.) | 44.50 |
Sound Pressure Level Low/Med./High (dB(A)) | 29 / 31 / 33 |
Safety Certifications | UL 60335-2-40 |
Fascia Panel Open Type (Round) L X W X H (in.) | 41 3/8 X 3 3/8 |
Fascia Panel Open Type (Round) Weight (lbs.) | 8.85 |
Fascia Panel Ceiling Type (Square) L X W X H (in.) | 39 3/8 X 39 3/8 X 2 5/8 |
Fascia Panel Ceiling Type (Square) Weight (lbs.) | 6.62 |
Fascia Panel Safety Certifications | UL 60335-2-40 |
Accessories
Category | Item | Model Number |
---|---|---|
Fascia Panel | Open Type (round, black) | V1V36D02CPBW |
Open Type (round, white) | V1V36D02CPWW | |
Ceiling Type (square, black) | V1V36D01CPBW | |
Ceiling Type (square, white) | V1V36D01CPWW | |
Controller | Advanced | VSTAT04P-1 |
Touchscreen | VSTAT02P-1 | |
Controller (Unspecified) | (Unspecified) | VSTAT09P-1 |
Controller (Unspecified) | (Unspecified) | VSTAT01P-1 |
Adapter | Thermostat adapter (for connection to standard 24VAC thermostats) | VCTRL11P-1 |
Controller | Wireless controller | VSTAT10P-1 |
Sensor | External temperature sensor | VCTRL11P-1 |
Module | External contact control interface module | VSTAT10P-1 |
Sensor | Motion detect sensor (MDS, white, compatible with square panel only) | V1MDS03CS |
Cable | CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Diagrams
Dimensional Drawing - With Ceiling Type Fascia Panel (Page 3)
This diagram illustrates the physical dimensions and connection points for the Lennox V36D012S6-5P unit when equipped with a Ceiling Type Fascia Panel. Key labeled components include:
- 1: Liquid pipe connection (1/4 in.)
- 2: Gas pipe connection (1/2 in.)
- 3: Drain pipe connection
- 4: Opening for power and communication wire conduit
- 5: Air outlet opening
- 6: Air inlet grille
- 7: Suction inlet for booster fan
- 8: Fascia panel
- 9: Drain hose
- 10: Fresh air intake
- 11: Display
- 12: Wireless signal receiver
Dimensional Drawing - With Open Type Fascia Panel (Page 4)
This diagram shows the physical dimensions and connection points for the Lennox V36D012S6-5P unit when equipped with an Open Type Fascia Panel. Key labeled components include:
- 1: Liquid pipe connection (1/4 in.)
- 2: Gas pipe connection (1/2 in.)
- 3: Drain pipe connection
- 4: Opening for power and communication wire conduit
- 5: Air outlet opening
- 6: Air inlet grille
- 7: Suction inlet for booster fan
- 8: Fascia panel
- 9: Drain hose
- 10: Fresh air intake
- 11: Display
- 12: Wireless signal receiver