R. STAHL 8530/1-MCB-STA103N-C32-000-4 Line Protection Circuit Breaker
Article No. 293859
System Components for System Technology
Disyuntor Disjonct. line protection
Article No. 293859
The R. STAHL series 8530 line protection circuit breakers offer good current limitation during short circuits and a high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity with upstream fuses. The components are modular and available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key features include:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of your system thanks to the modular design of the circuit breakers
- Simple mounting by clipping onto a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic lever for safe activation and deactivation
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Characteristics
Explosion Protection
Application Area (Zones) | 1, 2 |
---|---|
Application Area (Zones) Note | Usable in Zone 21 / 22 with protection by housing Ex tb / tc |
IECEx Gas Certificate | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX Gas Certificate | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Characteristics
Rated operational voltage AC | 230/400 V |
---|---|
Rated service current | 32 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | None |
Voltage 1st auxiliary function AC | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | None |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | C |
Number of poles | 3 poles + N |
Ambient Conditions
Ambient temperature | -40 °C ... 70 °C |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature | -40°F ... +158°F |
Ambient temperature Note | Ambient temperatures different from the base of the current certificates, on request |
Mechanical Characteristics
Degree of protection (IP) (IEC 60529) | IP2X |
---|---|
Housing material | Thermoplastic |
Minimum connection cross-section | 1.5 mm² |
Maximum connection cross-section | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection cross-section Note | 2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.) |
Allowed combination possibilities for connection cross-sections are indicated in the operating instructions. |
Dimensions
Width | 110 mm |
---|---|
Width in inches | 4.33 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm |
Mounting depth inches | 5.44 in |
Weight
Weight | 1.8 kg |
---|---|
Weight | 3.969 lb |
Mounting / Installation
Tightening torque | 2–3 N·m |
---|---|
Tightening torque in lbf in | 17.7 ... 26.6 lbf-in |
Auxiliary contact tightening torque | 0.4–0.6 Nm |
Auxiliary contact tightening torque lbf in | 3.5 ... 5.3 lbf in |
Technical Drawings
Subject to change without notice.
Tripping Characteristic Curve
Tripping characteristic C
Diagram Description: A graph showing tripping time in seconds versus multiples of rated current (I/In). The curve is labeled "Tripping characteristic C" and shows different curves for AC and DC, with a "limit from cold state" indicated.
Overall Dimensions (all dimensions in mm [inches])
Subject to change without notice.
Diagram Description: Technical drawings showing the dimensions of the circuit breaker. One drawing shows the overall dimensions with labels for width, length, and depth. Another drawing shows the unit as "8530/1; 4 division units".
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Item | Description | Article No. |
---|---|---|
Quadruple locking/unlocking system for individual locking of the component using up to 4 cylinder locks. | 227232 |
Fixing Kit
Item | Description | Article No. |
---|---|---|
A fixing kit to attach the component to the mounting plate without a DIN rail. | 276618 |
Cylinder Lock
Item | Description | Article No. |
---|---|---|
For locking (stirrup Ø 3) | 107115 |
Subject to change of technical characteristics, dimensions, weights, construction types, and delivery possibilities without notice. The figures are for indicative purposes only.