R. STAHL 8530/1-MCB-STA103-C16-500-4 Circuit Breaker

This document provides detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C16-500-4 circuit breaker, also known by the article number 293900. This device is designed for line protection within system technology.

Key Features

Technical Characteristics

Explosion Protection

CharacteristicSpecification
Application area (zones)1, 2
Application area (zones) NoteUsable in Zone 21 / 22 with protection by Ex tb / tc enclosure
IECEx certificate gasIECEx FMG 19.0029U
IECEx protection against explosion of gasEx db eb IIC Gb
ATEX certificate gasFM19ATEX0191U
ATEX protection against explosion of gasII 2 G Ex db eb IIC Gb
CertificatesATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of conformityCertificate of conformity (ATEX)

Electrical Characteristics

CharacteristicSpecification
Rated operational voltage AC230/400 V
Rated service current16 A
Frequency50/60 Hz
Rated switching capacity10 kA
Electrical service life2 x 104
Mechanical service life2 x 104
1st auxiliary functionAuxiliary contact 1 changeover contact + signal contact 1 changeover contact
Voltage 1st auxiliary function AC230 V
Max. current 1st auxiliary function2 A
2nd auxiliary functionNone
Max. voltage 2nd auxiliary function DC-
Tripping characteristicC
Number of poles3-pole

Ambient Conditions

CharacteristicSpecification
Ambient temperature-40 °C ... 70 °C
Ambient temperature-40 °C ... 70 °C
Ambient temperature-40 °F ... 158 °F
Ambient temperature-40°F ... +158°F
Ambient temperature NoteDifferent ambient temperatures based on current certificates, on request

Mechanical Characteristics

CharacteristicSpecification
Degree of protection (IP) (IEC 60529)IP2X
Housing materialThermoplastic
Minimum connection terminal size1.5 mm²
Maximum connection terminal size25 mm²
Minimum connection terminal AWG size16 AWG
Maximum connection terminal AWG size4 AWG
Minimum connection terminal 2 size1.5 mm²
Maximum connection terminal 2 size10 mm²
Minimum connection terminal 2 AWG size16 AWG
Maximum connection terminal 2 AWG size8 AWG
Connection terminal for aux. contact min.0.5 mm²
Connection terminal for aux. contact max.4 mm²
Connection terminal for aux. contact min. AWG18 (unece.unit.AWG)
Connection terminal for aux. contact max. AWG14 (unece.unit.AWG)
Minimum tightening torque2 N·m
Maximum tightening torque3 N·m
Connection terminal Note2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.)
Width110 mm (4.33 in)
Length165 mm (6.5 in)
Mounting depth138.3 mm (5.44 in)
Weight1.8 kg (3.969 lb)

Mounting / Installation

CharacteristicSpecification
Tightening torque2-3 N·m
Tightening torque in lbf in17.7 ... 26.6 lbf-in
Tightening torque auxiliary contact0.4 – 0.6 Nm
Tightening torque auxiliary contact lbf in3.5 ... 5.3 lbf in

Technical Drawings

Technical drawings are provided, including dimensions and tripping characteristic curves. The tripping characteristic curve shows the tripping delay in seconds based on multiples of the rated current (I/In) for AC and DC.

Accessories

Note: Technical characteristics, dimensions, weight, construction types, and delivery possibilities are subject to change. Figures are for illustrative purposes only.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-c16-500-4-293900-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C16-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C16-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for system solutions in hazardous environments.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103-C16-500-4 - Technical Data and Features
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA103-C16-500-4. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C16-500-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C16-500-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-B6-500-2 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-B6-500-2 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-B16-500-2 Circuit Breaker for Line Protection
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-B16-500-2 circuit breaker for line protection, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C16-000-3 Line Protection Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C16-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C32-000-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C32-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical features, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.