SUBMITTAL DATA SHEET

High Wall Heat Pump System

System Information

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

Approval:

Date:

Construction:

Unit #:

Drawing #:

Efficiency Ratings

Category Cooling Heating
SEER2 23.6 HSPF2-4: 11.5
EER2 14 COP: 3.72

Performance of Cooling

Rated Capacity (Btu/hr) 9000
Min/Max Capacity (Btu/hr) 3200~11500
Moisture Removal (L/h) 1.37
Standard Operating Range (°F/°C) -13 to 75 (-25 to 50)
Conditions Indoor: 80°F DB / 67°F WB; Outdoor: 95°F DB / 75°F WB

Performance of Heating

Rated Capacity (Btu/hr) @ 47°F 10000
Min/Max Capacity (Btu/hr) @ 47°F 4000~12900
Rated Capacity (Btu/hr) @ 17°F 7500
Capacity / COP @ 5°F 7300 / 2.17
Max Capacity (Btu/hr) @ 5°F 8400
Standard Operating Range (°F/°C) -13 to 122 (-25 to 24)
Conditions 1. Indoor: 70°F DB / 60°F WB; Outdoor: 47°F DB / 43°F WB
2. Indoor: 70°F DB / 60°F WB; Outdoor: 17°F DB / 15°F WB
3. Indoor: 70°F DB / 60°F WB; Outdoor: 5°F DB / 5°F WB

Indoor Unit Specifications

Parameter Value
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) 367.9 / 317.8 / 214.8 / 129.5 / 67.7
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) 43.0 / 39.5 / 33.5 / 24.0 / 18.0
Dimension (W×D×H) (inch) 31.57 x 7.44 x 11.69
Dimension (W×D×H) (mm) 802×189×297
Package (W×D×H) (inch) 36.02 x 16.34 x 14.37
Package (W×D×H) (mm) 915×415×365
Net/Gross Weight (lbs) 24.91 / 35.49
Net/Gross Weight (kg) 11.3 / 16.1

A diagram illustrates the indoor unit's dimensions, labeled with Width (W), Depth (D), and Height (H). A table provides specific measurements in inches and millimeters for various models or capacities.

Outdoor Unit Specifications

Parameter Value
Compressor Type ROTARY
Compressor Model KSK103D33UEZ3
Refrigerant R454B
Refrigerant Oil Charge (mL) 310
Refrigerant Oil 5.65
Outdoor Air Flow (Max) (CFM) 2100
Outdoor Noise Level (dBA) 54
Dimension (W×D×H) (inch) 30.12 x 11.93 x 21.85
Dimension (W×D×H) (mm) 765×303×555
Package (W×D×H) (inch) 36.22 x 16.54 x 27.56
Package (W×D×H) (mm) 920×420×700
Net/Gross Weight (lbs) 83.11 / 65.48
Net/Gross Weight (kg) 37.7 / 29.7

A diagram presents the outdoor unit's dimensions, with labels for Width (W, W1), Depth (D), and Height (H), including a detailed view (DETAIL A) with scale. Measurements are provided in inches and millimeters.

Electrical Specifications

Parameter Value
Power Supply 115V, 60Hz, 1Ph
System MCA 18.0
Connection Wiring 14#x4
System MOCP 20
Compressor RLA 14.0
Outdoor Fan Motor RLA 0.6
Outdoor Fan Motor W 34
Indoor Fan Motor RLA 0.6
Indoor Fan Motor W 35
System Power Input @ Cooling (W) 643 (200 ~ 970)
System Power Input @ Heating (W) 788 (220 ~ 1090)
MCA: Min. circuit amps (A)
MOCP: Max. over current protection (A)
RLA: Rated load amps (A)
W: Fan motor rated output (W)

Piping Specifications

Parameter Value
Throttle type (Indoor) N/A
Throttle type (Outdoor) EXV
Liquid Size 6.35mm (1/4in)
Gas Size 9.52mm (3/8in)
Max. Piping Length (ft/m) 82 (25)
Max. Height Difference (ft/m) 49.20 (15)
Max. Pre-charged Length (ft/m) 24.6 (7.5)
Refrigerant Pre-charged Amount (oz/g) 30.34 (0.86)
Additional Charge of Refrigerant (oz/ft) / (g/m) 0.16 (15)
Connection Method Flared

Installation Notes

Indoor Unit Installation

An illustration demonstrates installation options for the indoor unit's piping exit, showing four possible directions relative to the wall hole and mounting plate. A note advises that the wall hole should be 3-1/2 inches (90mm) if the gas side connective pipe is 5/8 inch (16mm) or larger.

Outdoor Unit Installation

An illustration outlines the required clearance space around the outdoor unit for optimal performance. It specifies minimum clearances: 20 inches (500mm) when front and sides are clear, 4 inches (100mm) on the sides, and 14 inches (350mm) at the rear. A checkmark symbol ? indicates that the unit meets these spatial requirements.

Features

Product Images and Certifications

A visual representation shows the indoor unit of the heat pump system, typically wall-mounted, with a slim, modern design. A visual representation shows the outdoor unit (condenser) of the heat pump system, featuring a fan grill and housing for the compressor and components. The document displays several certification logos: ALIDI PCERTIFIED, ETL LISTED, and ENERGY STAR.

PDF preview unavailable. Download the PDF instead.

blueridgebds2a09scv-9wmvspecificationssheet DB195532-2EE8-4BD3-9927-463F319CD140 Google Sheets

Related Documents

Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications, performance data, dimensions, and features for the Blue Ridge High Wall Heat Pump System, including cooling and heating performance, electrical requirements, and installation guidelines.
Preview Blue Ridge High Wall Heat Pump System: Technical Specifications and Installation Guide
Comprehensive technical specifications, performance data, electrical requirements, and installation guidelines for the Blue Ridge High Wall Heat Pump System, including SEER2, HSPF2-4, and detailed operating conditions.
Preview Blue Ridge XL1 FC Ceiling & Floor Regular System Submittal Data Sheet - Specifications and Features
Detailed submittal data sheet for the Blue Ridge XL1 FC Ceiling & Floor Regular System, including efficiency ratings, performance specifications for cooling and heating, indoor and outdoor unit dimensions, electrical requirements, piping details, and available control features.
Preview Ceiling & Floor Heat Pump System Submittal Data Sheet
Submittal data sheet for the Ceiling & Floor Heat Pump System, detailing efficiency, performance, indoor and outdoor specifications, electrical, and piping information. Includes features and installation clearance requirements.
Preview Blue Ridge 4-Way Cassette Regular System Submittal Data Sheet
This document provides detailed specifications for the Blue Ridge 4-Way Cassette Regular System, including indoor and outdoor unit dimensions, efficiency ratings, performance data for cooling and heating, electrical specifications, and piping details. It also outlines features and control options.
Preview Blue Ridge DS2 High Wall Heat Pump System - Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including specifications for cooling, heating, electrical, piping, dimensions, and installation clearances. Features include humidity control and WiFi capability.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge High Wall Heat Pump System, covering efficiency ratings, performance specifications for cooling and heating, indoor and outdoor unit details, electrical requirements, and piping information.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications and performance data for the Blue Ridge High Wall Heat Pump System, including efficiency ratings, cooling and heating performance, indoor/outdoor unit details, electrical requirements, and piping specifications.