R. STAHL 8530/1-MCB-STA103-C25-500-4 Line Protection Circuit Breaker

The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. This ensures minimal stress on lines and high selectivity with upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key Features

Technical Characteristics

Explosion Protection

Application Area (Zones)1, 2
Application Area (Zones) NoteUsable in Zone 21 / 22 with Ex tb / tc enclosure protection
IECEx Gas CertificateIECEx FMG 19.0029U
IECEx Gas Explosion ProtectionEx db eb IIC Gb
ATEX Gas CertificateFM19ATEX0191U
ATEX Gas Explosion ProtectionII 2 G Ex db eb IIC Gb
CertificatesATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)

Electrical Characteristics

Rated Operational Voltage AC230/400 V
Rated Service Current25 A
Frequency50/60 Hz
Rated Switching Capacity10 kA
Electrical Service Life2 x 104
Mechanical Service Life2 x 104
1st Auxiliary FunctionAuxiliary contact 1 changeover + signal contact 1 changeover
Voltage 1st Auxiliary Function AC230 V
Max. Current 1st Auxiliary Function2 A
2nd Auxiliary FunctionNone
Max. Voltage 2nd Auxiliary Function DCC
Trip CharacteristicC
Number of Poles3 poles

Ambient Conditions

Ambient Temperature-40 °C ... 70 °C
Ambient Temperature-40 °C ... 70 °C
Ambient Temperature-40 °F ... 158 °F
Ambient Temperature NoteAmbient temperatures different based on current certificates, on request

Mechanical Characteristics

Degree of Protection (IP) (IEC 60529)IP2X
Enclosure MaterialThermoplastic
Minimum Connection Terminal Size1.5 mm²
Maximum Connection Terminal Size25 mm²
Minimum AWG Connection Terminal Size16 AWG
Maximum AWG Connection Terminal Size4 AWG
Minimum Connection Terminal Size 21.5 mm²
Maximum Connection Terminal Size 210 mm²
Minimum AWG Connection Terminal Size 216 AWG
Maximum AWG Connection Terminal Size 28 AWG
Min. Connection Terminal Auxiliary0.5 mm²
Max. Connection Terminal Auxiliary4 mm²
Min. AWG Connection Terminal Auxiliary18 (unece.unit.AWG)
Max. AWG Connection Terminal Auxiliary14 (unece.unit.AWG)
Minimum Tightening Torque2 N·m
Maximum Tightening Torque3 N·m
Connection Terminal Note2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.)
Width110 mm (4.33 in)
Length165 mm (6.5 in)
Mounting Depth138.3 mm (5.44 in)
Weight1.8 kg (3.969 lb)

Mounting / Installation

Tightening Torque2-3 N·m (17.7 ... 26.6 lbf-in)
Tightening Torque Auxiliary Contact0.4–0.6 Nm (3.5 ... 5.3 lbf-in)

Technical Drawings

Diagrams showing dimensions and tripping characteristics are available. The tripping characteristic curve C is provided for AC and DC.

Dimensions:

Tripping Characteristic Curve C:

A graph illustrates the tripping delay in seconds versus the multiple of the rated current (I/In) for AC and DC, showing the limit from a cold state.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual component locking using up to 4 cylinder locks.

DescriptionPart No.
Quadruple locking device227232

Fixing Kit

A fixing kit for attaching the component to a mounting plate without a DIN rail.

DescriptionPart No.
Fixing kit for mounting without DIN rail276618

Cylinder Lock

For locking (shackle Ø 3).

DescriptionPart No.
Cylinder lock107115

Technical specifications, dimensions, weights, construction types, and delivery options are subject to change without notice. Figures are for illustrative purposes only.

Contact Information:

R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-c25-500-4-293902-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL Miniature Circuit Breaker 8530/1-MCB-STA103-C25-500-4: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530 series miniature circuit breaker (MCB), model 8530/1-MCB-STA103-C25-500-4. Includes information on explosion protection, electrical data, mechanical data, and mounting.
Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103-C25-500-4 circuit breaker, including explosion protection, electrical data, mechanical data, and dimensions.
Preview R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker, including features, electrical characteristics, environmental conditions, and dimensions. Suitable for explosion protection applications.
Preview R. STAHL 8530/1-MCB-STA103-C25-000-3 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103-C25-000-3 circuit breaker, designed for line protection in demanding environments.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Line Protection Circuit Breaker Technical Data
Detailed technical specifications and features for the R. STAHL 8530/1-MCB-STA103N-C25-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-B20-500-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B20-500-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.