General Information
- Compatible with R-32 VRF air, water, and mini systems.
- The indoor unit features an integral condensate pump with a maximum 29" lift from the bottom of the unit. It includes a check valve and float switch that disables the indoor unit in the event of condensate overflow.
- The indoor unit includes a built-in Wi-Fi adapter as standard, enabling control and monitoring using the Samsung SmartThings app.
Construction
Insulated, galvanized steel.
Refrigerant System
- The heat exchanger is constructed with mechanically bonded aluminum fins to copper tubes.
- Refrigerant flow is controlled by an electronic expansion valve located at the indoor unit.
- The indoor unit includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).
Indoor Fan
- Features smart pressure control that adjusts fan speed based on ESP, delivering consistent heating and cooling power.
- The indoor unit has a smart-tuning function that provides optimized comfort by allowing the occupant to adjust the fan CFM curve to increase or decrease airflow.
- The indoor unit includes automatic air volume scanning for simple setup and optimized comfort settings for the occupant.
Controls
- Control wiring requires 2 x 16 AWG wire.
- The unit is operated via a wired remote controller, model VSTAT04P-1, which must be purchased separately.
- Supports dual set temperature functionality when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality allows for configuration of fan operation during auxiliary heat, defrost, and emergency heat operations (requires VSTAT10P-1 accessory).
- External heat control configuration settings include: outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).
- Emergency heat functionality enables the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).
Convenience
- Features an Emergency Temperature Output (ETO) function: when the indoor unit is in an error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source, such as a backup system, building management system, or alert device (e.g., status light, warning lamp, buzzer).
Specifications
Model VHID054S6-5P
Parameter | Value |
---|---|
Indoor Unit Model Number | VHID054S6-5P |
Nominal Capacity (Cooling) | 54,000 Btu/h |
Nominal Capacity (Heating) | 61,400 Btu/h |
Voltage | 1 / 208-230 / 60 Hz |
Operating Current (max.) (Cooling) | 2.45 A |
Operating Current (max.) (Heating) | 2.45 A |
MCA | 4.3 A |
MOP | 15 A |
Type | BLDC (1) With Sirocco Fan (3) |
Consumption | 350 Watts |
Evaporator Fan External Static Pressure (Standard) | 0.20 "WC |
Evaporator Fan External Static Pressure (Min./Max.) | 0.12 / 0.59 "WC |
Airflow (Cooling) | 883 / 1,236 / 1,589 CFM (L/M/H/Turbo) |
Airflow (Heating) | 883 / 1,236 / 1,589 CFM (L/M/H/Turbo) |
Refrigerant Type | R-32 |
A2L Leak Detection | Integral |
Pipe Connections (High side) | 3/8 in. |
Pipe Connections (Low side) | 5/8 in. |
Condensate (W x H x D) | 51 3/16 x 11 13/16 x 27 9/16 in. |
Weight | 98.10 lbs. |
Duct Connections (Supply W x H) | 49 15/16 x 10 5/8 in. |
Duct Connections (Return ID) | 49 15/16 x 10 5/8 in. |
Sound Pressure Level (Low / Med. / High) | 35 / 39 / 43 dB(A) |
Safety Certifications | UL 60335-2-40 |
Accessories
VHID054S6-5P
- Filter box: V1FBX03-4P
- Wired controller (Advanced): VSTAT04P-1
- Wired controller (Touchscreen): VSTAT02P-1
- Thermostat adapter (for connection to standard 24VAC thermostats): VSTAT09P-1
- Wireless signal receiver: VCTRL10P-1
- Wireless signal control: VSTAT01P-1
- Wireless controller: VCTRL11P-1
- External temperature sensor: VSTAT10P-1
- External contact control interface module:
- CN83 Pigtail (for 12VDC VENT output): JV DB39-01263A CN83 Pigtail
Dimensional Drawing
Unit: Inches
The unit is a rectangular indoor unit with overall dimensions approximately 51 3/16 inches wide, 11 13/16 inches deep, and 27 9/16 inches high. It features an air inlet and an air outlet. The drawing details various connection points and openings for installation and operation.
No. | Description |
---|---|
1 | Liquid pipe connection (3/8 in.) |
2 | Gas pipe connection (5/8 in.) |
3 | Gravity Drain Connection |
4 | Drain Connection |
5 | Opening for Power and Communication Wire Conduit |
6 | Supply Air Outlet Flange |
7 | Return Air |
8 | Suspension Bolt Anchor Point |
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.
Related Documents
![]() |
Lennox VLOD009S6-5P VRF Low Static Ducted Unit Submittal Data Submittal data for the Lennox VLOD009S6-5P VRF Low Static Ducted Unit, detailing specifications, features, construction, and accessories. Compatible with R-32 VRF systems. |
![]() |
Lennox VMDD012S6-5P VRF Medium Static Ducted Submittal Data Submittal data for the Lennox VMDD012S6-5P VRF Medium Static Ducted indoor unit, detailing its specifications, features, accessories, and dimensions. Compatible with R-32 VRF systems and offers Wi-Fi connectivity via Samsung SmartThings app. |
![]() |
Lennox VHID030S6-5P VRF High Static Ducted Indoor Unit Submittal Data Submittal data for the Lennox VHID030S6-5P VRF High Static Ducted indoor unit, detailing specifications, features, construction, controls, and accessories. Compatible with R-32 VRF systems. |
![]() |
Lennox VVCD054S6-5P VRF Vertical Air Handler Submittal Data Technical specifications and submittal data for the Lennox VVCD054S6-5P VRF Vertical Air Handler, detailing performance, construction, controls, accessories, and dimensions. |
![]() |
Lennox VUCD036S6-5P VRF Ceiling Mount Submittal Data and Specifications Comprehensive submittal data and technical specifications for the Lennox VUCD036S6-5P VRF Ceiling Mount indoor unit, detailing performance, construction, controls, accessories, and dimensional information. |
![]() |
Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit Specifications Detailed submittal data and specifications for the Lennox V33D006S6-5P VRF 4-Way Cassette Indoor Unit, highlighting features like Calm Air mode, Wi-Fi connectivity, R-32 refrigerant compatibility, and external heat control. |
![]() |
Lennox VOWD007S6-5P VRF 1-Way Cassette Submittal Data and Specifications Detailed submittal data and specifications for the Lennox VOWD007S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance metrics, accessories, and dimensional details. |
![]() |
Lennox V36D030S6-5P VRF 360 Cassette Submittal Data and Specifications Detailed submittal data and technical specifications for the Lennox V36D030S6-5P VRF 360 Cassette indoor unit, including performance, construction, refrigerant, fan, controls, and accessories. |