R. STAHL Miniature Circuit Breaker
Model: 8530/1-MCB-STA101-C20-500-2
Art. No.: 293999
Key Features
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Modular design for simple replacement or expansion
- Easy installation on mounting rails in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching
- Padlockable design (accessories) for maintenance safety
Product Overview
R. STAHL 8530 series miniature circuit breakers are overcurrent devices offering excellent current limiting for short circuits and high switching capacity (10, 15, or 25 kA). They reduce load on cables and provide high selectivity for upstream fuses. These components feature a modular design, available in 1- to 4-pole versions with rated currents from 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEx gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX)
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230 V |
Rated operational current | 20 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 1-pole |
Ambient Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature (Fahrenheit): -40 °F ... 158 °F
- Ambient temperature note: Deviating ambient temperatures based on current certificates available on request
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplast
- Connection cross section min.: 1.5 mm²
- Connection cross-section max.: 25 mm²
- Connection cross-section AWG min.: 16 AWG
- Connection cross-section AWG max.: 4 AWG
- Connection cross-section 2 min.: 1.5 mm²
- Connection cross-section 2 max.: 10 mm²
- Connection cross-section 2 AWG min.: 16 AWG
- Connection cross-section 2 AWG max.: 8 AWG
- Min. aux. cont. con. cr.-sect.: 0.5 mm²
- Max. aux. cont. conn. cr.-sec.: 4 mm²
- Min. aux. co. con. cr.-se. AWG: 18 (unece.unit.AWG)
- Connection cross-section of auxiliary contact AWG max.: 14 (unece.unit.AWG)
- Min. tightening torque: 2 N·m
- Max. tightening torque: 3 N·m
- Connection cross-section note: 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16/10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions.
Dimensions
- Width: 65 mm (2.56 in)
- Length: 165 mm (6.5 in)
- Mounting depth: 138.3 mm (5.44 in)
Weight
- Weight: 1 kg (2.205 lb)
Mounting / Installation
- Tightening torque: 2-3 N·m
- Tightening torque lbf in: 17.7 to 26.6 lbf-in
- Tightening torque auxiliary contact: 0.4-0.6 N·m
- Tightening torque auxiliary contact lbf in: 3.5 to 5.3 lbf in
Technical Drawings
(Diagrams are described textually below)
Tripping Characteristic Curve: A graph showing tripping time in seconds and minutes against multiples of rated current. The curve is labeled 'C' for tripping characteristic. It illustrates tripping times for AC and DC currents in a cold state.
Dimensional Drawings:
- Main Unit: Shows a front view, side view, and top view of the miniature circuit breaker. Dimensions are provided in mm and inches. Key dimensions include width (65 mm / 2.56 in), height (165 mm / 6.5 in), and mounting depth (138.3 mm / 5.44 in).
- Side View Detail: A close-up of the side of the unit, highlighting mounting features and connections.
Accessories
4-way locking device
- Description: A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
- Art. No.: 227232
Cylinder lock
- Description: For closing (bracket Ø 3).
- Art. No.: 107115
Fastening set
- Description: A fastening set for securing the component on the mounting plate without a DIN rail.
- Art. No.: 276618
Company Information
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com