R. STAHL 8530/1-MCB-STA103-B20-500-4 Line Protection Circuit Breaker

Article Number: 293887

Key Features

Product Overview

The R. STAHL 8530 series line protection circuit breakers offer good current limitation in case of short circuits and a high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modularly designed and available in 1 to 4 pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Technical Characteristics

Explosion Protection

Feature Specification
Application Domain (Zones) 1, 2
Application Domain (Zones) Note Usable in Zone 21 / 22 with Ex tb / tc enclosure protection
IECEx Gas Certificate IECEx FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX Gas Certificate FM19ATEX0191U
ATEX Gas Explosion Protection II 2G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity ATEX Conformity Certificate

Electrical Characteristics

Feature Specification
Rated Operational Voltage AC 230/400 V
Rated Service Current 20 A
Frequency 50/60 Hz
Rated Switching Capacity 10 kA
Electrical Service Life 2 x 10⁴
Mechanical Service Life 2 x 10⁴
1st Auxiliary Function Auxiliary contact 1 changeover contact + signal contact 1 changeover contact
Voltage 1st Auxiliary Function AC 230 V
Max. Current 1st Auxiliary Function 2 A
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC -
Tripping Characteristic B
Number of Poles 3-pole

Ambient Conditions

Feature Specification
Ambient Temperature -40 °C ... 70 °C (-40°F ... +158°F)
Ambient Temperature Note Ambient temperatures different from current certificates, upon request

Mechanical Characteristics

Feature Specification
Degree of Protection (IP) (IEC 60529) IP2X
Enclosure Material Thermoplastic
Minimum Connection Terminal Size 1.5 mm²
Maximum Connection Terminal Size 25 mm²
Minimum AWG Connection Terminal Size 16 AWG
Maximum AWG Connection Terminal Size 4 AWG
Minimum Connection Terminal Size 2 1.5 mm²
Maximum Connection Terminal Size 2 10 mm²
Minimum AWG Connection Terminal Size 2 16 AWG
Maximum AWG Connection Terminal Size 2 8 AWG
Min. Connection Terminal Size (Auxiliary) 0.5 mm²
Max. Connection Terminal Size (Auxiliary) 4 mm²
Min. AWG Connection Terminal Size (Auxiliary) 18 (unece.unit.AWG)
Max. AWG Connection Terminal Size (Auxiliary) 14 (unece.unit.AWG)
Minimum Tightening Torque 2 N·m
Maximum Tightening Torque 3 N·m
Connection Terminal Size Note Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.) Authorized connection combination possibilities are indicated in the operating instructions.

Dimensions

Feature Metric Imperial
Width 110 mm 4.33 in
Length 165 mm 6.5 in
Mounting Depth 138.3 mm 5.44 in
Weight 1.8 kg 3.969 lb

Mounting / Installation

Feature Specification
Tightening Torque 2-3 N·m (17.7 ... 26.6 lbf-in)
Tightening Torque Auxiliary Contact 0.4-0.6 N·m (3.5 ... 5.3 lbf-in)

Technical Drawings

Diagrams illustrating tripping characteristics and overall dimensions are provided. The tripping characteristic curve shows the tripping limit from a cold state for AC and DC currents. The overall dimensions plan shows the unit in mm and inches, indicating width, length, mounting depth, and various internal dimensions.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.

Description Article Number
Quadruple locking/unlocking system for individual locking of the component using up to 4 cylinder locks. 227232

Fixing Kit

A fixing kit to attach the component to the mounting plate without a DIN rail.

Description Article Number
A fixing kit to attach the component to the mounting plate without a DIN rail. 276618

Cylinder Lock

For locking (stirrup Ø 3)

Description Article Number
For locking (stirrup Ø 3) 107115

Subject to technical modifications, dimensions, weights, construction types, and delivery possibilities. Figures are for indicative purposes only.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-b20-500-4-293887-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker, including features, electrical characteristics, environmental conditions, and dimensions. Suitable for explosion protection applications.
Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Line Protection Circuit Breaker Technical Data
Detailed technical specifications, features, and application information for the R. STAHL 8530/1-MCB-STA103-C25-500-4 line protection circuit breaker, including explosion protection data and electrical characteristics.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Line Protection Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C16-500-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and dimensions for the R. STAHL 8530/1-MCB-STA103-C16-500-4 circuit breaker, including explosion protection, electrical characteristics, and mounting information.
Preview R. STAHL 8530/1-MCB-STA103-C16-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C16-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for system solutions in hazardous environments.
Preview R. STAHL 8530/1-MCB-STA103-B16-500-4 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B16-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C16-000-3 Line Protection Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C16-000-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.