R. STAHL 8530/1-MCB-STA103N-C32-000-4 Line Protection Circuit Breaker

Article No. 293859

System Components for System Technology

Disyuntor Disjonct. line protection

Article No. 293859

The R. STAHL series 8530 line protection circuit breakers offer good current limitation during short circuits and a high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity with upstream fuses. The components are modular and available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key features include:

Technical Characteristics

Explosion Protection

Application Area (Zones) 1, 2
Application Area (Zones) Note Usable in Zone 21 / 22 with protection by housing Ex tb / tc
IECEx Gas Certificate IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Gas Certificate FM19ATEX0191U
ATEX Gas Explosion Protection II 2 G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity Certificate of Conformity (ATEX)

Electrical Characteristics

Rated operational voltage AC 230/400 V
Rated service current 32 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 104
Mechanical service life 2 x 104
1st auxiliary function None
Voltage 1st auxiliary function AC -
Max. current 1st auxiliary function -
2nd auxiliary function None
Max. voltage 2nd auxiliary function DC -
Tripping characteristic C
Number of poles 3 poles + N

Ambient Conditions

Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °F ... 158 °F
Ambient temperature -40°F ... +158°F
Ambient temperature Note Ambient temperatures different from the base of the current certificates, on request

Mechanical Characteristics

Degree of protection (IP) (IEC 60529) IP2X
Housing material Thermoplastic
Minimum connection cross-section 1.5 mm²
Maximum connection cross-section 25 mm²
Connection cross-section AWG min. 16 AWG
Connection cross-section AWG max. 4 AWG
Connection cross-section 2 min. 1.5 mm²
Connection cross-section 2 max. 10 mm²
Connection cross-section 2 AWG min. 16 AWG
Connection cross-section 2 AWG max. 8 AWG
Tightening torque min. 2 N·m
Tightening torque max. 3 N·m
Connection cross-section Note 2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.)
Allowed combination possibilities for connection cross-sections are indicated in the operating instructions.

Dimensions

Width 110 mm
Width in inches 4.33 in
Length 165 mm
Length in inches 6.5 in
Mounting depth 138.3 mm
Mounting depth inches 5.44 in

Weight

Weight 1.8 kg
Weight 3.969 lb

Mounting / Installation

Tightening torque 2–3 N·m
Tightening torque in lbf in 17.7 ... 26.6 lbf-in
Auxiliary contact tightening torque 0.4–0.6 Nm
Auxiliary contact tightening torque lbf in 3.5 ... 5.3 lbf in

Technical Drawings

Subject to change without notice.

Tripping Characteristic Curve

Tripping characteristic C

Diagram Description: A graph showing tripping time in seconds versus multiples of rated current (I/In). The curve is labeled "Tripping characteristic C" and shows different curves for AC and DC, with a "limit from cold state" indicated.

Overall Dimensions (all dimensions in mm [inches])

Subject to change without notice.

Diagram Description: Technical drawings showing the dimensions of the circuit breaker. One drawing shows the overall dimensions with labels for width, length, and depth. Another drawing shows the unit as "8530/1; 4 division units".

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.

Item Description Article No.
Quadruple locking/unlocking system for individual locking of the component using up to 4 cylinder locks. 227232

Fixing Kit

Item Description Article No.
A fixing kit to attach the component to the mounting plate without a DIN rail. 276618

Cylinder Lock

Item Description Article No.
For locking (stirrup Ø 3) 107115

Subject to change of technical characteristics, dimensions, weights, construction types, and delivery possibilities without notice. The figures are for indicative purposes only.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103n-c32-000-4-293859-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C32-000-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C32-000-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C32-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-B32-000-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B32-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C10-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-B6-000-4 Line Protection Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B6-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-B63-000-4 Line Protection Circuit Breaker Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-B63-000-4 line protection circuit breaker, including electrical characteristics, explosion protection, mechanical features, and accessories.