Product Overview

The R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breakers offer good current limitation for short circuits and high breaking capacity of 10, 15, or 25 kA. This results in lower stress on conductors and higher selectivity with upstream fuses. The modular design allows for 1- to 4-pole configurations and nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 modules (TE).

Key features include:

Technical Data

Explosion Protection

Parameter Value
Einsatzbereich (Zonen) 1, 2
Einsatzbereich (Zonen) Hinweis Usable in Zone 21 / 22 when protected by enclosure Ex tb / tc
IECEx Bescheinigung Gas IECEx FMG 19.0029U
IECEx Gasexplosionsschutz Ex db eb IIC Gb
ATEX Bescheinigung Gas FM19ATEX0191U
ATEX Gasexplosionsschutz II 2 G Ex db eb IIC Gb
Bescheinigungen ATEX (FM), Brasilien (ULB), IECEx (FM), Volksrepublik China (CQST)
Konformitätserklärungen Conformity certification (ATEX)

Electrical Data

Parameter Value
Bemessungsbetriebsspannung AC 230/400 V
Bemessungsbetriebsstrom 50 A
Frequenz 50/60 Hz
Bemessungsschaltvermögen 10 kA
Elektrische Lebensdauer 104
Mechanische Lebensdauer 2 x 104
Hilfsfunktion 1 changeover auxiliary contact + 1 fault signal auxiliary contact
Bemessungsspannung 1. Hilfsfunktion AC 230 V
Max. Bemessungsstrom 1. Hilfsfunktion 2 A
2. Hilfsfunktion -
Max. Spannung 2. Hilfsfunktion DC -
Auslösecharakteristik C
Polzahl 3-pole

Umgebungsbedingungen

Parameter Value
Umgebungstemperatur -40 °C ... 70 °C (-40 °F ... 158 °F)
Umgebungstemperatur Hinweis Deviating ambient temperatures are available upon request based on current certificates.

Mechanische Daten

Parameter Value
Schutzart (IP) (IEC 60529) IP2X
Gehäusematerial Thermoplast
Anschlussquerschnitt min. 1.5 mm²
Anschlussquerschnitt max. 25 mm²
Anschlussquerschnitt AWG min. 16 AWG
Anschlussquerschnitt AWG max. 4 AWG
Anschlussquerschnitt 2 min. 1.5 mm²
Anschlussquerschnitt 2 max. 10 mm²
Anschlussquerschnitt 2 AWG min. 16 AWG
Anschlussquerschnitt 2 AWG max. 8 AWG
Anschlussquerschnitt HIKO min. 0.5 mm²
Anschlussquerschnitt HIKO max. 4 mm²
Anschlussquerschnitt HIKO AWG min. 18 AWG
Anschlussquerschnitt HIKO AWG max. 14 AWG
Anzugsdrehmoment min. 2 N·m
Anzugsdrehmoment max. 3 N·m
Anschlussquerschnitt Hinweis 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16/10 mm² (A maximum cross-section difference between the upper and lower chamber can be clamped.) The permitted combination possibilities of the connection cross-sections can be found in the operating manual.
Breite 110 mm
Breite Zoll 4.33 in
Länge 165 mm
Länge Zoll 6.5 in
Einbautiefe 138.3 mm
Einbautiefe Zoll 5.44 in
Gewicht 1.8 kg (3.969 lb)

Montage / Installation

Parameter Value
Anzugsdrehmoment 2–3 N·m
Anzugsdrehmoment Ibf in 17.7 ... 26.6 lbf·in
Anzugsdrehmoment Hilfskontakt 0.4–0.6 Nm
Anzugsdrehmoment Hilfskontakt Ibf in 3.5 ... 5.3 lbf·in

Technical Drawings and Diagrams

Tripping Time Characteristic C: A graph shows tripping time in minutes and seconds versus multiples of the rated current (I/In). The curve indicates tripping behavior from a cold state for AC and DC.

Dimensional Drawings: Multiple views illustrate the dimensions of the circuit breaker in millimeters and inches. Key dimensions include width, length, and depth. The unit is shown as 8530/1; 4 division units.

Accessories

Abschließvorrichtung vierfach (Lock-out/Tag-out Device)

A lock-out/tag-out shear for individually locking the component using up to 4 padlocks.

Description Art. Nr.
Lock-out/Tag-out shear for individual locking of the component using up to 4 cylinder locks. 227232

Befestigungsset (Mounting Set)

A mounting set for attaching the component to the mounting plate without a top hat rail.

Description Art. Nr.
Mounting set for attaching the component to the mounting plate without a top hat rail. 276618

Zylinderschloss (Cylinder Lock)

For locking (shackle Ø 3).

Description Art. Nr.
For locking (shackle Ø 3) 107115

Contact Information

R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103-c50-500-4-293905-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C50-000-3 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103-C50-000-3 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and installation information.
Preview R. STAHL 8530/1-MCB-STA103-C32-500-4 Miniature Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C32-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-C25-500-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103-C16-500-4 - Technical Data and Features
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA103-C16-500-4. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-B16-500-4 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-B16-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103-C63-500-4 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C63-500-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103-C50-500-4 Line Protection Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103-C50-500-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.