Resclite Pro Tecton II Battery Replacement

Resclite Pro Tecton II Battery Replacement Instructions

Product Name: RESCLITE PRO TECTON II

Reference Numbers: 00160166 (Mounting Instructions), 00159920 (TEC2 Mounting Instructions)

Manufacturer: Zumtobel Lighting GmbH

Battery Replacement

If the backup power does not extend to the declared duration, the battery must be replaced. The electric source for safety service is not a user-serviceable item and shall only be replaced by the manufacturer's service agent or a similarly qualified person.

Battery Types

Type SAP Code Article Description
E1D 59014292 ACCU_LIION 3.2V 1.5Ah 18650 1 STI #100mm
E3D 59014293 ACCU_LIION 3.2V 3Ah 18650 2 SBS #100mm

Replacement Procedure

Step 1: Preparation

The process begins with power disconnection, indicated by a lightning bolt icon [lightning bolt]. The diagram shows the luminaire and a battery pack with an 'OFF' indicator [power off]. A general warning states: ⚠️ DO NOT OPEN LUMINAIRE! This is followed by instructions to OPEN LUMINAIRE for battery replacement. The illustration shows a battery pack being removed and a new one inserted, signifying the swap.

Step 2: Accessing the Battery Compartment

To access the battery, the luminaire housing must be unlocked and opened. This is depicted with a lock icon [lock] and a sequence of actions involving latches. A close-up view highlights the specific latch mechanism.

Step 3: Removing the Old Battery

The diagram illustrates disconnecting and removing the battery pack from its housing. A lock icon [lock] is shown, followed by steps to disengage the connector. A close-up view details the connector release.

Step 4: Installing the New Battery

The new battery pack is installed and connected. The diagram labels the new battery as '4e NEW' and the old battery as '4d OLD', with a recycle bin icon [recycle bin] indicating disposal. Components '4a', '4b', '4c' relate to the housing. The '4f' section provides space to record the 'Commissioned Date' or 'Inbetriebnahme'. Diagrams '4g', '4h', and '4i' illustrate the 'CLIX' connector mechanism used for securing parts.

Safety Precautions

Lithium Battery Warning

⚠️ CAUTION: Lithium batteries included! OBSERVE Manufacturer's Safety Instructions!

Do not tamper with the rechargeable batteries and/or battery packs in any way. In principle, lithium batteries are comparatively safe when handled properly.

Possible Hazards of Lithium Batteries

Lithium batteries or lithium accumulators contain:

  • Lithium or its compound (reacts violently)
  • Flammable organic solvents
  • Oxidising agents (fire promoters)
  • Reactive halogen compounds

A graphic depicts batteries with flames and a warning symbol [warning symbol]. Safety Data Sheets are referenced for Tridonic (EN) and Zumtobel (DE) via text placeholders for QR codes: [QR code placeholder for SDS EN], [QR code placeholder for SDS DE].

ExD Status LED Indicators

This section details the meaning of the status LEDs on the luminaire.

LED GREEN / GRÜN

Indicator Pattern Status
Solid light (1s) Everything okay / Alles o. k.
Pulsing (1s on, 1s off) Function test / Funktionstest
Pulsing (1s on, 1s off) Service life test / Betriebsdauertest
Short flashes (0.1s) Disabled / Blockiert

LED RED / ROT

Indicator Pattern Status
Solid light (1s) Lamp failure / Lampenfehler
Pulsing (1s on, 1s off) Charging failure / Ladefehler
Pulsing (1s on, 1s off) Battery failure / Batteriefehler

STATUS LED

A diagram illustrates the status LED indicator.

Models: 00160167, 00160167z00_D03_250603, 00160167 LED Strip Light, LED Strip Light, Strip Light

PDF preview unavailable. Download the PDF instead.

00160167 RESCLITE PRO TEC2 LFP CHANGE BATTERY GPL Ghostscript 9.52

Related Documents

Preview DALI MSENS HC TECTON II Mounting Instructions and Specifications
Official mounting instructions and technical specifications for the Zumtobel DALI MSENS HC TECTON II luminaire, including installation, operation, dimensions, and detection area adjustments.
Preview Resclite Pro Tecton II TEC2 Mounting Instructions
Comprehensive mounting, installation, and operation guide for the Zumtobel Resclite Pro Tecton II TEC2 emergency lighting luminaire. Includes details on lens options, switch modes, status indicators, battery replacement, and safety precautions.
Preview DIMLITE pro G2 TEC2 Mounting Instructions
Detailed mounting, installation, and operation instructions for the Zumtobel DIMLITE pro G2 TEC2 luminaire, including electrical connections, dimensions, and optional features. This guide is intended for qualified electricians.
Preview Zumtobel PST PIR CF TEC2 Mounting Instructions and Installation Guide
Official mounting and installation instructions for the Zumtobel PST PIR CF TEC2 luminaire, including technical specifications, wiring diagrams, dimensions, and operational guidance. This document is intended for qualified electricians.
Preview Zumtobel TEC2 Lighting Elements: Mounting Instructions and Specifications
Comprehensive mounting instructions, technical specifications, and product details for Zumtobel's TEC2 lighting elements, including AMPHIBIA, CRAFT II, ECOOS II, and CLARIS evolution series. Covers installation, options, and product variants.
Preview Zumtobel SCENO: Innovative Retail Lighting Solutions
Discover Zumtobel SCENO, a flexible and efficient lighting system designed to enhance retail environments. SCENO offers brilliant light, high color rendering, and adjustable optics to perfectly showcase merchandise and create engaging shopping experiences. Explore its various installation options, technical specifications, and suitability for both retail and office spaces.
Preview Zumtobel: 零售与展陈空间的照明解决方案
探索 Zumtobel 如何通过创新的照明技术和 Limbic® 研究,为零售和展陈空间打造引人入胜的客户体验,提升品牌形象和销售。
Preview Zumtobel PANOS R Recessed Downlight Installation and Operation Manual
Comprehensive guide for the installation, operation, and maintenance of the Zumtobel PANOS R recessed downlight series (R150/R200 WW). Includes safety instructions, technical specifications, and multilingual mounting guidance.