SUBMITTAL DATA SHEET
High Wall Heat Pump System
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 22.5 | HSPF2-4 11.5 |
EER2 | 13.7 | COP 4.02 |
Performance of Cooling
Cooling (Btu/hr)
Rated Capacity | 18000 |
Min/Max Capacity | 7700~20600 |
Moisture Removal(L/h) | 1.49 |
Standard Operating Range (°F/°C) | -13~75 (-25~50) |
Conditions | Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB |
Performance of Heating
Heating (Btu/hr)
1. @ 47°F Rated | 18000 |
1. @ 47°F Min/Max Capacity | 8100~22600 |
2. @ 17°F Rated | 13400 |
3. @ 5°F Rated: Capacity / COP | 12800/2.44 |
3. @ 5°F Max: Capacity | 12800 |
Standard Operating Range (°F/°C) | -13~122 (-25~24) |
Conditions | 1. Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB 2. Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB 3. Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Indoor Specification
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 671.0 / 470.9 / 382.6 / 323.7 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 54.5/44.5/40.5/30.5/19.0 |
Dimension (W×D×H) | inch: 42.52 x 8.90 x 13.19 mm: 1080×226×335 |
Package (W×D×H) | inch: 46.73 x 17.68 x 14.29 mm: 1187×449×363 |
Net/Gross Weight | lbs: 35.49/49.60 kg: 16.1/22.5 |
Outdoor Specification
Compressor Type | ROTARY |
Compressor Model | KSN140D58UFZ |
Refrigerant | R454B |
Refrigerant Oil Charge(mL) | 440 |
Refrigerant Oil | 7.2 |
Outdoor Air Flow (Max) (CFM) | 3000 |
Outdoor Noise Level (dBA) | 58.5 |
Dimension (W×D×H) | inch: 35.04 x 13.46 x 26.50 mm: 890×342×673 |
Package (W×D×H) | inch: 40.55 x 18.11 x 29.53 mm: 1030×460×750 |
Net/Gross Weight | lbs: 93.48/114.20 kg: 42.4/51.8 |
Electrical
Power Supply | 208/230V, 60Hz, 1Ph |
System MCA | 18 |
Connection Wiring | 14#x4 |
System MOCP | 20 |
Compressor RLA | 10.0 |
Outdoor Fan Motor RLA | 0.9 |
Outdoor Fan Motor W | 80 |
Indoor Fan Motor RLA | 0.6 |
Indoor Fan Motor W | 58 |
System Power Input @ Cooling (W) | 1300 (550~1690) |
System Power Input @ Heating (W) | 1280 (405~1670) |
Piping
Throttle type(Indoor) | N/A |
Throttle type(Outdoor) | EXV+Throttle valve |
Liquid Size | 6.35mm (1/4in) |
Gas Size | 12.7mm (1/2in) |
Max. Piping Length (ft/m) | 98.40 (30) |
Max. Height Difference (ft/m) | 65.60 (20) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/g) | 44.80 (1.27) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.16 (15) |
Connection Method | Flared |
Indoor Unit Dimensions and Installation
The indoor unit dimensions are detailed with Width (W), Depth (D), and Height (H) measurements.
Capacity | Body Code | W (inch/mm) | D (inch/mm) | H (inch/mm) |
---|---|---|---|---|
9k Entry Tier Series | A | 28-1/2in/722mm | 7-3/8in/187mm | 11-3/8in/290mm |
9k~12k | B | 31-1/2in/802mm | 7-1/2in/189mm | 11-3/4in/297mm |
18k Entry Tier Series | D | 38in /965mm | 8-1/2in/215mm | 12-1/2in/319mm |
18k~24k | E | 42-1/2in/1080mm | 8-7/8in/226mm | 13-1/4in/335mm |
Installation Instructions
Select Installation Location: The diagram shows placement guidelines for the indoor unit, indicating a 6 inch [top clearance] and 4-3/4 inch [side clearance] requirement from the top and sides respectively, with a recommended height of 70 inches [floor clearance].
Piping Exit Options: The unit allows for piping to exit from four directions: left-hand side, right-hand side, left rear, and right rear. The choice depends on the wall hole position relative to the mounting plate.
Note: If the gas side connective pipe is 5/8in (16mm) or larger, the wall hole should be 3-1/2in (90mm).
Outdoor Unit Dimensions and Installation
The outdoor unit dimensions are detailed with various measurements including Width (W, W1, W2, W3), Depth (D, D1, D2), and Height (H1, H2).
Installation Clearance Requirements
The diagram illustrates the necessary clearances around the outdoor unit for proper operation:
- 20 inches (500mm) or more clearance in the front.
- 4 inches (100mm) or more clearance on the sides.
- 14 inches (350mm) or more clearance on one side.
- 20 inches (500mm) or more clearance on any two sides (left, right, and rear) of the unit.
✓ Meets all spatial requirements shown in Installation Clearance Requirements above.
Features
- Indoor unit TU1 copper coil
- Humidity control
- 1~100% fan speed setting
- WiFi capability: through WiFi dongle or wired controller with built-in WiFi
- OTA (by using WiFi dongle)
- Multiple control options available:
- Two way communication wired controller: 120N(X6)
- Two way communication wired controller with built-in WiFi: 120N(X6W)
- Infrared wired controller: 120L
- Wireless remote controller
- Third-Party 24V Thermostat*
*24V interface is required.