R. STAHL 8530/1-MCB-STA103N-C20-000-4 Line Protection Circuit Breaker
Article Number: 293857
System Components for System Technology
Product: Disjoncteur Disjonct. protection de ligne (Line Protection Circuit Breaker)
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. This ensures minimal stress on lines and high selectivity to upstream fuses. The components are modularly designed and available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key Features:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or system extension due to modular circuit breaker design
- Simple plug-in mounting on a DIN rail in Ex e enclosures
- Fixed magnetic-thermal trip units
- Ergonomic lever for safe activation and deactivation
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Characteristics
Explosion Protection
Area of Application (Zones) | 1, 2 |
Area of Application (Zones) Note | Usable in Zone 21 / 22 with Ex tb / tc enclosure protection |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Protection Against Gas Explosion | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Protection Against Gas Explosion | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Characteristics
Rated Operational Voltage AC | 230/400 V |
Rated Service Current | 20 A |
Frequency | 50/60 Hz |
Rated Service Breaking Capacity | 10 kA |
Electrical Service Life | 2 x 104 |
Mechanical Service Life | 2 x 104 |
1st Auxiliary Function | None |
Voltage 1st Auxiliary Function AC | - |
Max. Current 1st Auxiliary Function | - |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | C |
Number of Poles | 3 poles + N |
Mechanical Characteristics
Ambient Conditions
Ambient Temperature | -40 °C ... 70 °C (-40 °F ... 158 °F) |
Ambient Temperature Note | Different ambient temperatures based on current certificates, on request |
Mechanical Specifications
Degree of Protection (IP) (IEC 60529) | IP2X |
Housing Material | Thermoplastic |
Minimum Connection Terminal Size | 1.5 mm² |
Maximum Connection Terminal Size | 25 mm² |
Minimum Connection Terminal Size AWG | 16 AWG |
Maximum Connection Terminal Size AWG | 4 AWG |
Minimum Connection Terminal Size 2 | 1.5 mm² |
Maximum Connection Terminal Size 2 | 10 mm² |
Connection Terminal Size 2 AWG min. | 16 AWG |
Connection Terminal Size 2 AWG max. | 8 AWG |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted combinations of connection terminal sizes are indicated in the operating manual. |
Dimensions
Width | 110 mm (4.33 in) |
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight
Weight | 1.8 kg (3.969 lb) |
Mounting / Installation
Tightening Torque | 2–3 N·m (17.7 ... 26.6 lbf·in) |
Auxiliary Contact Tightening Torque | 0.4–0.6 N·m (3.5 ... 5.3 lbf·in) |
Technical Drawings
Tripping Characteristic Curve C
The graph shows the tripping characteristic for a Type C circuit breaker, indicating the relationship between multiples of the rated current and tripping time in seconds and minutes. It is divided into AC and DC curves, with a note indicating the limit from the cold state.
Overall Dimensions (all dimensions in mm [inches])
Diagram showing the external dimensions of the circuit breaker, including width, length, and mounting depth. It indicates the product is 8530/1; 4 division units.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article Number |
Quadruple locking device for individual locking with up to 4 cylinder locks | 227232 |
Fixing Kit
Description | Article Number |
A fixing kit for mounting the component onto a mounting plate without a DIN rail. | 276618 |
Cylinder Lock
Description | Article Number |
For locking (shackle Ø 3) | 107115 |
Subject to technical modifications, dimensions, weights, construction types, and delivery possibilities. Figures are for illustrative purposes only.