Blue Ridge High Wall Heat Pump System

Submittal Data Sheet

Certifications

The system is certified by AHRI, ETL Listed, and ENERGY STAR qualified.

Indoor Unit Specifications

SpecificationValue
Indoor Air Flow (Turbo/H/M/L/Si) (CFM)759.3 / 588.6 / 470.9 / 323.7 / /
Indoor Noise Level (Turbo/H/M/L/Si) (dBA)54.0/48.0/43.0/33.5/20.0
Dimension (W×D×H) (inch)42.52 x 8.90 x 13.19
Dimension (W×D×H) (mm)1080×226×335
Package (W×D×H) (inch)46.73 x 17.68 x 14.29
Package (W×D×H) (mm)1187×449×363
Net Weight (lbs / kg)35.93 / 16.3
Gross Weight (lbs / kg)49.82 / 22.6

Outdoor Unit Specifications

SpecificationValue
Compressor TypeROTARY
Compressor ModelKTM240D46UKT2
RefrigerantR454B
Refrigerant Oil Charge (mL)620
Refrigerant Oil (L)9.3
Outdoor Air Flow (Max) (CFM)3800
Outdoor Noise Level (dBA)58.5
Dimension (W×D×H) (inch)37.24 x 16.14 x 31.89
Dimension (W×D×H) (mm)946×410×810
Package (W×D×H) (inch)42.91 x 19.88 x 37.01
Package (W×D×H) (mm)1090×505×940
Net Weight (lbs / kg)122.80 / 55.7
Gross Weight (lbs / kg)155.64 / 70.6

Efficiency Ratings

RatingCoolingHeating
SEER222.7-
EER212.7-
HSPF2-4-9.5
COP-3.07

Performance of Cooling

ParameterValue
Rated Capacity (Btu/hr)23000
Min/Max Capacity (Btu/hr)6200~26200
Moisture Removal (L/h)3.09
Standard Operating Range (°F / °C)-13~75 (-25~50)
ConditionsIndoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB

Performance of Heating

ParameterValue
1. @ 47°F Rated (Btu/hr)23000
1. @ 47°F Min/Max Capacity (Btu/hr)10300~28200
2. @ 17°F Rated (Btu/hr)17900
3. @ 5°F Rated: Capacity / COP15900 / 2.00
3. @ 5°F Max: Capacity (Btu/hr)15900
Standard Operating Range (°F / °C)-13~122 (-25~24)
1. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB
2. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB
3. ConditionsIndoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB

Electrical Specifications

SpecificationValue
Power Supply208/230V, 60Hz, 1Ph
System MCA (A)24
Connection Wiring14#x4
System MOCP (A)25
Compressor RLA (A)15.4
Outdoor Fan Motor RLA (A)1.0
Outdoor Fan Motor W120
Indoor Fan Motor RLA (A)0.8
Indoor Fan Motor W58
System Power Input @ Cooling (W)2000 (650~2500)
System Power Input @ Heating (W)2400 (640~2940)

Piping Specifications

SpecificationValue
Throttle type (Indoor)N/A
Throttle type (Outdoor)EXV + Throttle valve
Liquid Size9.52mm (3/8in)
Gas Size15.9mm (5/8in)
Max. Piping Length (ft/m)164 (50)
Max. Height Difference (ft/m)82 (25)
Max. Pre-charged Length (ft/m)24.6 (7.5)
Refrigerant Pre-charged Amount (oz/g)67.37 (1.91)
Additional Charge of Refrigerant ((oz/ft) / (g/m))0.32 (30)
Connection MethodFlared

Indoor Unit Dimensions and Installation

The indoor unit dimensions are detailed in a table and visual representation. The table lists capacities from 9k to 36k BTU, with corresponding Body Codes (A, B, D, E, F). Dimensions are provided in inches and millimeters for Width (W), Depth (D), and Height (H) for each capacity range. For example, the 18k-24k capacity (Body Code D) has dimensions of 38 inches (965mm) W x 8.5 inches (215mm) D x 12.5 inches (319mm) H. The visual diagram shows the indoor unit with labels for W, D, and H.

Installation instructions for the indoor unit focus on selecting the mounting location and managing piping exit. The diagram illustrates a wall with recommended clearances: 6 inches (15cm) from the ceiling and 4-3/4 inches (12cm) from the side for the mounting plate. It also shows four possible exit directions for the piping: left-hand side, right-hand side, left rear, and right rear. A note advises that if the gas side connective pipe is 5/8 inch (16mm) or larger, the wall hole should be 3-1/2 inches (90mm).

Outdoor Unit Dimensions and Installation

The outdoor unit dimensions are presented through detailed diagrams showing the unit from multiple views (front, side, top). Various measurements are provided in inches and millimeters, indicating the overall width, depth, and height, as well as specific component placements and connection points.

Installation clearance requirements for the outdoor unit are visually represented. The diagram shows the unit with specific minimum clearances: 20 inches (500mm) or more at the front and sides when these areas are clear; 4 inches (100mm) or more on the sides; and 14 inches (350mm) or more at the rear. An important note states that all spatial requirements shown must be met.

Features

  • Indoor unit TU1 copper coil
  • Humidity control
  • 1% to 100% fan speed setting
  • WiFi capability: through WiFi dongle or wired controller with built-in WiFi
  • OTA (Over-The-Air updates) via WiFi dongle
  • Multiple control options available:
    • Two-way communication wired controller: 120N(X6)
    • Two-way communication wired controller with built-in WiFi: 120N(X6W)
    • Infrared wired controller: 120L
    • Wireless remote controller
    • Third-Party 24V Thermostat* (*24V interface is required)

PDF preview unavailable. Download the PDF instead.

blueridgebds2a24sc0-24wmspecificationssheet 219F892F-105E-4B9A-950F-A7E57484B666 Google Sheets

Related Documents

Preview Blue Ridge High Wall Heat Pump System: Technical Specifications and Installation Guide
Comprehensive technical specifications, performance data, electrical requirements, and installation guidelines for the Blue Ridge High Wall Heat Pump System, including SEER2, HSPF2-4, and detailed operating conditions.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Comprehensive submittal data sheet for the Blue Ridge High Wall Heat Pump System, detailing efficiency ratings, cooling and heating performance, indoor and outdoor unit specifications, electrical requirements, piping details, installation guidelines, and key features.
Preview Blue Ridge DS2 High Wall Heat Pump System - Technical Specifications & Features
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including efficiency ratings (SEER2, HSPF2-4), performance data, indoor/outdoor unit specifications, electrical requirements, piping details, and features like WiFi connectivity.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge High Wall Heat Pump System, covering efficiency ratings, performance specifications for cooling and heating, indoor and outdoor unit details, electrical requirements, and piping information.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications and performance data for the Blue Ridge High Wall Heat Pump System, including efficiency ratings, cooling and heating performance, indoor/outdoor unit details, electrical requirements, and piping specifications.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications, performance data, dimensions, and features for the Blue Ridge High Wall Heat Pump System, including cooling and heating performance, electrical requirements, and installation guidelines.
Preview Blueridge XS2+Entry High Wall Heat Pump System - 21 SEER2 Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS2+Entry high wall heat pump system, detailing efficiency ratings (21 SEER2), performance specifications for cooling and heating, electrical requirements, piping details, and key features. Includes indoor and outdoor unit dimensions and installation clearance guidelines.
Preview Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series Submittal Data Sheet
Submittal data sheet for the Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series heat pump system, detailing efficiency ratings, cooling and heating performance, indoor and outdoor specifications, electrical requirements, piping details, installation guidelines, and fan performance.