Mircom FX-3318 Single Loop Intelligent Fire Alarm Control Panel
Model: FX-3318
Description
Mircom's FX-3318 Addressable Fire Alarm Control Panel is an intelligent addressable multi-zoned panel offering exceptional value without compromising the features needed for small to medium job applications. The FX-3318 is shipped pre-assembled with all main components, including the main board, power supply, transformer, and main display, housed within a red enclosure.
A built-in dialer is included to communicate panel status to a remote central monitoring station using two dedicated phone lines. It supports both SIA and Contact ID protocols. Up to seven annunciators can be added with enclosure options in red, white, or NEW stainless steel.
The panel features one built-in signaling line circuit (SLC). With Mircom's Advanced Protocol (AP), a superior group polling method and an interrupt feature allow for a faster response to alarms. The AP or Advanced Protocol supports greater system capacity with up to 318 devices in AP mode and offers legacy CLIP support for up to 198 devices.
The FX-3318 has four Power Limited Class B (Style Y) or Class A (Style Z) NAC circuits. NAC circuits can be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or relay output. The audible signal can be Steady, Temporal Code, California Code, or March Time. Sync strobe protocols from major manufacturers are supported.
The built-in trim ring accommodates both retrofits and new installations, reducing installation time with semi-flush or surface mountable options. The panel is UL, 9th edition listed and has COA and CSFM listings.
Features
- One onboard SLC communication circuit
- Supports up to 318 intelligent devices in AP mode
- Legacy CLIP support of up to 198 devices
- Built-in Dialer Module for remote monitoring
- 4 x 20 LCD with 80 characters
- Supports up to 7 annunciators
- Optional City Tie/Polarity Reversal module for central station monitoring & field installable
- Four Power Limited Class B (Style Y) or Class A (Style Z) NAC circuits (max 1.5 Amps each - 5.0 amps total)
- Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC filtered and regulated, and resettable auxiliary power supply
- Positive Alarm Sequence (PAS): Provides an alarm delay of up to 180 seconds if an alarm is acknowledged at the control panel within 15 seconds. This action allows responding personnel time to investigate an alarm before evacuating a building.
- Supports sync strobe protocols from major manufacturers
- Two-stage, alarm verification, waterflow retard, and positive alarm sequence operations
- Configurable Signal Silence Inhibit, Auto Signal Silence, and One-Man Walk Test
User Interfaces
Indication and Controls:
- 12 control buttons with associated LEDs
- 16-button Numeric Keypad with cursor buttons
LCD Display:
The display is a four-line, 4 x 20, 80-character back-lit alphanumeric LCD. It displays information regarding the panel, its circuits, and devices. Report information provided by the LCD display includes:
- Alarm Log
- Event Log
- Current Levels
- Device Information
- Verification and Maintenance Reports
System Specifications
Advanced Protocol and CLIP Devices:
- Maximum Loop Current = 350mA
- Maximum Loop Resistance = 40 ohms
- Maximum Loop Capacitance = 0.5uF
- Maximum number of isolators = 20
Agency Listings and Approvals:
UL-864 Rev 9, NFPA 70, 72, CSFM and COA
System Capacity:
- Intelligent Signaling Line Circuits: 1
- Addressable device capacity: 318
- Programmable Software Zones: 99
- ACS Annunciators: 32
- ANN-Bus Devices: 16
Compatible Receivers
The FX-3318 is compatible with the following Digital Alarm Communicator Receivers:
DACR Receiver | Model Protocols |
---|---|
SurGard MLR2 Multi-Line Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
SurGard SLR Single-Line Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
Osborne-Hoffman Quickalert! II Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
Osborne-Hoffman OH-2000 Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
Silent Knight Model 9500 Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
Radionics Model D6500 Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
Radionics Model D6600 Receiver (ULI approved) | SIA Format Protocol and SIA Contact ID |
DSC SurGard System III Receiver (ULI approved)* | SIA Contact ID |
DSC SurGard System IV Receiver (ULI approved)* | SIA Contact ID |
*Please refer to manual
Electrical Specifications
AC Power: 120 VAC, 60Hz / 240 VAC, 50 Hz. Wire size: minimum 14 AWG (2.08mm²) with 600v insulation. Fire alarm systems must be installed in compliance with local codes and standards and with the Authority Having Jurisdiction (AHJ).
Auxiliary Power: Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC filtered and regulated, and resettable auxiliary power supply.
Power Supply Rating: 29VAC 6A (secondary of transformer), 120 VAC 60Hz 1.6 Amp (maximum primary of transformer). 240 VAC 50 Hz 0.9 Amp (maximum primary of transformer). Total load not to exceed 5A @ 24VDC.
Battery Charger Capacity: 10AH – 24AH charging capability. Charging current 1.575A maximum. Protection 10A on-board slow micro fuse (not field replaceable). Stand-by current rating at full load 0.7A.
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Refer to manual for all details. Power Limited NAC circuits (max 1.5 Amps each - 5.0 Amps total) if no auxiliary power is used. Strobe/Horn circuits with multiple strobes/horns in one open area, needs to be synchronized.
Maximum Wiring Run to Last Device (ELR)
Amperes | 18AWG | 16AWG | 14AWG | 12AWG | MAX Loop Resistance | ||||
---|---|---|---|---|---|---|---|---|---|
ft | m | ft | m | ft | m | ft | m | Ohms | |
0.06 | 2350 | 416 | 3750 | 1143 | 6000 | 1929 | 8500 | 2591 | 30 |
0.12 | 1180 | 360 | 1850 | 567 | 3000 | 915 | 4250 | 1296 | 15 |
0.30 | 470 | 143 | 750 | 229 | 1200 | 366 | 1900 | 579 | 6 |
0.60 | 235 | 71 | 375 | 114 | 600 | 183 | 850 | 259 | 3 |
0.90 | 156 | 47 | 250 | 76 | 400 | 122 | 570 | 174 | 2 |
1.20 | 118 | 36 | 185 | 56 | 300 | 91 | 425 | 129 | 1.5 |
1.50 | 94 | 29 | 150 | 46 | 240 | 73 | 343 | 105 | 1.2 |
Addressable Loops & Device Wiring:
Advanced protocol mode supports one loop with 159 addressable sensors and 159 addressable modules per loop. CLIP mode supports one loop with 99 addressable sensors and 99 addressable modules per loop. The addressable loop can be configured as Class A or Class B operation. Maximum loop resistance depends on the number of devices and device type. Specifications: Power Limited / 22VDC / 350mA alarm maximum / 0.5 µF; Power Limited / 22VDC / 280mA normal standby maximum / 0.5 µF.
Cabinet Specifications:
- Dimensions of Enclosure (minus built-in trim ring): 14.5" W x 4.25" D x 21" L
- Complete Dimensions of Enclosures: 16.7" W x 5.78" D x 23" L
Suitable for Flush or surface mounting with a built-in trim ring.
Temperature and Humidity Ranges:
- Operating Temperature: 32°F to 120°F (0°C to 49°C)
- Humidity: 0 to 93% relative humidity (non-condensing)
Ordering Information
Model | Description |
---|---|
Panel | |
FX-3318 | Black backbox and red door enclosure. Comes complete with main board, power supply, transformer and main display. |
Annunciators | |
RAM-3318-LCD | Remote Annunciator with 4-line LCD display |
RAX-LCD-LITE | Remote Annunciator with 4-Line LCD display |
SRM-312R | Smart Relay module with red enclosure. Can support up to 12 relays |
RAM-1016TZDS | 16 Point remote annunciator chassis with 16 trouble LED's |
RAM-1032TZDS | 32 Point Remote Annunciator with 32 Trouble LED's |
MGD-32 | Graphic Annunciator |
AGD-048 | Graphic Annunciator Adder Driver board |
Optional Adder Modules | |
PR-300 | Polarity reversal and city tie module |
PCS-100 | Power Supply interface board. Use for powering 3G4010 and 3G4010CF universal wireless alarm communicator. |
Enclosures for Remote Annunciators | |
BB-1001D | Annunciator Enclosure - Houses 1 module (White) |
BB-1001DR | Annunciator Enclosure - Houses 1 module (Red) |
BB-1001DS | Annunciator Enclosure - Houses 1 module (Stainless Steel) |
BB-1002D | Annunciator Enclosure - Houses 2 modules (White) |
BB-1002DR | Annunciator Enclosure - Houses 2 modules (Red) |
BB-1002DS | Annunciator Enclosure - Houses 2 modules (Stainless Steel) |
BB-1003D | Annunciator Enclosure - Houses 3 modules (White) |
BB-1003DR | Annunciator Enclosure - Houses 3 modules (Red) |
BB-1003DS | Annunciator Enclosure - Houses 3 modules (Stainless Steel) |
Other | |
MP-300 | End of Line resistor plate. 3K9. |
BC-160R | External Battery, red cabinet |
BAT-12V12A | Battery 12AH |
BAT-12V18A | Battery 18AH |
BAT-12V26A | Battery 26AH |
RT1 | Common, remote trouble indicator, buzzer and LED |
Note: *Please see manual for list of compatible devices