R. STAHL 8530/1-MCB-STA103N-C32-000-4 Circuit Breaker

Article No.: 293859

Product Description

The R. STAHL 8530/1-MCB-STA103N-C32-000-4 circuit breaker is part of the system technology components. It offers good current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA), leading to reduced load on electrical lines and improved selectivity with connected fuses. The modules feature a modular design, are available in 1 to 4-pole versions, and support nominal currents from 0.5–63 A. Maximum mounting capacity is 4.5 division units.

Key features include:

Technical Data

Explosion Protection

Attribute Value
Applications (zones) 1, 2
Applications (zones) Note Can be used in zones 21/22 with Ex tb/tc enclosure protection
IECEX gas homologation IECEX FMG 19.0029U
IECEx gas explosion protection Ex db eb IIC Gb
ATEX gas homologation FM19ATEX0191U
ATEX gas explosion protection II 2 G Ex db eb IIC Gb
Certifications ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformity Certificate of conformity (ATEX)

Electrical Data

Attribute Value
Rated operating voltage AC 230/400 V
Rated operating current 32 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 104
Mechanical service life 2 x 104
1st auxiliary function none
1st auxiliary function voltage -
Maximum current 1st auxiliary function -
2nd auxiliary function none
Maximum voltage 2nd aux. function CC -
Trip characteristic C
Number of poles 3 pole + N

Environmental Conditions

Attribute Value
Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °F ... 158 °F
Ambient temperature Note Divergent ambient temperatures based on current certificates upon request

Mechanical Data

Attribute Value
Degree of protection (IP) (IEC 60529) IP2X
Enclosure material Thermoplastic
Connection terminal cross-section min. 1.5 mm²
Connection terminal cross-section max. 25 mm²
Connection terminal AWG min. 16 AWG
Connection terminal AWG max. 4 AWG
Connection terminal 2 cross-section min. 1.5 mm²
Connection terminal 2 cross-section max. 10 mm²
Connection terminal 2 AWG min. 16 AWG
Connection terminal 2 AWG max. 8 AWG
Tightening torque min. 2 N·m
Tightening torque max. 3 N·m
Connection terminal Note 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only a maximum cross-sectional difference between the upper and lower chamber can be connected). Permitted connection cross-section combinations are listed in the operating instructions.
Width 110 mm (4.33 in)
Length 165 mm (6.5 in)
Installation depth 138.3 mm (5.44 in)
Weight 1.8 kg (3.969 lb)
Mounting/Installation tightening torque 2-3 N·m (17.7 ... 26.6 lbf-in)
Auxiliary contact tightening torque 0.4–0.6 Nm (3.5 ... 5.3 lbf in)

Technical Diagrams

Trip Curve Characteristic: The document includes a graph illustrating the trip characteristic 'C' for AC and DC, showing the relationship between the multiple of the rated current (I/In) and the tripping time in seconds and minutes. This curve indicates the time it takes for the circuit breaker to trip under various overcurrent conditions.

Dimensional Drawings: Several diagrams provide the dimensions of the circuit breaker and its mounting configurations. These include:

Accessories

The following accessories are available for the circuit breaker:

Accessory Description Article No.
Cylinder lock For locking (shackle Ø 3) 107115
Quadruple locking device Locking/tagging tool for individual component locking using up to 4 cylinder locks. 227232
Fixing kit A fixing kit for mounting the component on the mounting plate without a top-hat rail. 276618

General Information

R. STAHL Schaltgeräte GmbH reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103n-c32-000-4-293859-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C32-000-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Line Protection Circuit Breaker Technical Data
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C32-000-4 line protection circuit breaker, including electrical characteristics, explosion protection, mechanical features, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-B16-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B16-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 21/22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C25-000-4 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C20-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C20-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C10-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.