SUBMITTAL DATA SHEET

High Wall Heat Pump System

Efficiency

CoolingHeating
SEER222.5HSPF2-4 11.5
EER213.7COP 4.02

Performance of Cooling

Cooling (Btu/hr)

Rated Capacity18000
Min/Max Capacity7700~20600
Moisture Removal(L/h)1.49
Standard Operating Range (°F/°C)-13~75 (-25~50)
ConditionsIndoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB

Performance of Heating

Heating (Btu/hr)

1. @ 47°F Rated18000
1. @ 47°F Min/Max Capacity8100~22600
2. @ 17°F Rated13400
3. @ 5°F Rated: Capacity / COP12800/2.44
3. @ 5°F Max: Capacity12800
Standard Operating Range (°F/°C)-13~122 (-25~24)
Conditions1. Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB
2. Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB
3. Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB

Indoor Specification

Indoor Air Flow (Turbo/H/M/L/Si) (CFM)671.0 / 470.9 / 382.6 / 323.7 / /
Indoor Noise Level (Turbo/H/M/L/Si) (dBA)54.5/44.5/40.5/30.5/19.0
Dimension (W×D×H)inch: 42.52 x 8.90 x 13.19
mm: 1080×226×335
Package (W×D×H)inch: 46.73 x 17.68 x 14.29
mm: 1187×449×363
Net/Gross Weightlbs: 35.49/49.60
kg: 16.1/22.5

Outdoor Specification

Compressor TypeROTARY
Compressor ModelKSN140D58UFZ
RefrigerantR454B
Refrigerant Oil Charge(mL)440
Refrigerant Oil7.2
Outdoor Air Flow (Max) (CFM)3000
Outdoor Noise Level (dBA)58.5
Dimension (W×D×H)inch: 35.04 x 13.46 x 26.50
mm: 890×342×673
Package (W×D×H)inch: 40.55 x 18.11 x 29.53
mm: 1030×460×750
Net/Gross Weightlbs: 93.48/114.20
kg: 42.4/51.8

Electrical

Power Supply208/230V, 60Hz, 1Ph
System MCA18
Connection Wiring14#x4
System MOCP20
Compressor RLA10.0
Outdoor Fan Motor RLA0.9
Outdoor Fan Motor W80
Indoor Fan Motor RLA0.6
Indoor Fan Motor W58
System Power Input @ Cooling (W)1300 (550~1690)
System Power Input @ Heating (W)1280 (405~1670)

Piping

Throttle type(Indoor)N/A
Throttle type(Outdoor)EXV+Throttle valve
Liquid Size6.35mm (1/4in)
Gas Size12.7mm (1/2in)
Max. Piping Length (ft/m)98.40 (30)
Max. Height Difference (ft/m)65.60 (20)
Max. Pre-charged Length (ft/m)24.6 (7.5)
Refrigerant Pre-charged Amount (oz/g)44.80 (1.27)
Additional Charge of Refrigerant ((oz/ft)/(g/m))0.16 (15)
Connection MethodFlared

Indoor Unit Dimensions and Installation

The indoor unit dimensions are detailed with Width (W), Depth (D), and Height (H) measurements.

CapacityBody CodeW (inch/mm)D (inch/mm)H (inch/mm)
9k Entry Tier SeriesA28-1/2in/722mm7-3/8in/187mm11-3/8in/290mm
9k~12kB31-1/2in/802mm7-1/2in/189mm11-3/4in/297mm
18k Entry Tier SeriesD38in /965mm8-1/2in/215mm12-1/2in/319mm
18k~24kE42-1/2in/1080mm8-7/8in/226mm13-1/4in/335mm

Installation Instructions

Select Installation Location: The diagram shows placement guidelines for the indoor unit, indicating a 6 inch [top clearance] and 4-3/4 inch [side clearance] requirement from the top and sides respectively, with a recommended height of 70 inches [floor clearance].

Piping Exit Options: The unit allows for piping to exit from four directions: left-hand side, right-hand side, left rear, and right rear. The choice depends on the wall hole position relative to the mounting plate.

Note: If the gas side connective pipe is 5/8in (16mm) or larger, the wall hole should be 3-1/2in (90mm).

Outdoor Unit Dimensions and Installation

The outdoor unit dimensions are detailed with various measurements including Width (W, W1, W2, W3), Depth (D, D1, D2), and Height (H1, H2).

Installation Clearance Requirements

The diagram illustrates the necessary clearances around the outdoor unit for proper operation:

✓ Meets all spatial requirements shown in Installation Clearance Requirements above.

Features

*24V interface is required.

PDF preview unavailable. Download the PDF instead.

blueridgebds2a18sc0-18wmspecificationssheet 70F8EBF2-A92E-4E4F-B034-ABF519EFC493 Google Sheets

Related Documents

Preview Blue Ridge DS2 High Wall Heat Pump System - Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including specifications for cooling, heating, electrical, piping, dimensions, and installation clearances. Features include humidity control and WiFi capability.
Preview Blue Ridge Slim Duct Heat Pump System: Submittal Data Sheet & Specifications
Detailed submittal data sheet for the Blue Ridge Slim Duct Heat Pump System, including specifications, performance data, dimensions, and installation clearances. Features R454B refrigerant and Energy Star certification.
Preview Blue Ridge High Wall Heat Pump System: Technical Specifications and Installation Guide
Comprehensive technical specifications, performance data, electrical requirements, and installation guidelines for the Blue Ridge High Wall Heat Pump System, including SEER2, HSPF2-4, and detailed operating conditions.
Preview Blue Ridge DS2 High Wall Heat Pump System - Technical Specifications & Features
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including efficiency ratings (SEER2, HSPF2-4), performance data, indoor/outdoor unit specifications, electrical requirements, piping details, and features like WiFi connectivity.
Preview Blue Ridge XS3 LW Series R454B Console Heat Pump Technical Specifications
Comprehensive technical specifications for the Blue Ridge XS3 LW Series R454B Console Heat Pump. This document details cooling and heating performance metrics, indoor and outdoor unit specifications, electrical requirements, piping details, and key features. Designed for efficiency and performance, it includes Energy Star certification information.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge High Wall Heat Pump System, covering efficiency ratings, performance specifications for cooling and heating, indoor and outdoor unit details, electrical requirements, and piping information.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications and performance data for the Blue Ridge High Wall Heat Pump System, including efficiency ratings, cooling and heating performance, indoor/outdoor unit details, electrical requirements, and piping specifications.
Preview R454b Air Handler Heat Pump System - Submittal Data Sheet | Blue Ridge
Detailed submittal data sheet for the Blue Ridge R454b Air Handler Heat Pump System (Model KSN140D58UFZ), including efficiency, performance, electrical, and piping specifications, along with unit dimensions and installation clearances.