R. STAHL 8530/1-MCB-STA103-C50-500-4 Line Protection Circuit Breaker

Article Number: 293905

Product Overview

The R. STAHL 8530 series line protection circuit breakers, specifically the 8530/1-MCB-STA103-C50-500-4, offer robust current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. These components are designed for minimal load on lines and high selectivity to upstream fuses. They feature a modular design, available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key features include:

Technical Characteristics

Explosion Protection

Characteristic Specification
Application Area (Zones) 1, 2
Application Area (Zones) Note Usable in Zone 21 / 22 with protection via Ex tb / tc enclosure
IECEx Gas Certificate IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Gas Certificate FM19ATEX0191U
ATEX Gas Explosion Protection II 2G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity Certificate of Conformity (ATEX)

Electrical Characteristics

Characteristic Specification
Rated Operational Voltage AC 230/400 V
Rated Service Current 50 A
Frequency 50/60 Hz
Rated Switching Capacity 10 kA
Electrical Service Life 104
Mechanical Service Life 2 x 105
1st Auxiliary Function Auxiliary contact 1 changeover + error signal contact 1 changeover
Voltage 1st Auxiliary Function AC 230 V
Max. Current 1st Auxiliary Function 2 A
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC -
Tripping Characteristic C
Number of Poles 3-pole

Mechanical Characteristics

Characteristic Specification
Ambient Temperature -40 °C ... 70 °C
Ambient Temperature (Fahrenheit) -40 °F ... 158 °F
Ambient Temperature Note Different ambient temperatures based on current certificates, on request
Degree of Protection (IP) (IEC 60529) IP2X
Enclosure Material Thermoplastic
Connection Terminal Minimum Section 1.5 mm²
Connection Terminal Maximum Section 25 mm²
Connection Terminal AWG Min. 16 AWG
Connection Terminal AWG Max. 4 AWG
Connection Terminal 2 Minimum Section 1.5 mm²
Connection Terminal 2 Maximum Section 10 mm²
Connection Terminal 2 AWG Min. 16 AWG
Connection Terminal 2 AWG Max. 8 AWG
Connection Terminal Auxiliary Contact Min. 0.5 mm²
Connection Terminal Auxiliary Contact Max. 4 mm²
Connection Terminal Auxiliary Contact AWG Min. 18 (unece.unit.AWG)
Connection Terminal Auxiliary Contact AWG Max. 14 (unece.unit.AWG)
Tightening Torque Min. 2 N·m
Tightening Torque Max. 3 N·m
Connection Terminal Note 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted connection combinations are listed in the operating manual.
Width 110 mm (4.33 in)
Length 165 mm (6.5 in)
Mounting Depth 138.3 mm (5.44 in)
Weight 1.8 kg (3.969 lb)

Mounting / Installation

Characteristic Specification
Tightening Torque 2-3 N·m (17.7 ... 26.6 lbf-in)
Tightening Torque Auxiliary Contact 0.4-0.6 Nm (3.5 ... 5.3 lbf-in)

Technical Drawings

Tripping Characteristic Curve

A graph illustrating the tripping characteristic curve C for AC and DC, showing time in seconds versus multiple of rated current (I/In). The curve indicates the limit from a cold state.

Overall Dimensions (Enclosure Plan)

Diagrams showing the overall dimensions of the circuit breaker in millimeters and inches. The main unit is 110 mm (4.33 in) wide and 165 mm (6.50 in) long, with a mounting depth of 138.3 mm (5.44 in). It is noted as 4 division units.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual component locking using up to 4 cylinder locks.

Description Article Number
Quadruple locking/unlocking system for individual component locking with up to 4 cylinder locks. 227232

Fixing Kit

A fixing kit for mounting the component onto a mounting plate without a DIN rail.

Description Article Number
Fixing kit for mounting the component onto a mounting plate without DIN rail. 276618

Cylinder Lock

For locking (stirrup Ø 3).

Description Article Number
For locking (stirrup Ø 3). 107115

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-c50-500-4-293905-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker, including features, electrical characteristics, environmental conditions, and dimensions. Suitable for explosion protection applications.
Preview R. STAHL 8530/1-MCB-STA103-B20-500-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B20-500-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Line Protection Circuit Breaker Technical Data
Detailed technical specifications, features, and application information for the R. STAHL 8530/1-MCB-STA103-C25-500-4 line protection circuit breaker, including explosion protection data and electrical characteristics.
Preview R. STAHL 8530/1-MCB-STA103-C50-000-3 Miniature Circuit Breaker for Line Protection
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-000-3 miniature circuit breaker, designed for line protection in hazardous environments. Includes details on explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C50-500-4 circuit breaker, including features, electrical data, mechanical data, and environmental conditions. Suitable for Ex e installations.
Preview R. STAHL 8530/1-MCB-STA103-C16-500-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and dimensions for the R. STAHL 8530/1-MCB-STA103-C16-500-4 circuit breaker, including explosion protection, electrical characteristics, and mounting information.