Mircom FX-400 Addressable Fire Alarm Control Panel
Description
The Mircom FX-400 is an Addressable Fire Alarm Control Panel, ideal for small to medium jobs. The FX-400 is shipped pre-assembled with the main board, power supply, transformer, main display, black backbox, and a black or red door enclosure.
The FX-400 is compatible with MGC devices (MIX-4000 Series), including photoelectric duct smoke detectors and multi-modules. It features one addressable (SLC) loop with a maximum of 240 MGC devices in total. The FX-400 is equipped with a built-in POTs dialer, providing a means to communicate panel status to a remote central monitoring station using two dedicated phone lines.
Features
- 4 x 20 LCD display
- One addressable (SLC) loop with a maximum of 240 MGC devices (MIX-4000 series) in total. Class A, Class X or Class B analog loop(s).
- SLC current capability is 200mA in standby and 400mA in alarm. SLC maximum line resistance 40 Ohms and maximum line capacitance 0.47uF.
- Flexible zones and group configuration options allowing for grouped inputs and outputs.
- Compatible with MGC devices (MIX-4000 Series) including photoelectric duct smoke detector and multi-modules.
- Device sub-addressing which saves physical address space for multi-modules, sounder bases, relay bases and dual input modules.
- Compatible with conventional detectors using MGC MIX-4042 Conventional Zone module.
- Four Power Limited Class B, Class A NAC circuits (max 1.5 Amps each - 5.0 Amps total).
- NAC circuits may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or auxiliary power output. The audible signal may be Steady, Temporal Code, California Code, or March Time.
- Supports sync strobe protocols from major manufacturers.
- USB port on core board for simple programming and firmware upgrade by local keypad or PC.
- Auto-Configuration through the main display to correlate all detected inputs to all outputs.
- Configurable Signal Silence Inhibit, Auto Signal Silence, and One-Man Walk Test. Supports Auto Suite Silence.
- Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
- Additional outputs include connections for a remote trouble indicator, reverse polarity module, and up to seven remote annunciators.
- Built-in POTs dialer which allows for the reporting of events to a monitoring facility. The UDACT/Digital Communicator can be configured for single or dual line operation and uses the Security Industry Association (SIA) and Ademco Contact ID protocols.
- Bypass modules IPS-2424DS and IPS-4848DS can be used when connected to this panel as remote annunciators. These modules are mounted into a series of enclosures and connected to the RAM-3318-LCD.
- Two event history logs comprised of a 400 event alarm log for alarm related events and a 400 event general log for all other events.
- Buzzer Silence can be repurposed as Auxiliary Reset.
- The addressable devices will not flash their LEDs when no flashing flag is enabled.
Cabinet Dimensions
Dimensions | |
---|---|
Dimensions of Enclosure (minus built in trim ring) | 14.5" W x 4.25" D x 21" H (36.83 cm x 10.79cm x 53.34cm) |
Complete Dimensions of Enclosures | 16.7" W x 5.7" D x 23" H (42.42cm x 14.48 x 58.42cm) |
Electrical Specifications
Primary Input Power | 120VAC 60Hz / 240VAC 50Hz 1.81 Amp / 0.98 Amp (primary) |
Battery Type | 24VDC Gel Cell / Sealed lead acid |
Temperature and Humidity Ranges | Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 0 to 93% relative humidity (noncondensing) |
System Components
RAM-3318-LCD Remote Annunciator
The RAM-3318-LCD Remote Annunciator is used as a component of an FX-400 Fire Alarm System. It provides an exact mimic of the FX-400 display at a remote location. The display is four lines, 20 characters back-lit alphanumeric LCD. It displays information regarding the panel, its circuits, and devices. An on-screen cursor is controlled by the cursor buttons for menu selection and control. The RAM-3318-LCD occupies one display position in the BB-1000 enclosure.
RAX-LCD-LITE Remote LCD Annunciator
The FX-400 also supports the RAX-LCD-LITE Remote LCD Annunciator. It is equipped with a large 4-line x 20-character back-lit alphanumeric LCD display that uses a simple menu system complete with a directional keypad and switches for Enter, Menu, Cancel and Info. The RAX-LCD-LITE occupies one display position in the BB-1000 enclosures.
RAM-1032TZDS-CC Conformal Coated Main Remote LED Annunciator
The RAM-1032TZDS-CC Conformal Coated Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM-1032TZDS-CC has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. Each display point can be identified by the slide-in label that slides in beside the LED. The RAM-1032TZDS-CC occupies one display position in the BB-1001WP(R)A or BB-1002WP(R)A enclosures.
RAM-1032TZDS Main Remote LED Annunciator
The RAM-1032TZDS Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM-1032TZDS has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. The RAM-1032TZDS occupies one display position in the BB-1000 enclosure.
RAX-1048TZDS-CC Conformal Coated Programmable LED Annunciator Module
The RAX-1048TZDS-CC Conformal Coated Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDS-CC connects to the main control unit or main annunciator module (RAM-1032TZDS) when mounted remotely. Each display point can be identified by the slide-in label that slides in besides the LED. The RAX-1048TZDS occupies one display position in the BB-1001WP(R)A or BB-1002WP(R)A Series enclosures.
RAX-1048TZDS Programmable LED Annunciator Module
The RAX-1048TZDS Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDS connects to the main control unit or main annunciator module (RAM-1032TZDS) when mounted remotely. Each display point can be identified by the slide-in label that slides in beside the LED. The RAX-1048TZDS occupies one display position in the BB-1000 Series enclosures.
PS-2424DS Programmable Input Switches Module
The IPS-2424DS provides 24 programmable switches that can be configured for zone bypass. The IPS-2424DS connects to the main panel or the remote LCD annunciator when mounted remotely. The IPS-2424DS occupies one display position in the BB-1000 Series enclosures.
IPS-4848DS Programmable Input Switches Module
The IPS-4848DS provides 48 programmable switches that can be configured for zone bypass. The IPS-4848DS connects to the main control unit or the the remote LCD annunciator when mounted remotely. The IPS-4848DS occupies one display position in the BB-1000 Series enclosures.
AGD-048 Graphic Annunciator Adder Driver Board
The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 Master Graphic Driver modules. The AGD-048 will support an additional 48 supervised outputs. As with the master modules, the AGD-048 will support both LEDs and incandescent lamps.
UIMA4 Interface for Configuring MGC Fire Panels
The UIMA4 is an interface for configuring FX-400. The UIMA4's ribbon cable can be disconnected and replaced with the replacement part number RPL-WC-25022 (it comes with 3 replacement cables). The UIMA4 interface has 3 connectors: 9 pin male serial connector, USB B female connector, and 10 pin female connector.
MGD-32 Master Graphic Driver Module
For use with FX-400 Fire Alarm Control Panels. The MGD-32 Master Graphic Driver Module provides common control inputs for the switches such as System Reset, Signal Silence, Auxiliary Disconnect, Fire Drill, Lamp Test and Acknowledge.
PR-300 Polarity Reversal/City Tie Module
The PR-300 provides outputs for city box and polarity reversal applications. As a city tie module, the PR300 provides an interface between the control panel indicating circuits and a master box. It provides off-premises signal transmission for systems that must comply with NFPA requirements for Auxiliary Protective Systems. As a polarity reversal module, the PR-300 provides an interface between the control panel and a reverse polarity receiver.
RTI-1 Trouble Remote Indicator
Mircom's Remote Trouble Indicator provides remote annunciation of fire alarm troubles. The RTI-1 mounts onto a standard single gang electrical box. The RTI-1 can be used with any of Mircom's fire alarm control panels.
MP-300 End of Line Plates
Mircom's MP-300 is a 3.9K End Of Line resistor for use with Mircom conventional panels and detection circuits.
Enclosures
BB-1001WP(R)A Outdoor Weather Protected Enclosure
The BB-1001WP(R)A is a complete enclosure that comes with either a RED or WHITE door, a black back-box, two keys and a durable lock at the top of the door. The door comes hinged to the bottom side of the box for added weather protection. The box is capable of handling one RAM-1032TZDS-CC Main Annunciator Chassis which provides up to 32 points of annunciation. RAM-1032TZDS-CC is ordered separately to match UL, ULC installation requirements.
Note: there is no need for thermostat or heater. RAM-1032TZDS-CC must be ordered separately to match UL, ULC installation requirements.
Dimensions | Rated for Outdoor Environment | Wet Location |
---|---|---|
11-5/32" H x 12-15/16" W x 3-1/2" (283mm x 329mm x 89mm) | +50°C to -40°C (-122°F to -40°F) | 95% R.H. @60°C |
BB-1002WP(R)A Outdoor Weather Protected Enclosure
The BB-1002WP(R)A is a complete enclosure that comes with either a RED or WHITE door, a black back-box, two keys and a durable lock at the top of the door. The door comes hinged to the bottom side of the box for added weather protection. The box is capable of handling one RAM-1032TZDS-CC Main Annunciator Chassis which provides up to 32 points of annunciation and one RAX1048TZDS-CC Adder Annunciator, which provides up to 48 points of annunciation. RAM-1032TZDS-CC and RAX1048TZDS-CC are ordered separately to match the UL, ULC installation requirements.
Note: there is no need for thermostat or heater. RAM-1032TZDS-CC and RAX-1048TZDS-CC must be ordered separately to match UL, ULC installation requirements.
Dimensions | Rated for Outdoor Environment | Wet Location |
---|---|---|
17-15/16" H x 12-15/16" W x 3-1/2" (456mm x 329mm x 89mm) | +50°C to -40°C (-122°F to -40°F) | 95% R.H. @60°C |
SRM-312R Smart Relay Module with Red Enclosure
The SRM-312R provides twelve configurable relay circuits, rated @ 28 VDC, 1 amp (resistive). Each circuit can be configured as a Normally Open (N.O.) or Normally Closed (N.C.) contact. Each relay is equipped with an LED that is lit when the relay is energized. The relays can be configured as relay per zone (1 to 1), Common on Alarm, Common on Supervisory or programmable for a logical or adjacent zone configuration. An adjacent zone configuration will turn on an adjacent zone when the configured zone is active. A chaining configuration allows for multiple relays to turn on. The SRM-312R is DIP switch configurable and connects to the RS-485 bus. The SRM-312R comes complete with a red enclosure and a CAT-30 lock and key.
BB-1001/2/3 Remote Annunciator Enclosures
The BB-1000 Series comes complete with a backbox, door and hinge. The enclosures doors come with Lexan windows, two keys and a durable lock. The enclosures can handle the RAM-1032TZDS, RAM-3318-LCD, RAXN-LCD-LITE, Main Annunciator Chassis.
BB-1001D/DR/DS/DB | 9" H x 12.75" W x 1.85" D |
BB-1002D/DR/DS/DB | 18" H x 12.75" W x 1.85" D |
BB-1003D/DR/DS/DB | 26.4" H x 12.75" W x 1.85" D |
Ordering Information
Model | Description |
---|---|
Panel | |
FX-400B | Addressable Fire Alarm Control Panel - Black door |
FX-400R | Addressable Fire Alarm Control Panel - Red door |
Displays | |
RAM-3318-LCD | Remote Annunciator with 4-Line LCD Display |
RAX-LCD-LITE | Remote Annunciator with 4-Line LCD Display |
RAM-1032TZDS | 32 Point Remote Main Annunciator with 32 Trouble and Alarm LEDs |
RAM-1032TZDS-CC | Conformal Coated 32 Point Remote Main Annunciator with 32 Trouble and Alarm LEDs |
RAX-1048TZDS | Adder Annunciator Chassis c/w 48 Bi-Colored LEDs |
RAX-1048TZDS-CC | Conformal Coated Adder Annunciator Chassis c/w 48 Bi-Colored LEDs. |
IPS-2424DS | Programmable Input Switches Module with 24 switches |
PS-4848DS | Programmable Input Switches Module with 48 switches |
MGD-32 | Master Graphic Driver Board |
AGD-048 | Adder Graphic Driver Board |
SRM-312R | Smart Relay Module with Red Enclosure. Supports up to 12 relays |
Optional Adder Modules | |
PR-300 | Polarity reversal and City Tie Module |
Enclosures | |
BB-1001D | White Remote Annunciator Enclosure. Houses one module. |
BB-1001DR | Red Remote Annunciator Enclosure. Houses one module. |
BB-1001DS | Stainless Steel Remote Annunciator Enclosure. Houses one module. |
BB-1001DB | Black Remote Annunciator Enclosure. Houses one module |
BB-1002D | White Remote Annunciator Enclosure. Houses two modules. |
BB-1002DR | Red Remote Annunciator Enclosure. Houses two modules. |
BB-1002DS | Stainless Steel Remote Annunciator Enclosure. Houses two modules. |
BB-1002DB | Black Remote Annunciator Enclosure. Houses two modules. |
BB-1003D | White Remote Annunciator Enclosure. Houses three modules. |
BB-1003DR | Red Remote Annunciator Enclosure. Houses three modules. |
BB-1003DS | Stainless Steel Annunciator Enclosure. Houses three modules. |
BB-1003DB | Black Annunciator Enclosure. Houses three modules. |
BB-1001WPA | White Weather Protected Enclosure. Houses one module. |
BB-1001WPRA | Red Weather Protected Enclosure. Houses one module. |
BB-1002WPA | White Weather Protected Enclosure. Houses two modules. |
BB-1002WPRA | Red Weather Protected Enclosure. Houses two modules. |
Accessories | |
RTI-1 | Common Remote Trouble Indicator, Buzzer and LED |
MP-300 | End of Line Resistor plate. 3K9 |
BC-160R | External Battery Cabinet - Red |
BAT-12V12A | Battery 12AH |
BAT-12V18A | Battery 18AH |
BAT-12V26A | Battery 26AH (To house BAT-12V26A (26 AH) batteries, an external BC-160R Battery Cabinet is required.) |
UIMA4 | Interface for Configuring MGC Fire Panels |
MGC-CONFIG-KIT4 | Fire Panel Configuration KIT with UIMA4 |
RPL-WC-25022 | Replacement Ribbon Cable for UIMA4 (Pack of 3) |
ARW-VESP211-KIT | 1-port Ethernet Serial Server Kit Kit includes: 1 x 1-port Ethernet Serial Server 1 x DB9 Female to 5-pin 3.8mm Terminal Block RS485 Adapter 1 x DIN Rail Kit |
MGC Devices
Model | Description |
---|---|
MIX-4001 | 6" Diameter Base |
MIX-4002 | 4" Diameter Base |
MIX-4003-S | 4000 Series Sounder Base |
MIX-4003-R | 4000 Series Relay Base |
MIX-4003-LF | 4000 Series Low Frequency Sounder Base |
MIX-4010 | Photoelectric Smoke Sensor |
MIX-4010-ISO | Photoelectric Smoke Sensor with Built-in Short Circuit Isolator |
MIX-4020 | Multi-Sensor Detector |
MIX-4020-ISO | Multi-Sensor Detector with Built-in Short Circuit Isolator |
MIX-4030 | Tri-Mode Heat Detector |
MIX-4030-ISO | Tri-Mode Heat Detector with Built-in Short Circuit Isolator |
MIX-4010-DUCT | 4000 Series Addressable Photoelectric Duct Smoke Detector |
MIX-4010-D | Series Non-Isolated Photoelectric Duct Detector Sensor head (For replacement only) |
MIX-4040-M | 4000 Series Multi Input Module (6 Class A/12 class B) |
MIX-4045-M | 4000 Series Multi Relay Module (8 form C SPDT contacts) |
MIX-4070-M | 4000 Series Multi Isolator Module (8 isolator sections) |
MIX-4040 | Dual Input Module |
MIX-4041 | Mini Dual Input Module |
MIX-4042 | Conventional Zone Module |
MIX-4045 | Dual Relay Module |
MIX-4046 | Supervised Output Module |
MIX-4050 | Sync Module |
MIX-4070 | Short Circuit Isolator Module |
MIX-4090 | MGC Devices Programmer |
MS-401MPU | Addressable Single Stage Manual Station MP |
MS-407MPU | Addressable Single Stage Manual Station MP with Additional N.C. Switch |
MS-710MPU | Addressable Key-Resettable Single Stage Dual Action Manual Station MP |
MPS-810MPU | MP 1 Stage addressable double action pull station, UL |
MGC Devices Accessories | |
DUCT-ST1 | Sampling tube width up to 1ft (0.3m) for MIX-4010-DUCT |
DUCT-ST2 | Sampling tube widths 1ft to 2ft (0.6m) for MIX-4010-DUCT |
DUCT-ST5 | Sampling tube widths 2ft to 5ft (0.6m) for MIX-4010-DUCT |
DUCT-EXTEND | Sampling Tube Extension (3.5 ft) for MIX-4010-DUCT |
DUCT-MB | Mounting bracket for MIX-4010-DUCT |
DUCT-RG | Rubber gasket for MIX-4010-DUCT (Pack of 10 units) |
BB-800 | Surface back box for 800 Series manual station |
BB-700 | Series 700 Surface mount back box |
BB-700WP | Series 700 weatherproof surface mount back box |
BB-300 | Mounting box, surface mount, RED |
Related Documents
![]() |
Mircom FX-400 Addressable Fire Alarm Control Panel Mircom FX-400 is an addressable fire alarm control panel ideal for small to medium-sized installations. This document outlines its features, specifications, and compatible components, including remote annunciators, input modules, and cabinets. |
![]() |
Mircom FX-400 Fire Alarm Control Panel Installation and Operation Manual This Installation and Operation Manual provides comprehensive guidance for the Mircom FX-400 Addressable Fire Alarm Control Panel (FACP). It details system features, component compatibility, wiring diagrams, configuration options, operational procedures, and troubleshooting tips for ensuring effective fire safety system deployment. |
![]() |
Mircom MIX-4090 Device Programmer: Installation and Maintenance Guide Comprehensive guide for installing and maintaining the Mircom MIX-4090 Device Programmer, detailing its features, operation, address programming, and parameter reading for MIX-4000 series fire alarm devices. |
![]() |
Mircom FX-400 Intelligent Fire Alarm Control Panel - Features and Components Comprehensive overview of the Mircom FX-400 Addressable Fire Alarm Control Panel, detailing its features, system components, enclosures, and ordering information. This panel is designed for small to medium fire alarm installations. |
![]() |
Mircom FX-3500 Fire Alarm Control Panel Installation and Operation Manual Comprehensive guide for the installation and operation of the Mircom FX-3500 Addressable Fire Alarm Control Panel, detailing system components, wiring, configuration, and features for effective fire safety. |
![]() |
Mircom FX-401 Addressable Fire Alarm Control Panel Mircom FX-401 is a versatile addressable fire alarm control panel designed for small to medium-sized installations. This document details its features, specifications, and compatible components, including remote annunciators, input modules, and cabinets. |
![]() |
Mircom MIX-4045 Dual Relay Module Installation and Maintenance Instructions Detailed installation and maintenance guide for the Mircom MIX-4045 Dual Relay Module, covering module description, mounting, specifications, and wiring diagrams for fire alarm systems. |
![]() |
Mircom FX-400 Intelligent Fire Alarm Control Panel | Product Overview Discover the Mircom FX-400, an intelligent addressable fire alarm control panel designed for small to medium jobs. Learn about its features, system components, and compatibility for robust fire detection and notification. |