Submittal Data
VOWD018S6-5P VRF 1-Way Cassette
General Information
- Compatible with R-32 VRF air, water, and mini systems.
- The indoor unit features "calm air mode." When activated in cooling mode, the unit closes its louver and disperses air through micro-holes on the front, preventing cold air drafts.
- The indoor unit includes an integral condensate pump with a maximum lift of 26-5/16" from the bottom of the unit (21-5/16" from the drain outlet). It has a check valve and float switch to disable the unit in case of condensate overflow.
- The indoor unit fascia panel includes a built-in Wi-Fi adapter as standard for control and monitoring via the Samsung SmartThings app.
An image shows the Lennox VRF 1-Way Cassette indoor unit, a rectangular unit designed for ceiling installation with a clean, white fascia panel.
Construction
- Insulated, HIPS chassis and fascia panel certified to UL94 V0.
- High-voltage terminal block temperature sensor disables the unit if power connection overheats.
Refrigerant System
- The heat exchanger is mechanically bonded aluminum fin to copper tube.
- The indoor unit includes an R32 alarm output plug for notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).
Indoor Fan
- Features three fan speed settings and an auto setting.
- Includes an electro-static, washable filter as standard (integrated with the fascia panel).
- Fascia panel has an LED display, infrared receiver, and motorized louvers.
Controls
- Control wiring is 2 x 16 AWG.
- Operation is via a wired remote controller model VSTAT04P-1 (purchased separately).
- Supports dual set temperature when connected to compatible controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Allows configuration of fan operation during auxiliary heat, defrost, and emergency heat modes (requires VSTAT10P-1 accessory).
- Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).
- Emergency heat functionality ensures the system continues controlling the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).
Convenience
- Emergency Temperature Output (ETO) function: When the indoor unit is in an error status or room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Specifications
Model | Indoor Unit Model Number | VOWD018S6-5P |
Performance | Nominal Capacity Cooling (Btu/h) | 18,000 |
Nominal Capacity Heating (Btu/h) | 20,000 | |
Voltage | Ø/V/Hz | 1/208-230/60 |
Power | Operating Current (max.) Cooling (A) | 0.28 |
Operating Current (max.) Heating (A) | 0.28 | |
MCA (A) | 0.35 | |
MOP (A) | 15 | |
Evaporator Fan | Type | BLDC motor with cross-flow fan |
Output (Watts) | 54 | |
Airflow | Air Volume (L/M/H) Cooling (CFM) | 441 / 494 / 565 |
Air Volume (L/M/H) Heating (CFM) | 441 / 494 / 565 | |
Refrigerant | Type | R-32 |
A2L Leak Detection | Integral | |
Pipe Connections | High side (In.) | 1/4 |
Low side (In.) | 1/2 | |
Condensate | 1 1/4 in. OD, 1 in. ID | |
Dimensions | W x H x D (In.) | 47 1/4 x 5 7/16 x 17 3/4 |
Weight (lbs.) | 28.70 | |
Sound Pressure Level (Low/Med./High) (dB(A)) | 35 / 38 / 41 | |
Safety | Certifications | UL 60335-2-40 |
Fascia Panel L x W x H (In.) | 55 1/2 x 4.75 x 1 3/8 | |
Fascia Panel Weight (lbs.) | 11.0 | |
Fascia Panel Certifications | UL 60335-2-40 |
Accessories
Accessory Type | Model Number |
---|---|
Fascia Panel | V1VOWD05CPWW |
Wired controller (Advanced Touchscreen) | VSTAT04P-1 |
Wired controller | VSTAT02P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless controller | VSTAT01P-1 |
External temperature sensor | VCTRL11P-1 |
External contact control interface module | VSTAT10P-1 |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
Dimensional drawings illustrate the unit's dimensions and connection points. Key dimensions include overall width of approximately 55-1/2 inches, height of 5-7/16 inches, and depth of 17-3/4 inches. The ceiling opening required is approximately 54-5/16 inches by 18-1/2 inches. Connection points are detailed for liquid and gas refrigerant pipes, drain hose, power/communication conduit, air outlet louver, and air inlet grille.
No. | Description |
---|---|
1 | Liquid pipe connection (1/4") |
2 | Gas pipe connection (1/2") |
3 | Drain hose connection |
4 | Opening for power and communication wire conduit |
5 | Air outlet louver |
6 | Air inlet grille |
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.